Magic-Pak V Series User manual

Page 1 of 21507389-01 Issue 1504
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Installation and service must be performed by a licensed professional
installer (or equivalent), service agency or the gas supplier.
WARNING
If these instructions are not followed exactly, a fire or
explosion may result causing property damage, personal
injury, or loss of life.
CAUTION
These units are not approved for mobile home applicaons.
Such use could result in property damage, personal injury,
or death.
WARNING
Do not store combusble materials near the furnace or
warm air ducts. The material may ignite by spontaneous
combuson creang a re hazard.
WARNING
For your safety, do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any
other appliance. Such actions could result in property
damage, personal injury, or death.
WARNING
Installaon shall be made in accordance with the requirements of the local ulity and other authories having jurisdicon, or with
the Naonal Fuel Gas Code, ANSI Z223.1 (latest edion) and the Naonal Electrical Code in the United States or CAN/CGA-B149.1 &
.2 and the Canadian Electrical Code CSA C22.1 Part 1 (latest edion) in Canada. Any alteraon of internal wiring will void cercaon
and warranes.
CAUTION
Save these instrucons for future reference
HWC9 V-SeriesTM Models
INSTALLATION INSTRUCTIONS
TABLE OF CONTENTS
INSTALLATION-----------------------------------------------------2
START-UP--------------------------------------------------------- 11
OPERATION-------------------------------------------------------12
MAINTENANCE--------------------------------------------------12
WIRING DIAGRAMS--------------------------------------------20
Manufactured By
Allied Air Enterprises LLC
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*P507389-01*
*P507389-01*

Page 2 of 21 507389-01Issue 1504
install the union and manual shuto valve as well as providing
accessibility for eld wiring. Do not install directly on carpeng,
le, or other combusble material other than wood ooring.
The grille side of the unit may be ush with, or extend beyond, the
face of the exterior wall, but should not be recessed more than
2” from the face of the building and should not be obstructed
with trees, landscape materials, or building structure.
There is no minimum clearance required on locang the unit to
an interior corner of a building.
If the unit is to be enclosed, provisions should be made allowing
access to the indoor side of the unit for changing lters and for
inspecon. At least 29” of unobstructed space should be provided
in front of the indoor side, whether enclosed or not, to permit
removal of the cooling chassis should repairs or inspecon be
required.
If the unit is installed in a residenal garage, it must be located
or protected to avoid physical damage by vehicles. Unit must be
installed so the burners and ignion source are not less than 18”
(457 mm) above the oor. This unit must be installed so that no
electrical components are exposed to water.
This appliance should be installed in a locaon such that the vent
outlet is located in the following manner:
1. Distances to windows that open, building openings, or public
walkways should be consistent with the Naonal Fuel Gas
Code Z223.1 or CAN/CGA-B149.1 & .2.
2. For U.S. installaons, the vent system shall terminate a
minimum horizontal clearance of 4’ from electric meters,
regulators, and relief equipment. For installaons in Canada,
refer to the current CAN/CGA-B149.1 & .2 or with the
authories having local jurisdicon.
3. Flue products will not cause degradation to building
materials.
This furnace design is not listed for installaon in mobile homes,
recreaonal vehicles, or outdoors.
Use of Furnace as a Construcon Heater
Allied Air does not recommended the use of these units as a
construcon heater during any phase of construcon. Very low
return air temperature, harmful vapors and operaon of the unit
with clogged or misplaced lters will damage the unit.
Units may be used for heang of buildings or structures under
construcon, if the following condions are met:
• The Unit must be permanently installed per these installaon
instrucons.
• A room thermostat must control the furnace. The use of xed
jumpers that will provide connuous heang is not allowed.
• The return air duct must be provided and sealed to the
furnace.
Location
The design is cered for indoor installaon only. The interior
porons of the unit may be surrounded by a closet with
clearances to combusble material held to 0” sides, 2” top, and
1” front and plenum. Adequate clearance must be provided to
INSTALLATION
General
These instrucons must be hung on or near the furnace in a
conspicuous place.
The HWC9 V-Series™ units are self-contained, gas-red heang
with electric cooling models. The unit design has been cered by
Intertek Tesng Services for compliance with the latest edion of
the American Naonal Standard – ANSI Z21.47/Naonal Standard
of Canada – CAN/CGA-2.3 for direct vent central furnaces. The
HWC9 models are cered to be in compliance with the latest
edion of A.H.R.I. Standard 390. All models are design cered
for heang operaon when red with natural or propane gas.
These installaon instrucons are intended as a general guide
only, for use by an experienced, qualied contractor.
Inspection
The unit is shipped in one package, completely assembled and
wired. The Evaporator drain tubing is in the cooling compartment
behind the lter access panel. Fings for furnace condensate
drainage are located in the hardware kit bag.
If any damage is found, proper notaon should be made on the
carrier’s freight bill. Damage claims should be led with the
carrier as quickly as possible.
Check the rang plate to conrm heang and cooling capacies.
The unit should be operated only with the type of gas and
electrical supply noted on the rang plate.
IMPORTANT: Remove the chassis hold down shipping bracket
before installaon. These brackets are located on the outdoor
side of the unit below the louver panels.
In the State of Massachuses:
This product must be installed by a licensed Plumber or Gas
Fier. When exible connectors are used, the maximum
length shall not exceed 36”. When lever-type gas shutos
are used, they shall be T-handle type.
WARNING
Install operate and maintain unit in accordance with
manufacturer’s instrucons. The State of California has
determined that this product may contain or produce
chemicals, in very low doses, which may cause serious
illness or death. it may also cause cancer, birth defects or
reproducve harm.
WARNING

