Magic-pac MHP4 Series User manual

506325-01 Page 1 of 18Issue 0941
Save these instructions for future reference
Improper installation, adjustment, alteration, service, or maintenance can cause injury
or property damage. Refer to this manual. For assistance or additional information,
consult a qualified installer or service agency.
WARNING
For your safety, do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or
any other appliance. Such actions could result in
property damage, personal injury, or death.
WARNING
These units are not approved for mobile home
applications. Such use could result in property damage,
personal injury, or death.
WARNING
The unit must be installed with approved wall sleeve and
grille accessories for safe operation. Improper installation
could result in property damage, personal injury, or death.
WARNING
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the
National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1,
CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having
jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence
over the general instructions in this manual.
CAUTION
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualified service personnel should install or service this
equipment. Installation and service performed by
unqualified persons can result in property damage,
personal injury, or death.
WARNING TABLE OF CONTENTS
INSTALLATION .................................................... 2
OPERATION ........................................................8
MAINTENANCE ................................................. 10
ACCESSORIES.................................................. 11
WIRING DIAGRAMS ..........................................14
Manufactured By
Allied Air Enterprises Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*506325-01*
Installation and Maintenance Instructions
MHP4 Series Self-Contained Heat Pump

Page 2 of 18 506325-01Issue 0941
INSTALLATION
General
These instructions explain the recommended method of
installation of the MHP4 heat pump unit and associated
electrical wiring.
This unit is designed and approved for use as a self-
contained air to air heat pump system.
These instructions, and any instructions packaged with
matingcomponentsand/oraccessories,shouldbecarefully
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
These instructions are intended as a general guide only, for
usebyqualifiedpersonnelanddonotsupersedeanynational
or local codes in any way. Compliance with all local, state,
provincial,ornationalcodespertainingtothistypeofequipment
should be determined prior to installation.
Inspection
Upon receipt of equipment, carefully inspect it for possible
shippingdamage. Ifdamageisfound, it should be noted on
the carrier’s freight bill. Take special care to examine the
unit inside the carton if the carton is damaged. File a claim
with the transportation company. If any damages are
discovered and reported to the carrier do not install the
unit, as claim may be denied.
Check the unit rating plate to confirm specifications are
as ordered.
Limitations
The unit should be installed in accordance with all national
and local safety codes.
Limitationsofthe unit andappropriateaccessories must also
be observed.
The outdoor fan is designed to operate against no more
than .10" W.C. static pressure.
Minimum and maximum operation conditions must be
observed to assure maximum system performance with
minimum service required. Refer to Table 1 for the
application limitations of the unit.
Location
For information on wall sleeves and grille accessories, see
ACCESSORIES beginning on page 11.
The design is certified for thru-the-wall or up-to-the wall
(insidewall)installationonly.Theinteriorportionsofthe unit
may be surrounded by a closet with clearances to
combustiblematerialheldto0"atthesides,top,and front of
the plenum. All servicing and cleaning of the unit can be
performedfrom thefront.If installedina closet orutilityroom,
provide 25" clearance in front for service if the door to the
room is not in line with the front of the unit (see Figure 1).
Accessibility clearances must take precedence over fire
protection clearances.
The outside of the unit may be flush with the face of the
exterior wall, and it should not be obstructed with trees,
landscape materials, or building structure. Unit can be
installedrecessedwithappropriatewallsleeve accessories.
There is no minimum clearance required on locating the
unit to an interior corner of a building.
Iftheunitisinstalledinaresidentialgarage, itmust belocated
orprotected to avoid physical damageby vehicles.The unit
must be installed so that no electrical components are
exposed to water.
Table 1
Application Limitations
Outdoor Ambient Air Temperature °F
Minimum DB Maximum DB
Cool Cool Heat
65 115 75
Indoor Ambient Air Temperature °F
Minimum Maximum
DB/WB DB DB/WB DB
62/57 50 90/72 80
Cool Heat Cool Heat
This unit must be installed level to allow for proper
drainage of the unit base pan and indoor drain pan.
CAUTION
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
WARNING

