R7M-RR8
P. 2 / 4
■I / O STATUS INDICATOR LED
Output and feedback input status are indicated with LED.
ON: LED on
OFF: LED off
■POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT
■
4
DA
567
123
DG
U(
+
)V(
–
)
DB SLD FG
(1) DB –
(2) SLD Shield
(3) FG FG
(4) DA –
(5) DG –
(6) U(+) Power input
(7) V(–) Power input
OUTPUT TERMINAL ASSIGNMENT
10
NC
11
Y0
12
Y1
1
NC
2
C0
3
C1
13
Y2
4
C2
14
Y3
5
C3
15
Y4
6
C4
16
Y5
7
C5
17
Y6
8
C6
9
C7
18
Y7
NO. ID FUNCTION NO. ID FUNCTION
1 NC No connection 10 NC No connection
2 C0 Common 11 Y0 Output 0
3 C1 Common 12 Y1 Output 1
4 C2 Common 13 Y2 Output 2
5 C3 Common 14 Y3 Output 3
6 C4 Common 15 Y4 Output 4
7 C5 Common 16 Y5 Output 5
8 C6 Common 17 Y6 Output 6
9 C7 Common 18 Y7 Output 7
■TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate.
(Factory setting OFF)
■EXTENSION MODULE
Combinations with all extension modules are available.
■STATUS INDICATOR LED
ID COLOR FUNCTION
PWR Red
Turns on when the internal 5V is supplied
normally.
RUN Red
Turns on when the refresh data is received
normally.
ERR Red
Turns on when the received data is abnormal.
SD Red
Turns on when the module is transmitting.
RD Red
Turns on when the module is receiving.
■NODE ADDRESS
Node Address is selected between 1 and 99 in decimal. The
left switch determines the tenths place digit, while the right
switch does the ones place digit of the address.
■
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Node Address Setting (x10)
BAUD RATE
Baud Rate is selected with the rotary switch.
■
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps
5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps
OPERATING MODE
•Extension (SW1-1, 1-2)
SW1-1 SW1-2 EXTENSION
OFF OFF No extension (*)
ON OFF Discrete input 8 or 16 points
OFF ON Discrete output 8 or 16 points
(*) Factory setting
Note : Be sure to set unused SW1-3 through 1-8 to OFF.
■PC CONFIGURATOR
The following parameters can be set with using PC Configu-
rator Software.
•Modbus parameters: Parity, bit length, stop bit
COMPONENT IDENTIFICATION
■ SIDE VIEW ■ FRONT VIEW
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
ERR RD
RUN SD
PWR X10 X1
NODE ADD. B.RATE
12345678
01234567
4567
123
10 11 12 13
2341
15 16 17 18
7896
14
5
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) I/O Status Indicator LED
(G) Modbus, Power Supply Terminals
(H) Output Terminals
( I ) Terminating Resistor SW
(A)
(G) (H)
(B) (C) (D) (E) (F)
01234567
CNFG.
INPUT OUTPUT
(I)Terminating Resistor SW
TERM
ON OFF