Page 3 of 21507389-01 Issue 1504
The sleeve is not intended as the sole support for the unit.
An addional support must be provided near the return
opening on the unit for adequate support. The use of
vibraon isolaon material between the unit and the support
is recommended.
CAUTION
Seal the space between the wall sleeve and the building opening
with non-hardening caulking compound. The seal must be
weatherght to prevent entrance of moisture and water into
the building.
Assure that the unit is completely seated against the gaskets on
the wall sleeve.
• Return air temperature range between 60°F (16°C) and 80°F
(27°C) must be maintained.
• Air lters must be installed in the system and must be
maintained during construcon.
• Air lters must be replaced upon construcon compleon.
• The input rate and temperature rise must be set per the
furnace rang plate.
• One hundred percent (100%) outdoor air must be provided
for combuson air requirements during construcon.
• The furnace heat exchanger, components, duct system, air
lters and evaporator coils must be thoroughly cleaned
following nal construcon clean-up.
• All furnace operang condions (including ignion, input
rate, temperature rise and venting) must be verified
according to these installaon instrucons.
Installing With a Wall Sleeve
Refer to the installaon instrucons packed with the wall sleeve
and Figure 1 for guidance in assembly and mounng using a
wall sleeve.
Make sure the gaskets aached to the sleeve are not damaged.

Page 4 of 21 507389-01Issue 1504
Figure 1
HWC Installaon
Plywood
28" Min.
Wall Sleeve
Vibration Isolating Material
FLO
O
R
6 x 22 Minimum Opening
to Align with Return Air
Opening in Unit.
""
Figure 2
HWC Evaporator Condensate Drain Installaon
Drain Pan
Open Drain Trap
Return
Air Duct
To Open
Drain Trap
Alternative
Method
5/8
" I . D.
Plastic Tube
(Supplied)
Top of Drain Tube
Must be Below
Bottom of Drain Pan
Drain Tube - Pitch 1"
for every 10 ft.
(Field Supplied)
Evaporator Condensate Drain
Install the plasc drain tube (furnished) over the 5/8” O.D. ng
in the center of the Evaporator condensate pan. Connect other
end of the drain tube to the open trap (see Figure 2). The plasc
drain connecon is provided so that it may be disconnected from
the permanent drain tubing in the building in the event it becomes
necessary to remove the cooling chassis assembly.
The drain line should pitch gradually downward at least 1” per
10’ of horizontal run to the open drain trap.
Be certain that the plasc drain tube has free drainage and is not
crimped or aened at any bend.
Installing Without a Wall Sleeve
Refer to the following direcons and Figure 1 for guidance in
installing the unit without a wall sleeve:
1. Measure the size of the unit and provide an opening in an
outside wall that will accept the unit. Local ordinances may
require a steel lintel to support the wall above the opening.
The opening must be square in all four corners.
2. Posion the unit so that the grilles on the outside face of the
unit are ush or extend beyond the face of the exterior wall,
but not recessed more than 2” from the face of the building.
Provide a support under the unit, inside the building. Make
sure that the inside support does not block the return air.
The unit should be installed level or pitched slightly to the
outside of the building so that rain water will drain away.
3. Seal the space between the unit and building opening using
a non-hardening caulking compound. The seal must be
weatherght to prevent entrance of moisture and water into
the building. Make sure the drain holes in the base are not
plugged with caulking.