506325-01 Page 3 of 18Issue 0941
Side View
Minimum Clearances
Plenum
Exterior Wall
Wall Sleeve
(one each side)
Interior Wall
Clearances*
Mounting Strap
(one each side)
3/4" Plywood Riser
Floor
Platform (field supplied) - Must be level with sill plate of hole in exterior wall
Front of Unit
Sill Plate
4" Min.
Figure 1
Top View
Clearance to combustible materials is 0" at the side, top, and front of plenum. If accessibility clearances are greater
than clearances to combustibles, accessibility clearances take precedence.
The front of the unit must be accessible for service. If the unit is enclosed, providing a door or access panel opposite
the front of the unit is the preferred method of providing access. The door or access panel must be at least 30" wide
(centered on the unit) and as tall as the unit. If a return duct is not installed, in order to provide adequate return air the
minimum clearance required between the front of the unit and the door or access panel is 4" for 43" tall cabinets and 5"
for 48" and 56" tall cabinets.
IMPORTANT
The unit must be installed with approved wall sleeve and
grilleaccessories for safe operation. Improper installations
could result in property damage, personal injury, or death.
* With no return duct installed, minimum
clearances to the front of the unit are 4"
for 43" tall cabinets and 5" for 48" and 56"
cabinets. If a return duct is installed,
enough clearance must be provided for
the drain trap installation.
unit must be supported by platform.

Page 4 of 18 506325-01Issue 0941
Installing and Securing Unit to Wall Sleeve
1. Make sure the gaskets attached to the sleeve are not
damaged.
2. Verifydividerpanelispositioned properly.Figure3shows
the correct position for 48" and 56" tall units (flange
Wall Sleeve and Louver Grille Installation
Refer to installation instructions included with the wall sleeve
kit and the louver grille kit along with Figure 2 for guidance in
assembling and installing the wall sleeve and louver grille.
pointing up). For 43" tall units, the divider panel should
be positioned so the flange points down.
3. Place MHP4 unit into wall sleeve. Lift leading end of
unit and walk unit onto sleeve. Once in sleeve, lower
the unit into position. This prevents damage to the base
pads.Assure that the unit is level and completely seated
against the gaskets on the wall sleeve.
4. Use the two installation brackets to secure the unit to
the wall sleeve (see Figure 4). The units are shipped
with the brackets placed in the return air compartment.
Hookeachbracketinto the front edge of the wall sleeve
side. Position the bracket so it can be bent around the
front corner of the unit. Remove one of the two screws
in that position on the unit. Line up one of the holes in
the installation bracket with the screw hole and attach
the bracket to the unit with that screw. Make sure to
fasten tight enough that the seal is maintained.Trim off
excess bracket if applicable.
Figure 2
Wall Sleeve and Louver Kit Installed
NOTE: Platform must be
constructed so that it
is level with sill plate of
wallopening.
The sleeve is not intended as the sole support for the
unit. An additional support must be provided for
adequate support (see Figure 2).
CAUTION

506325-01 Page 5 of 18Issue 0941
Inspect the fit up of the unit to the wall sleeve. Verify
that the gaskets of the wall sleeve make a complete
seal to the unit paying particular attention to top and
bottom corners of unit to sleeve seal. Caulk if needed.
Ductwork
Ductwork should be designed and sized according to the
methods in Manual Q of theAir Conditioning Contractors of
America (ACCA).
Check unit air supply outlet for debris before making
ductwork connections.
It is recommended that supply and return duct connections
at the unit be made with flexible joints. If flexible ducts are
used, a 6" sheet metal starter collar is required.
The supply and return air duct systems should be designed
for the CFM and static requirements of the job (see Table 3
on page 6). They should not be sized to match the
dimensions of the duct connections on the unit. The
returnduct should besealedtothe unit casing andterminate
outside the space containing the unit.
Air Filter
All indoor return air must be filtered. A washable filter is
furnished with the unit, located in the return air opening. If
return duct is installed, provisions must be made to
accommodate filter servicing.
Securing Unit
Figure 4
Thefiltershouldbecleanedatleastthreetimesduring each
of the heating and cooling seasons, or more frequently if
unusualconditions are encountered. To clean the washable
filter, shake filter to remove excess dirt and/or useavacuum
cleaner. Wash filter in soap or detergent water and replace
after filter is dry. It is not necessary to oil the filter after
washing.
If an installation is made in which it is more desirable to
mountthefilter exterior to the unit, in thereturnduct work or
elsewhere, the washable filter can be used or replaced with
a disposable filter. If a disposable filter is used, use the
information provided in Table 2 when sizing the disposable
filter.
Installation
Brackets
Remove and replace screw to secure bracket
(one each side)
Figure 3
Positioning Divider Panel
Do not screw into the side of the drain pan, or into the
indoor coil or heat strip.
CAUTION
Minimum Required Surface Area
for Disposable Filters
Table 2
* 9 and 10 SEER models
Mode l Number Filter Area
MHP*12
MHP*18
MHP*24
MHP*30-36
192 square inches
288 square inches
384 square inches
480 square inches

