M-TI TST Series User manual

Website: www.metertreater.com
Meter Treater Inc.: 1349 South Killian Drive • Lake Park, FL 33403
Sales: 561.845.2007 Toll: Free: 800.638.3788 Fax: 561.848.2372
Email: sales@metertreater.com
MT-TSTSERIES-3/18
The TST Series of SPDs (surge protection devices) are designed to protect
sensitive electronic equipment from the harmful effects of transients.
Models are congured for both parallel or series installation and can be either
din rail or wall mounted. Units are rated as Type 2 SPDs component
assembly making the TST Series the ideal choice for incorporation into control
cabinets for sensitive microelectronic based equipment.
TST units are self-contained in rugged plastic enclosures and use twenty
millimeter (20mm) MOVs as their key suppression elements. Units are not
line load sensitive and interface with the incoming power cables via screw
terminals (barrier strips):
Small Terminals are capable of handling #14 to #30 AWG Wire.
Large Terminals are capable of handling #6 to #20 AWG Wire.
Product Specications
In
Max Surge Current
Fusing
Short Circuit Current
Short Circuit Current
Diagnostics
3kA
10 - 40kA/Phase (depending on model)
Internal (Thermal)
5kA Symmetrical w/external breaker
100kA Symmetrical w/external T Fuse
LED
Model Number Service Voltage Current Rating Surge Rating Case Size L1 - N L1 - G N - G
TST020/120-10-0-1/15A
TST020/250-10-0-1/30A
TST020/120-10-0-1/30A
TST040/120-10-0-1/15A
TST040/220-10-0-1/15A
TST040/250-10-0-1/15A
TST040/120-10-0-1/30A
TST040/220-10-0-1/30A
TST040/250-10-0-1/30A
TST010/024-2P-0-1/15A
TST010/048-2P-0-1/15A
TST020/024-2P-0-1/30A
TST020/048-2P-0-1/30A
120 Volts
250 Volts
120 Volts
120 Volts
250 Volts
250 Volts
120 Volts
250 Volts
250 Volts
24 Volts
48 Volts
24 Volts
48 Volts
600
1000
600
500
800
800
500
800
800
L1-N
200
200
200
200
15 Amp
30 Amp
30 Amp
15 Amp
15 Amp
15 Amp
30 Amp
30 Amp
30 Amp
15 Amp
15 Amp
30 Amp
30 Amp
20 kA
20 kA
20 kA
40 kA
40 kA
40 kA
40 kA
40 kA
40 kA
10 kA
10 kA
20 kA
40 kA
Small
Small
Small
Large
Large
Large
Large
Large
Large
Small
Small
Large
Large
VPR
Mechanical/Environmental Specications
Enclosure
Safety Standards (Type 2 SPD)
Operating Frequency
Max. Operatin Temp
Plastic (UL94-VO) Polycarbonate
ANSI/UL 1449 (most current)
50/60 Hz
-40° to +85° C
600
1000
600
500
800
800
500
800
800
L2-G
200
200
200
200
600
1000
600
600
800
800
600
800
800
L1-L2
200
200
200
200
Low Voltage ATL Listed 120V +
Dimensions Typical Installations
Commercial & Light Industrial
Surge Protection Devices
TST Series
(Diagrams not drawn to scale)
(3.485)(3.625)
(2.770)
(3.485)
(3.625)
(2.300)
(3.454)
(3.599)
(1.400)
(2.270)
(3.454)
(3.599)
Case M Large Case M Small
All product dimensions provided are ± 0.125

TST Series
Surge Protection
Device
SURGE PROTECTION DEVICES FOR
SERIES/PARALLEL APPLICATIONS
USER MANUAL AND
INSTALLATION GUIDE
WARRANTY INFORMATION
Meter-Treater, Inc. (MTI) warrants all TST Series models
to be free from defects, and will at our option repair or
replace the product should it fail within fteen (15)
years from the rst date of shipment. This warranty is
limited to defects in workmanship or materials, and does
not cover customer damage, abuse or unauthorized
modication. If this product fails or does not perform as
specied, your sole recourse shall be repair or
replacement as described above. Under no condition
shall MTI be liable for any damages incurred by the use
of this product. Damages include, but are not limited to,
the following: lost prots, lost savings and incidental or
consequential damages arising from the use of or inability
to use this product. MTI specically disclaims all other
warranties, expressed or implied, and the installation or
use of this product shall be deemed an acceptance of
these terms by the user.
WARRANTY RETURNS
All warranty and non-warranty repairs must be returned
freight prepaid and insured to MTI. All returns must have
a Return Authorization (RA) number on the outside of the
shipping container. This number may be obtained from MTI
Warranty Department (800) 342-6890. Products returned
without an RA number will not be accepted.
IF UNIT(S) ARE RECEIVED DAMAGED,
NOTIFY THE SHIPPING COMPANY
IMMEDIATELY. RETAIN ALL SHIPPING
CONTAINERS AND PACKING MATERIALS FOR
INSPECTION.
Meter-Treater, Inc.
1349 South Killian Drive • Lake Park, FL 33403
Phone: 561.845.2007 • Fax: 561.848.2372
Email: sales@metertreater.com
Website: www.metertreater.com
Please Note:
There are no user serviceable parts inside.
MT-TSTINSTALL-42017
GENERAL
1. This document provides detailed information on how
to install and operate the TST Series of Surge Protection
Devices (SPD).
2. Incorrect installation may signicantly impair the
performance of the SPD. It is particularly important that all
installation procedures and guidelines be followed exactly.
3. INSTALLATION OF THIS SPD SHOULD ONLY BE
PERFORMED BY A QUALIFIED INSTALLER
4. CHECK TO ENSURE THAT ALL CONNECTIONS ARE
CORRECT AND SECURE BEFORE ENERGIZING.
5. KEEP THIS MANUAL IN A SAFE, DRY PLACE FOR
FUTURE REFERENCE.
IMPORTANT SAFETY INSTRUCTIONS
NOTICE: All instructions and measurements must be
completed by a qualied electrician in accordance with
the National Electric Code and/or other applicable state
and local codes. The U.S. National Electric Code
and/or applicable state/local requirements supersede
these instructions.
CAUTION: HAZARDOUS VOLTAGES
PRESENT
Improper installation or misapplication of these SPD’s
may result in serious injury to the installer and/or damage
to electrical system(s) or related equipment. Read and
understand all instructions before commencing with the
installation. Appropriate personal protective equipment
should be worn during the installation process.
COMMERCIAL INSTALLATIONS