Page 5 of 21507389-01 Issue 1504
Condensate
Trap
Side panel
Upper Drain hose
(From Collector box)
Lower drain hose
(To drain tting)
Drain tting
Figure 3
read street elbow into
drain tting solvent weld
piping to street elbow
Furnace condensate drain component locaons - Side exit
Condensate
Trap
Side panel
Upper Drain hose
(From Collector box)
Lower drain hose
(To drain tting)
reposition and reconnect
Drain tting
repositioned to front
Figure 4
Grommet plug
(Remove from access panel
and use here)
Furnace condensate drain component locaons - Front exit
read hose barb
into drain tting

Page 6 of 21 507389-01Issue 1504
Furnace Condensate Drain
The HWC9 furnace is provided with an internal condensate
drain and drain ng. A street elbow and a hose barb for con-
necon to the drain ng are factory-supplied in the manual
bag. All other piping is eld-supplied to suit the installaon and
local codes.
Units are shipped with the drain ng installed for side-exit
condensate drainage. The drain ng can be reposioned for
front-exit condensate drainage if desired. Do not relocate or re-
move the internal condensate trap.
If unit will be started immediately upon compleon of installa-
on, the drain must be primed as described in the procedure
outlined in the “Start-up” secon.
Field-installed piping from the furnace must slope downward a
minimum of 1/2” per foot toward the oor drain.
Piping for Side-Exit Condensate Drain
Determine whether the installaon beer suits a side-exit or a
front-exit furnace condensate drain. For side condensate drain,
see Figure 3 for component locaons and addional details. A
2” clearance to the cabinet side is required for service access to
the condensate drain ng when using the side locaon.
1. Aach the factory-supplied street elbow to the drain ng
by threading into place. Use a thread sealant suitable for
PVC; do not use thread tape.
2. Use the appropriate primer and solvent cement to bond
eld-supplied drain line piping or ngs to the PVC street
elbow.
Do not use copper tubing or exisng copper conden
sate
lines for drain line.
3. Route the piping to an open oor drain.
Piping for Front-Exit Condensate Drain
For front condensate drain, see Figure 4 for component loca-
ons and addional details. Use the factory-supplied hose barb
with eld-supplied exible tubing for these installaons. A 4”
clearance to the cabinet front is required for service access
when using the front locaon. The modicaons necessary to
convert to front-exit condensate drain are:
1. Disconnect the lower drain hose from the drain ng.
2. Remove the screw securing the drain ng to the division
panel.
3. Remove the drain ng and rotate it so that it faces the
front of the furnace.
4. Replace the securing screw.
5. Disconnect lower drain hose from drain trap and rotate the
hose so that the angled end will connect to the drain ng
in its new orientaon.
6. Reconnect the lower drain hose to the drain trap and drain
ng.
7. Remove the grommet plug from the front access panel and
insert it into the oval opening in the side panel.
8. Remove the perforated insulaon from inside the front
access panel around the oval opening. Be sure the area is
clean and free of insulaon and glue, as it will be used as a
sealing surface for the drain ng gasket.
9. Prior to seng the unit into operaon, replace the access
panel.
10. Aach the factory-supplied hose barb to the drain ng
by threading into place.
Use a thread sealant suitable
for
PVC; do not use thread tape.
11. Ax a suitable length of exible tubing to the hose barb
and route to an open oor drain. Secure the end of the
tubing to the drain.
COMBUSTION AIR
This unit is a direct-vent furnace which obtains all air needed
for combuson from outdoors.
Venting
The venng system is an integral part of the appliance. The
venng system must not be modied or added on to.
The unit contains a combuson inducer. The inducer draws the
combuson products out of the heat exchanger and forces them
from the unit to the outside. No special provisions are required
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
WARNING

Page 7 of 21507389-01 Issue 1504
Never use a ame to check for gas leaks. Explosion causing
injury or death may occur.
CAUTION
for supplying air for combuson, nor is a chimney required.
The vent outlet must not be altered or extended.
The venng system is designed for proper operaon under all
weather condions and for winds up to 31 m.p.h.
Removal of Unit from Common Venng System
When an exisng furnace is removed from a common venng
system serving other appliances, the venng system is likely to be
too large to properly vent the remaining aached appliances. The
following test should be conducted with each appliance while
the other appliances connected to the common venng system
are not in operaon.
1. Seal any unused openings in the common venng system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restricon, leakage, corrosion, or other deciencies which
could cause an unsafe condion.
3. Insofar as is praccal, close all building doors and windows
between the space in which the appliances remaining
connected to the common venng system are located and
other spaces in the building. Turn on clothes dryers and any
appliance not connected to the common venng system.
Turn on exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace dampers.
4. Following the lighng instrucons, place the unit being
inspected in operation. Adjust the thermostat so the
appliance will operate connuously.
5. Test for spillage at the dra control relief opening aer 5
minutes of main burner operaon. Use the ame of a match
or candle.
6. Follow the preceding steps for each appliance connected to
the common venng system.
7. Aer it has been determined that each appliance remaining
connected to the common venng system properly vents
when tested as outlined above, return doors, windows,
exhaust fans, replace dampers, and any other fuel burning
appliance to their previous condion of use.
8. If improper venng is observed during any of the above tests,
the common venng system must be corrected. See Naonal
Fuel Gas Code, ANSI Z223.1 (latest edion) or CAN/CGA
B149.1 & .2 Canadian Installaon Codes to correct improper
operaon of common venng system.
Gas Connecons
The gas line to the unit should be adequately sized to prevent
undue pressure drop and should never be smaller than the
manual valve used. Consult the local ulity or Naonal Fuel Gas
Code for complete details on special requirements in sizing gas
piping.
The units supplied for operaon with natural gas contain a
gas regulator which must be operated with inlet gas pressures
specied on the rang plate. If gas line pressure exceeds this
gure, an addional high pressure regulator must be installed
to reduce this pressure.
Units for operation with propane must be converted with a
kit supplied by the manufacturer and require for operaon an
inlet pressure of 11” W.C. minimum and 13” W.C. maximum. A
regulator is also required on the propane tank.
If local codes allow use of a exible gas connector, a new listed
connector must be used. Do not use a connector which has
previously serviced another gas appliance.
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
CAUTION
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
IMPORTANT