Page 6 of 18 506325-01Issue 0941
Condensate Drain
Provisions must be made to properly drain the indoor and
outdoor drain pans of this appliance.
Indoordrainconnection:1/2"NPTto3/4"PVCfitting(schedule
40). Outdoor drain connection: 3/4" NPT to 3/4" PVC fitting
(schedule40). BothdrainsmustbetrappedasshowninFigure
5. The drain line should pitch gradually downward at least 1"
per 10' of horizontal run to open drain.
If local codes require the use of metal condensate lines, do
not thread metal fittings into the unit drain pan. A1/2" x 3/4"
threaded plastic nipple is available from the manufacturer as
Figure 5
Condensate Drain Installation
Use thread sealant on the threaded fittings. Install
threaded fittings by hand only. Do not over torque the
fittings.
Do not thread metal condensate fittings to unit drain
pan.
CAUTION
Blower Performance
Table 3
Blower
Speed
Medium/Low
0.1
External Static Pressure (in.w.c. w/filter)
Model
0.2 0.3 0.4 0.5
MHP4-9-12
MHP4-9-18
MHP4-9-24
MHP4-9-30
MHP4-9-36
MHP4-10-18
MHP4-10-24
MHP4-10-30
Medium/Low
Low
Medium/High
High
Low
Low
Low
Low
Medium/Low
Medium/Low
Medium/Low
Medium/High
Medium/High
Medium/High
Medium/High
High
High
High
High
450 440 425 400 370
700 690 680 650 600
810 800 790 770 730
940 920 875 850 810
620 600 580 560 535
840 820 785 750 700
975 940 870 825 760
1075 1000 930 880 800
750 720 680 650 620
1000 980 950 920 880
1100 1080 1050 1020 980
1270 1230 1200 1170 1130
450 440 425 400 370
700 690 680 650 600
810 800 790 770 730
940 920 875 850 810
630 620 610 580 550
900 890 850 800 750
1070 1030 1000 920 840
1220 1150 1100 1030 920

506325-01 Page 7 of 18Issue 0941
Electrical Connections
All wiring must be done in accordance with the National
Electrical Code (NEC), ANSI/NFPANo. 70 (latest edition);
Canadian ElectricalCode CSA C22.2Part 1 (latest edition);
orlocalcodes, where they prevail. Any alteration of internal
wiring will void certification and warranty.
Unitsare factory wiredfora 230 volt power supply. If power
supply is 208 volts, it will be necessary to change a wire
connectiononunittransformerfrom240voltterminalto208
volt terminal as shown on the wiring diagram.
Use wiring with a temperature limitation of 75°F minimum.
Run the 208 or 230 volt, 60 hertz electric power supply
through a fused disconnect switch to the control box of the
unit and connect as shown in the wiring diagram located on
the inside of the control access panel.
The unit must be electrically grounded in accordance with
localcodesor,intheabsenceoflocalcodes,withtheNational
Electrical Code ANSI/NFPANo. 70 (latest edition) or CSA
C22.2 Part 1 (latest edition).
PowersupplytotheunitmustbeNECClass1andmustcomply
with all applicable codes. Afused disconnect switch should
be field provided for the unit. The switch must be separate
from all other circuits. If any of the wire supplied with the unit
mustbereplaced,replacementwiremustbeofthetypeshown
on the wiring diagram. Electrical wiring must be sized to
minimum circuit ampacity marked on the unit. Use copper
conductors only. Each unit must be wired with a separate
branch circuit and be properly fused.
NOTE: Some MHP4 models require two separate power
supply circuits. See the unit wiring diagrams and rating
plates for specifications.
Thermostat
Theroomthermostatshouldbelocatedonaninsidewallwhere
it will not be subject to drafts, sun exposure, or heat from
electrical fixtures or appliances. Follow manufacturer’s
instructions enclosed with the thermostat for general
installation procedures. Color-coded insulated wires (#18
AWG) should be used to connect the thermostat to the unit.
a kit (see ACCESSORIES on page 11). Thread the 1/2"
end of the nipple into the unit drain pan and make the field
connection to the 3/4" end.
Fresh Air Intake (Fresh Air Models Only)
On fresh air capable models (designated by the FA in the
model number – 7MHP4-10-30FA-1), up to 5% fresh air is
drawn into the unit from outside when the indoor blower
comes on.
To access the fresh air intake feature, the threaded cap must
be removed from the fresh air intake pipe (see Figure 6). The
fresh air intake pipe is located at the rear of the unit return air
intake. When not in use, cap should be placed nearby in the
air intake area in case it is needed in the future.
Figure 6
Fresh Air Intake Pipe and Cap
Fresh Air Intake Pipe
Threaded Cap
The location of fresh air capable models must conform
to the requirements of National Fire Protection
Association NFPA No. 54 in regards to proximity of
forced air inlets to flue gas terminals. Improper
installation could result in personal injury or death.
WARNING