INSTALLATION INSTRUCTIONS FOR: NOTE
SPD’s must be connected to the electrical service with appropriate ampacity Class T Fuse, rated 300V. Equipment Safety
Grounds MUST be run separately - not through the traces of the Surge Protection Device.
WARNING
ANY ALTERATIONS, TAMPERING, MISUSE OR UNAUTHORIZED REPAIRS OF THIS SPD WILL VOID ITS
ORIGINAL FACTORY WARRANTY.
INSTALLATION
1. This document provides detailed information on how to install and operate the TST Series of Surge Protecion Devices (SPDs).
2. SPD’s should be installed per the information and illustrations provided herein.
3. SPD’s are installed/connected in either series or parallel with the line and the equipment to be protected.
4. Identied or indicated Leads/Wires must be connected exactly with respect to the power feeding/supplying the SPD and
equipment. Failure to do so may result in damage to the SPD, the equipment/system or pose a danger to personnel.
5. Incorrect installation may signicantly impair the performance of the SPD. It is particularly important that all installation
procedures and guidelines be followed exactly.
6. Prior to installation, verify service voltages (AC or DC) with a volt meter to ensure that the correct model has been
selected for the supply voltage.
7. DO NOT INSTALL THE SPD IF MEASURED VOLTAGE EXCEEDS UNIT RATINGS.
8. The SPD MUST BE mounted in an enclosure to assure personnel safety from exposed terminals.
9. REMOVE POWER FROM ELECTRICAL SYSTEM PRIOR TO INSTALLATION.
10. The SPD should be positioned as the last device in the circuit prior to protected equipment.
11. The SPD Line/Load designations are for orientation purposes only and do not eect the install.
12. Mechanically mount the SPD utilizing the mounting tabs or attach the din rail.
13. For Series (AC) Applications
A) Connect “LINE” Side:
* System Ground to the terminal labeled “G”
* Neutral or Line 2 wire to the terminal labeled “L2”
* HOT wire to the terminal labeled “L1”
B) Connect “LOAD” Side:
* System Ground to the terminal labeled “G” (connect safety ground directly to enclosure ground)
* Neutral or Line 2 wire to the terminal labeled “L2”
* HOT wire to the terminal labeled “L1”
14. For parallel (AC) Applications, keeping lead as short as possible
* System Ground to the terminal labeled “G”
* Neutral or Line 2 wire to the terminal labeled “L2”
* HOT wire to the terminal labeled “L1”
NOTE: In parallel applications, SPD’s are not current limited as they are in series applications. For parallel applications,
unused output terminals are left empty, no plugs are provided.
15. ENSURE THAT ALL CONNECTIONS ARE CORRECT BEFORE ENERGIZING.
16. Apply power (energize). LED indicator should illuminate. If light fails to illuminate, contact supplier. If LED is out, unit
requires service.
17. Keep this MANUAL in a safe dry place for future reference.
TST010/024-2P-F-1/15A
TST010/048-2P-F-1/15A
TST020/024-2P-F-1/30A
TST020/048-2P-F-1/30A
TST020/120-10-F-1/15A
TST020/250-10-F-1/30A
TST040/120-10-F-1/15A
TST040/250-10-F-1/15A
TST020/120-10-F-1/30A
TST040/120-10-F-1/30A
TST040/250-10-F-1/30A
WIRING DIAGRAMS
Series Installation
Line In
Line 2/N in
Ground
Ground out
Line 2/N out
Load out
Line 2/N out
Loud out Ground out
Line In
Line 2/N in Ground
Parallel Installation
Line In
Line 2/N in
Ground
Line In
Line 2/N in Ground
Note: Circuit Protection NOT required for neutral application. If two(2) hots
are used, a second interrupt device is required.
15Amp Models are capable of handling #12 to #30AWG Wire
30Amp Models are capable of handling #6 to #20AWG Wire
This manual suits for next models
13
Other M-TI Surge Protector manuals
Popular Surge Protector manuals by other brands

ICM Controls
ICM Controls ICM516 manual

M-system
M-system MDCAT-A Series instruction manual

Eaton
Eaton COOPER POWER UltraSIL VariSTAR Series installation instructions

Mersen
Mersen Surge-Trap instructions

MTL Surge Technologies
MTL Surge Technologies TP-P48 installation guide

Uniteck
Uniteck UNISPLIT 160.12 instruction manual