Page 8 of 21 507389-01Issue 1504
Electrical Connecons
All wiring must be done in accordance with the National
Electrical Code, ANSI/NFPA No. 70 (latest edion); Canadian
Electrical Code Part 1, CSA C22.1 (latest edion); or local codes,
where they prevail. Any alteraon of internal wiring will void
cercaon and warranty.
A manual shuto valve must be located outside the unit. The use
of a union located upstream of the controls is recommended,
between the controls, and the manual shuto valve. This will
facilitate removal of controls and manifold. See Figure 5 for
recommended placement of the union.
Provide a drip leg in the supply piping located exterior to the
unit. Piping must be ght and non-hardening. Pipe compound
resistant to propane must be used.
The rang plate indicates the operang voltage, phase, minimum
circuit ampacity, maximum fuse size, and minimum voltage.
Units must never be installed where voltage exceeds 10% over
the voltage indicated on the rang plate.
Units are factory wired for a 230 volt power supply. If power
supply is 208 volts, it will be necessary to change a wire
connection on unit transformer from 240 volt terminal to 208
volt terminal as shown on the wiring diagram.
Failure of the compressor as a result of operation on
improper voltage voids the compressor replacement
warranty.
A separate electric line with wire having a temperature rating
of 60°C should be run directly from the main supply panel
to the leads in the unit. Refer to the rating plate located on
the unit for proper fuse or breaker size. Make sure the unit
is electrically grounded in accordance with local codes or,
in the absence of local codes, with the National Electrical
Code, ANSI/NFPA No. 70 (latest edition) for installations in
the U.S. or the Canadian Electrical Code Part 1, CSA C22.1
(latest edition) for installations in Canada.
See rating plate for correct wire ampacity for the cooling
chassis required, and size wire accordingly.
The furnace must be isolated from the gas supply piping system by closing the individual manual shuto valve during any pressure
tesng of gas supply piping system at test pressures equal to or less than 1/2 psig or 14” W.C. If the piping system is to be tested at
pressures in excess of 1/2 psig, the furnace and its individual shuto valve must be disconnected from the gas supply piping system.
The gas valve supplied with this furnace is rated at 1/2 psig. Any higher pressure may rupture the pressure regulator diaphragm
which will cause overring of the burners and improper burner operaon. This acon may produce a high concentraon of carbon
monoxide which can result in asphyxiaon.
WARNING
Figure 5
Gas Supply Piping
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and service
to protect the furnace’s electronic controls. Precautions
will help to avoid control exposure to electrostatic
discharge by putting the furnace, the control and
the technician at the same electrostatic potential.
Neutralize electrostatic charge by touching hand and
all tools on an unpainted unit surface, such as the gas
valve or blower deck, before performing any service
procedure.
CAUTION
Leak Check
After gas piping is completed, carefully check all piping
connections (factory and eld installed) for gas leaks. Use
a leak detecting solution or other preferred means.
NOTE: If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect the main power to the
furnace. The installer should properly label these devices.
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after
leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
CAUTION