Page 8 of 18 506325-01Issue 0941
OPERATION
Sequence of Operation
Uponinitial “power up” to unit, there is a 3-minute time delay
to the compressor contactor (R to Y).Any 24V interrupt (R,
C) to the defrost control will initiate the
3-minute delay to the contactor.
Cooling
When the thermostat is in the cooling mode, the O circuit is
powered which energizes the reversing valve. Upon cooling
demand,thethermostatclosescircuit RtoYandG.ClosingR
to Y closes the unit contactor, starting the compressor and
outdoorfan.ThethermostatautomaticallyclosesRtoGcircuit
whichalsobringsontheindoorbloweratthesametime.Upon
satisfyingcoolingdemand, thethermostatwillopen theabove
circuitsandopenthemaincontactor,stoppingthecompressor
and outdoor fan. The unit is equipped with a time delay; the
blowerwillcontinuetooperatefor90secondswhich improves
system efficiency.
Heating
Upon heating demand, the thermostat closes circuit R to Y,
which closes the unit contactor, starting the compressor and
outdoorfan.Thereversingvalveisnotenergizedintheheating
mode.Thethermostatagainautomaticallybringsontheindoor
fan at the same time. The second stage of the thermostat
closescircuitRtoW,whichclosestheunitsequencers,bringing
theauxiliaryelectricheaton.Uponsatisfyingheatingdemand,
the thermostat opens the above circuits and stops unit
operation.
NOTE: The 7.2 and 10 kW heats strips offer a W1 and W2
thermostat connection.Taking advantage of the two heat strip
circuitsrequiresa3-stagethermostat(Yforheatpump,W1for
electric heat stage 1, and W2 for electric heat stage 2). If a 2-
stage thermostat is used, “pigtail” W1 and W2 wires together
when connecting the thermostat wires at the unit.
Defrost Cycle
Ifthe outdoorambient conditionsaresuchthat frost formson
the outdoor coil, the defrost control monitors the need for,
initiates, and terminates defrost cycles as necessary to
maintain system performance. The defrost control is time/
temperature initiated and temperature terminated with a
maximumdefrosttime(time-out)of10minutes.Timebetween
defrost cycles is preset at 60-minute intervals at the factory,
but can be field adjusted between 30, 60, or 90 minutes. To
field adjust time between defrost cycles, place defrost time
plug in the proper position (see Figure 8).
Defrostcontrolwill initiateadefrostcycleifthetime periodhas
elapsed and the defrost sensor sees a temperature below
freezing.At the start of a defrost cycle, the defrost control will
energizethereversingvalvesolenoid,shiftingthe reversing
valve and de-energizing the outdoor fan. The defrost relay
willalsoclose,energizingauxiliaryheat forincreasedcomfort
duringdefrost.Theunit will remain in defrost untilthedefrost
sensorhas determinedthatthefrost hasbeenremovedfrom
the coil or a 10-minute time period has elapsed.
The defrost control is also equipped with a set of pins to aid
in the troubleshooting of the defrost system (see Figure 8).
Figure 7
Defrost Control
x
30
60
90
TEST
NORM
DL
Y
NOPS
Defrost Jumpers
Figure 8