Page 9 of 21507389-01 Issue 1504
x3600 x
=Cubic Feet Per RevoluonBTU/HR
INPUT # Seconds Per Revoluon
Heang
Value
Supply and Return Duct(s)
Provide duct(s) sized suciently to handle the larger of the air
volumes for heang or cooling provided by this model.
Connect the supply duct to the top of the unit using canvas
connections or other flexible connections to prevent noise
transmission into the duct system.
To connect the return duct to the system, use a straight piece
of duct 22” wide by 6” deep. Insert the duct into the return
opening in the boom of the unit and ange the duct over the
exisng anges around the opening inside the unit. Make sure
that all sides of the duct are anged over to permit removal of
the cooling chassis if required. Use a exible connecon to aach
the remainder of the return duct. The return duct should be
sealed to the unit casing and must terminate outside the space
containing the furnace.
Adjustments – Heang Secon
Temperature Rise
At me of installaon, the temperature rise must be adjusted to
be within the range specied on the unit rang plate. See Table 2.
Pressure Regulator
The gas input must not exceed the gures shown on the rang
plate. The unit is equipped for rated inputs with manifold
pressures of: 3.5” W.C. for natural gas and 10.0” W.C. for
propane.
The manifold pressure can be measured by removing the pipe
plug in the automac gas valve. Connect a water manometer and
measure the pressure.
Only small variaons in gas input may be made by adjusng the
regulator. In no case should the nal manifold pressure vary
more than 0.3” W.C. for natural gas or 0.7” W.C. for propane.
To adjust the regulator, turn the adjusng screw on the regulator
clockwise to increase pressure and input or counterclockwise to
decrease pressure and input.
For natural gas installaons, check the burner rate by observing
the gas meter (making sure that all other gas appliances are
turned o). The test hand on the meter should be med for
at least one revoluon. Note the number of seconds for one
revoluon.
Adjustments – Cooling Secon (HWC models)
No adjustments are required or should be aempted regarding
any of the components of the cooling chassis. The chassis should
be checked to see that none of the wiring is loose or missing.
Cooling chassis is charged with R410A refrigerant.
Model
Number
Filter Area
(sq. in.)
HWC9-12 300
HWC9-18 480
HWC9-24 480
HWC9-30 480
Minimum Required Surface Area
for Disposable Filters
Table 1
Thermostat
Install the thermostat according to the direcons furnished with
it. The thermostat must be located on an inside wall where it will
not be aected by dras, sunlight, or any other heat producing
appliances. Connect the thermostat wires to the low voltage
leads on top of the unit following the wiring diagram aached
to the unit. The heat ancipator seng is 0.50 amp.
Air Filter
All indoor return air must be ltered. A permanent-type lter is
furnished with the unit, located directly behind the access panel.
Removing the panel permits access to the lter. See Figure 5.
If an installaon is made in which it is more desirable to mount the
lter exterior to the unit, in the return duct work or elsewhere, the
permanent lter can be used or replaced with a disposable lter.
If a disposable lter is used, refer to the informaon provided in
Table 1 when sizing the disposable lter.

Page 10 of 21 507389-01Issue 1504
SCFM
Temp
Rise
(F°)
SCFM
Temp
Rise
(F°)
SCFM
Temp
Rise
(F°)
SCFM
Temp
Rise
(F°)
TAP 1 (HEAT) * 208 or 230 455 42 415 46 385 50 355 54
TAP 2 (HEAT) 208 or 230 570 34 540 36 510 38 485 40
TAP 3 (HEAT) 208 or 230 655 29 625 31 595 32 575 33
TAP 4 (COOL) 208 or 230 410 370 340 305
TAP 5 (COOL) 208 or 230 455 415 385 355
TAP 1 (HEAT) 208 or 230 455 63 415 N/A 385 N/A 355 N/A
TAP 2 (HEAT) * 208 or 230 570 50 540 53 510 56 485 59
TAP 3 (HEAT) 208 or 230 655 44 625 46 595 48 575 50
TAP 4 (COOL) 208 or 230 410 370 340 305
TAP 5 (COOL) 208 or 230 455 415 385 355
TAP 1 (HEAT) * 208 or 230 630 45 600 48 570 50 550 52
TAP 2 (HEAT) 208 or 230 770 37 740 39 715 40 690 42
TAP 3 (HEAT) 208 or 230 885 32 855 34 830 35 810 35
TAP 4 (COOL) 208 or 230 605 575 545 520
TAP 5 (COOL) 208 or 230 650 615 585 555
TAP 1 (HEAT) 208 or 230 630 61 600 64 570 N/A 550 N/A
TAP 2 (HEAT) * 208 or 230 770 50 740 52 715 54 690 56
TAP 3 (HEAT) 208 or 230 885 43 855 45 830 46 810 47
TAP 4 (COOL) 208 or 230 605 575 545 520
TAP 5 (COOL) 208 or 230 650 615 585 555
TAP 1 (HEAT) 208 or 230 630 N/A 600 N/A 570 N/A 550 N/A
TAP 2 (HEAT) 208 or 230 770 61 740 64 715 66 690 68
TAP 3 (HEAT) * 208 or 230 885 53 855 55 830 57 810 58
TAP 4 (COOL) 208 or 230 605 575 545 520
TAP 5 (COOL) 208 or 230 650 615 585 555
TAP 1 (HEAT) * 208 or 230 645 44 615 47 590 49 565 51
TAP 2 (HEAT) 208 or 230 780 37 755 38 730 39 710 40
TAP 3 (HEAT) 208 or 230 900 32 875 33 855 34 835 34
TAP 4 (COOL) 208 or 230 800 775 755 735
TAP 5 (COOL) 208 or 230 880 860 835 815
TAP 1 (HEAT) 208 or 230 645 59 615 62 590 65 565 N/A
TAP 2 (HEAT) * 208 or 230 780 49 755 51 730 52 710 54
TAP 3 (HEAT) 208 or 230 900 43 875 44 855 45 835 46
TAP 4 (COOL) 208 or 230 800 775 755 735
TAP 5 (COOL) 208 or 230 880 860 835 815
TAP 1 (HEAT) 208 or 230 645 73 615 N/A 590 N/A 565 N/A
TAP 2 (HEAT) 208 or 230 780 61 755 63 730 65 710 67
TAP 3 (HEAT) * 208 or 230 900 53 875 54 855 55 835 57
TAP 4 (COOL) 208 or 230 800 775 755 735
TAP 5 (COOL) 208 or 230 880 860 835 815
TAP 1 (HEAT) 208 or 230 735 52 700 55 670 57 640 60
TAP 2 (HEAT) * 208 or 230 825 46 795 48 770 50 745 51
TAP 3 (HEAT) 208 or 230 895 43 865 44 840 46 810 47
TAP 4 (COOL) 208 or 230 800 765 735 715
TAP 5 (COOL) 208 or 230 880 845 820 795
TAP 1 (HEAT) 208 or 230 735 64 700 68 670 71 640 74
TAP 2 (HEAT) 208 or 230 825 57 795 59 770 61 745 63
TAP 3 (HEAT) * 208 or 230 895 53 865 55 840 56 810 58
TAP 4 (COOL) 208 or 230 800 765 735 715
TAP 5 (COOL) 208 or 230 880 845 820 795
-
HWC9N5511P30A 45 60- 75
HWC9N4411P18A
HWC9N4411P30A 35
35 - 65 50
HWC9N5511P18A 45 - 75
60
HWC9N3311P18A 30 - 60 45
HWC9N5511P24A 45 - 75
35
55 40
65 50
- 65 50
0.4 " w.c.
HWC9N2211P12A 25 -
HWC9N3311P12A
Model
Rise
Range
(F°)
Mid
Rise
(F°)
Indoor Blower
Speed
AIRFLOWS AND HEATING TEMPERATURE RISES
AS A FUNCTION OF EXTERNAL STATIC PRESSURE
0.2 " w.c. 0.3 " w.c.
Unit
Voltage
(V)
0.1 " w.c.
65 50
60
HWC9N4411P24A 35 -
N/A: Do not operate unit in heating mode using this blower speed at this external static pressure. Outside of temperature rise range.
* : As shipped speed for heating operation
Table 2
HWC9N3311P24A 30 - 60 45
Table 2

Page 11 of 21507389-01 Issue 1504
Blower
The unit contains a direct-drive, mulspeed blower. The proper
speeds have been preset at the factory for heang and cooling.
Refer to the wiring diagram for recommended
heang/cooling speeds for specic models. Direct-drive blower
motors are permanently lubricated and do not require oiling.
Limit Control
A xed temperature limit control is provided which will shut
o the gas to the main burners if the unit is overheated for any
reason. The control must not be adjusted or relocated.
High Altude Adjustments (U.S. Installaons)
Rangs shown on the rang plate are for elevaons up to 2000
feet. For elevaons above 2000 feet, rangs should be reduced at
a rate of 4% for each 1000’ above sea level. Refer to the Naonal
Fuel Gas Code Z223.1 (latest edion) for further explanaon.
High Altude Adjustments (Canadian Installaons)
High altude conversions may be made by the manufacturer’s
authorized representave, in accordance with the requirement
of the manufacturer, provincial, or territorial authories having
jurisdicon, and in accordance with the requirements of CAN/CGA
B149.1 or B149.2 Installaon Code. A high altude conversion kit,
available from the manufacturer and approved for this purpose,
must be used.
Installaon and Operaon in Extremely Cold Weather Areas
In areas where extremely cold (below – 20°F) outdoor temperatures
can be expected, some additional installation and operating
precauons should be taken. The following precauons are taken
to prevent possible vent system ice blockage that could result in
safety shutdown of the burners:
1. Adjust to the highest achievable temperature rise within
the rise and stac pressure ranges specied on the rang
plate. Depending on specic model, it may be possible to
change to a lower heang blower speed tap to get a higher
temperature rise. This also increases comfort.
2. Make sure there are no leaks of outside air into the return
air system.
3. Keep the outside louver grille as free as possible of any ice
that may form and obstruct the ue outlet.
START-UP
For Your Safety Read Before Lighng
If you do not follow these instrucons exactly, a re or
explosion may result causing property damage, personal
injury, or loss of life.
WARNING
This furnace is equipped with a direct ignion control. Do
not aempt to manually light the burners.
CAUTION
Priming Condensate Trap
The condensate trap must be primed with water prior to
start-up to ensure proper condensate drainage. See Figure 3 or
Figure 4 to idenfy the upper drain hose. Follow these steps to
prime the trap:
1. Disconnect the upper drain hose at the collector box.
2. Rotate the hose from beneath the control board.
3. Flex the hose so that water can be poured into it. Pour 5 .
oz. (100 mL) of water into the trap.
4. Reconnect the upper drain hose.
5. Follow the lighng instrucons to place the unit into
operaon.
6. Set the thermostat to iniate a heang demand.
To Light Main Burners
1. Turn o electrical power to unit.
2. Turn the thermostat to lowest seng.
3. Move the gas valve ON/OFF switch to the “ON” posion (see
Figure 6).
4. Turn on electrical power to the unit.
5. Set the room thermostat to the desired temperature.
(If the thermostat “set” temperature is above room
temperature aer the pre-purge me expires, main burners
will light.)