506325-01 Page 9 of 18Issue 0941
The following is a brief outline of the testing of the defrost
system.
1. Defrost sensor must be closed, 32°F or below. If
temperatures are such that the switch will not close,
jumperbetweendefrostsensorterminalson the defrost
control.
2. Start system in heating operation.
3. Jumpertestpins.A1/4"quick connect terminal crimped
onto a solid wire or brazing rod works well for a test
jumper. Closing test pins speeds up time interval by a
factor of 256.
gnitteSlortnoCtsorfeDemiTelcyCtseTtsorfeD
setunim03sdnoces7
setunim06sdnoces41
setunim09sdnoces12
After closing test pins and appropriate cycle time has
elapsed, the reversing valve should shift to defrost mode
and the outdoor fan should stop. After 2 seconds of defrost
operation, the reversing valve should shift back to heating
operation and the outdoor fan should start.
Quiet Defrost Feature
The defrost control in this appliance is equipped with a quiet
defrostfeature. WiththejumperpinsetattheDLYposition, at
the start of the defrost cycle, the defrost control will energize
thereversingvalvesolenoidandde-energizedtheoutdoorfan,
andde-energizethecompressorcircuitaperiodof10seconds.
The result is a much quieter defrost cycle.
All units have the jumper pin set at the NORM position.
PS1and PS2 terminals: Theseappliancesarenot equipped
witha pressureswitch intherefrigeration system. Therefore,
thejumper on theNOPSpinis factory installedand required.
System Performance
For maximum performance of this heat pump system, the
operating temperatures and pressures should be checked
and superheat determined at StandardARI test conditions
of 82°F outdoor – 80°F indoor dry bulb/67°F wet bulb. If
superheat measured deviates from the values given in
Table 4, refrigerant charge should be adjusted accordingly
for maximum performance.
Forreliableoperation,allMHP9A12models mustalways
have the jumper pin in the NORM position.
CAUTION
Suction Superheat
Table 4
Magic-Pak
®
Model
Suction Superheat
@ ARI Conditions
82° OD
80° IDDB/67° IDWB
MHP4-09-12
15-18
9-11
MHP4-09-18
MHP4-09-24
MHP4-09-30
MHP4-09-36
MHP4-10-18
MHP4-10-24
MHP4-10-30
17-19
11-13
23-25
8-10
16-18
24-26

Page 10 of 18 506325-01Issue 0941
MAINTENANCE
Periodic inspection and maintenance normally consists of
changing or cleaning filters and (under some conditions)
cleaning the coils.
Filter
Inspect the filter once a month. Replace disposable filter or
clean the washable filter as necessary (a minimum of three
timeseachheatingorcoolingseasonis recommended). Do
notreplace washable filter with a disposable filterunlessan
installationwasmade inwhichthefilterwas mountedexterior
to the unit.
Motors
The indoor and outdoor fan motors are permanently
lubricated and require no maintenance.
Outdoor Coil
Foreign material should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
clean.To clean the coil,removethe lower access paneland
blow out debris by using compressed air or water. Be sure
power to unit is shut off before using water to clean the
coil.
Care should be used when cleaning the coils so that
the coil fins are not damaged.
Outdoor Base Drain
Foreignmaterial shouldnotbe allowedtoclogthe drainhole.
Inspect and clear drain opening prior to heating season.
Disconnect all electrical power to the unit before
conducting any maintenance procedures. Failure to
disconnect the power could result in personal injury or
death.
WARNING