Page 12 of 21 507389-01Issue 1504
To Shut Down Main Burners
1. Turn o electrical power to unit.
2. Move the ON/OFF switch to the “OFF” posion
(see Figure 6).
OPERATION
Operaon of the unit is automac and will provide heang and
cooling depending on the seng of the thermostat.
Heang
1. Turn on main power supply.
2. Open manual gas shuto valve.
3. Set thermostat system to “HEAT”.
4. Set thermostat to temperature desired.
Cooling
1. Turn on main power supply.
2. Set thermostat system switch to “COOL”.
3. Set thermostat to temperature desired.
Heang Sequence of Operaon
1. Thermostat calls for heat.
2. Combuson blower starts and proper air ow is proven by
the pressure switch closing.
3. Blower connues to operate for 30 seconds prior to the
burners lighng.
4. Ignion control begins spark and opens gas valve. The
burners are lit. Ignion is proved through the ame sensor.
5. Circulang air blower starts 30 seconds aer the burners
light.
6. When the thermostat is sased, the burners and combuson
blower shut o.
7. Circulang air blower will shut o 120 seconds later.
If the burners should fail to ignite, the ignion control will try to
ignite the burners a total of three mes. Should the burners fail
to ignite within the three trials for ignion, the ignion control
will lock out for 1 hour before beginning another ignion cycle.
To reset the control, turn the thermostat down or o for 10
seconds and then set to desired seng. At this me, the ignion
sequence will try again.
Blower Control
The blower will start approximately 30 seconds after the
burners ignite and will stop approximately 120 seconds aer the
thermostat is sased. The me delay is preset at the factory
and ming can not be adjusted.
Cooling sequnce of Operaon
When the thermostat system switch is set for “COOL”, the blower
will start 5 seconds aer the thermostat calls for cooling and will
stop 90 seconds aer the thermostat is sased.
Connous fan Operaon
Connuous operaon of the air handling blower will be obtained
if the thermostat fan switch is set to “ON”. With the thermostat
fan switch set to “AUTO”, the air handling blower will cycle
corresponding with the thermostat cycling.
To Shut Down Unit
For temporary or short periods of shutdown, set the thermostat
system switch to “OFF”. For a prolonged period of shutdown, set
the thermostat system switch to “OFF” and turn o the electrical
power supply and the gas supply to the unit.
Gas Valve
Figure 6
Gas Inlet
ON/OFF
SWITCH
Gas Inlet
Pressure
test tap
Regulator
adjustment
Screw
(Under Cap)
Gas manifold
Pressure test
tap
MAINTENANCE
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, Serious injury, death or property
damage.
Improper servicing could result in dangereous operaon,
Serious injury, death or property damage
•Before servicing. disconnect all electrical power to
furnace
•When servicing controls, label all wires prior to
disconnecting reconnect wires correctly.
• Any disassembly of components containing ue
or vent gases shall be done by a qualied service
agency.
•Verify proper operation after servicing.
WARNING

Page 13 of 21507389-01 Issue 1504
The HWC9 models are newly designed with improved performance
and added features over previous models. Refer to Figure 7 for
heang cabinet component layout. It is recommended that the
furnace be inspected annually by a qualied service person.
Inducer prover
switch
Ignition
Control board
Remove these
screws to remove
Burner Assembly
Igniter
Combustion
Inducer
Gas Valve
Gas Manifold
Rollout switch
Burner & Manifold
Assembly
Figure 7
COMPONENT LAYOUT
Primary limit
Heat exchanger
access panel
Cold end
header box
Condensate
Drain trap
Inducer elbow
Flue tube
Drain hoses
Drain tting
Flame Sensor