506325-01 Page 11 of 18Issue 0941
ACCESSORIES
2Thru-the-wallinstallationsonly
2
Kit No. Description Used With
Polypropylene Louver Kit (White) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24LVRPWHT-1
ALVRPWHT-2 Polypropylene Louver Kit (White) MHP4-10-30/MHP4-09-36
ALVRPSAN-1 Polypropylene Louver Kit (Sandstone) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPSAN-2 Polypropylene Louver Kit (Sandstone) MHP4-10-30/MHP4-09-36
ALVRPBGE-1 Polypropylene Louver Kit (Beige) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPBGE-2 Polypropylene Louver Kit (Beige) MHP4-10-30/MHP4-09-36
ALVRPTPST-1 Polypropylene Louver Kit (Toupestone) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPTPST-2 Polypropylene Louver Kit (Toupestone) MHP4-10-30/MHP4-09-36
MHP4-10-30/MHP4-09-36
MHP4-10-30/MHP4-09-36
ALVRAL-1
Extruded Aluminum Louver Kit
Extruded Aluminum Louver Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 &24
ALVRAL-2
ALVRAL-3 Extruded Aluminum Louver Kit (45” Height) MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ALVRAL-4 Extruded Aluminum Louver Kit (45” Height) MHP4-10-30/MHP4-09-36
ALVRAL-5
ALVRAL-6
Extruded Aluminum Louver Kit (50” Height) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
Extruded Aluminum Louver Kit (50” Height)
Wall Sleeve Kit (45” Louver) MHP4-09-12 & 18
ASLEEVE-3
ASLEEVE2-2
ASLEEVE2-1 2” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30MHP4-10-18 & 24
ASLEEVE6-2
2” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE6-1 6” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ASLEEVE8-1
6” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE10-2
8” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ASLEEVE8-2 8” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE10-1 10” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
10” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE12-1 12” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ASLEEVE12-2 12” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE6-3 6” Wall Sleeve for 45” Louver
6” Wall Sleeve for 45” Louver
MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE6-4 MHP4-10-30/MHP4-09-36
ASLEEVE8-3 8” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-010-18 & 24
ASLEEVE8-4 8” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
ASLEEVE10-3 10” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE10-4 10” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
ASLEEVE12-3 12” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE12-4 12” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
AFILTMP-1 Outdoor Coil Filter Kit All Models
AADAPTPVC412-1 Threaded PVC Nipple All Models

Page 12 of 18 506325-01Issue 0941
Wall Sleeve Dimensions (in.)
* Thru-the-wall installations only
1-6EVEELSA6928/1-928/1-92
2-6EVEELSA64/3-238/7-238/1-92
3-6EVEELSA 6548/1-548/1-92
4-6EVEELSA
1-8EVEELSA8928/1-928/1-92
2-
8EVEELSA84/3-238/7-238/1-92
3-8EVEELSA 8548/1-548/1-92
4-8EVEELSA
1-01EVEELSA01928/1-928/1-92
2-01EVEELSA014/3-238/7-238/
1-92
3-01EVEELSA 01548/1-548/1-92
4-01EVEELSA
1-21EVEELSA21928/1-928/1-92
2-21EVEELSA214/3-238/7-238/1-92
3-21EVEELSA 2
1548/1-548/1-92
4-21EVEELSA
*3-EVEELSA*548/1-548/1-92
.oNtiKABCD
928/1-928/1-92
ASLEEVE2-2
ASLEEVE2-1
2
2
4/3-23 8/7-23 8/1-92

506325-01 Page 13 of 18Issue 0941
NOTE: Bottom surface of wall opening must be at least 4" off the floor.
29
16
Range of
Wall Thickness
16
B
1
A
C
D
Required Wall Opening
12
/
58
/
The unit must be installed with approved wall sleeve and
grille accessories for safe operation. Improper installations
could result in property damage, personal injury, or death.
WARNING

Page 14 of 18 506325-01Issue 0941
Figure 12
Connection Diagram
#537246-01

506325-01 Page 15 of 18Issue 0941
Figure 13
Schematic Diagram
#537246-01

Page 16 of 18 506325-01Issue 0941
Figure 14
Connection Diagram
Part #46358-005

506325-01 Page 17 of 18Issue 0941
Figure 15
Schematic
Part #46358-005

Page 18 of 18 506325-01Issue 0941
NOTES
Table of contents
Popular Heat Pump manuals by other brands

Daikin
Daikin Altherma M ECH2O Series Installation and maintenance instructions

Bryant
Bryant 548J*D Series installation instructions

Bard
Bard SH431 installation instructions

Daikin
Daikin EKHHE200CV37 User, installation, and maintenance manual

Ingersoll-Rand
Ingersoll-Rand ENL 5 Vario Instructions for installation and operation

Allied
Allied 4HP17L installation instructions

Olimpia splendid
Olimpia splendid MAESTRO SMART 9HP Service manual

Bard
Bard WH422D installation instructions

Panasonic
Panasonic WH-UX09FE5 operating instructions

Lennox
Lennox 13HPX installation instructions

Samsung
Samsung RC090MHXEA installation manual

Ochsner
Ochsner AIR BASIC 211 T201 OPERATING AND INSTALLATION Manual