Page 14 of 21 507389-01Issue 1504
Burner & manifold assembly
To remove the burner & manifold assembly:
1. Disconnect electrical service and turn o gas to the appliance.
2. Loosen the pipe union external to the unit and remove the
gas line to the gas valve.
3. Disconnect the orange high voltage spark wire at the ignion
control board.
4. Disconnect the white ame sensor wire at the ame sensor
on the underside of the burner assembly..
5. Disconnect the orange wires at the rollout switch.
6. Disconnect the red and blue wires at the gas valve.
7. Refer to Figure 8. Remove the two screws on the burner
assembly that secure it to the mounng brackets. The
mounng brackets contain pins to locate the assembly and
hold it in place aer the screws are removed. The mounng
brackets are hidden unl the burner assembly is removed.
8. First, carefully pull the burner assembly toward you unl it
is clear of the locang pins in the mounng brackets.
9. Then move the assembly away from the vest panel.
10. Finally, pull the assembly from the unit.
11. Once the burner assembly is removed, the burners can be
cleaned using a bole brush.
12. For reassembly, follow the above steps in reverse order. Use
cauon to insure rear of manifold assembly is properly
engaged in rear mounng bracket.

Page 15 of 21507389-01 Issue 1504
BURNER & MANIFOLD ASSEMBLY REMOVAL
Step 7
Mounting Brackets
Step 8
Step
9
Step 10
Burner &
Manifold
Assembly
Figure 8

Page 16 of 21 507389-01Issue 1504
Control board mounng bracket
The control board mounng bracket is designed to be removed
to allow component access for some service procedures. The
ignion control board and the inducer prover switch are mounted
to the bracket. Refer to Figure 9.
1. Disconnect electrical service and turn o gas to the
appliance.
2. The bracket is mounted to tabs molded into the side of the
cold-end header box. Depress the locking tab on the cold-end
header box that engages the lower corner of the bracket, then
slide the bracket away from the vest panel and clear of the
tabs.
3. Carefully lower and pivot the bracket and ignion board to
the boom of the compartment.
4. It may be necessary to remove the inducer prover switch
tubing at the switch.
5. For reassembly, follow the above steps in reverse order.
Igniter
The igniter can be accessed from the front of the unit without
removing any other components. To remove the igniter:
1. Disconnect electrical service and turn o gas to the appliance.
2. Disconnect the orange high voltage spark wire at the ignion
control board.
3. Remove the screw and pull the igniter out of the burner
assembly.
4. For reassembly, follow the above steps in reverse order.
Rollout switch
If for any reason the heat exchanger becomes blocked the
temperature-sensive rollout switch located beside the burners
will open and the ignion control will turn o the burners. Aer
invesgang and correcng the problem, the rollout switch must
be manually reset by pressing the buon on top of it.
The rollout switch can be accessed from the front of the unit
without removing any other components. To remove the rollout
switch:
1. Disconnect electrical service and turn o gas to the appliance.
2. Disconnect the orange leads at the rollout switch.
3. Remove the screw and slip the rollout switch from beneath
the lanced tab on the burner assembly.
4. For reassembly, follow the above steps in reverse order.
Flame sensor
1. Remove the control board mounng bracket as described
previously.
2. Remove the screw and pull the ame sensor from the boom
of burner assembly.
3. For reassembly, follow the above steps in reverse order.
Primary limit switch
The primary limit will shut down the unit in case of overheang
and automacally resets when temperature falls to an acceptable
level. It is not eld adjustable
1. Remove the control board mounng bracket as described
previously.
2. Disconnect the two orange leads at the primary limit switch.
3. Remove the three screws securing the primary limit switch
to the vest panel.
4. For reassembly, follow the above steps in reverse order.
Inducer prover switch
1. Remove the control board mounng bracket as described
previously.
2. Disconnect the two purple leads at the inducer prover switch.
3. If the tubing is in place, remove it.
4. Remove the screw securing the switch to the bracket and slip
the strap end out of the hole in the bracket.
5. For reassembly, follow the above steps in reverse order.
Burner orices
Orices are threaded into the gas manifold. To remove them:
1. Remove the burner & manifold assembly as described
previously.
2. Remove the four screws securing the gas manifold to the
burner assembly.
3. Remove the orices by unscrewing them. Do not use any
pipe thread sealant during reassembly.
4. For reassembly, follow the above steps in reverse order.
Combuson inducer
The combustion inducer can be removed for inspection,

Page 17 of 21507389-01 Issue 1504
Ignition board & Bracket removal
Tabs on Cold-End
Header box
Figure 9
Press down on
locking tab then
slide bracket
Slots on ignition
board bracket

Page 18 of 21 507389-01Issue 1504
replacement, or to access the heat exchanger and ue tube
extension for cleaning. To remove the combuson inducer:
1. Remove the control board mounng bracket as described
previously.
2. Disconnect the inducer motor leads.
3. Disconnect the inducer prover switch tubing at the switch.
4. Disconnect the drain hose tubing at the collector box.
5. Loosen the hose clamp at the inducer elbow-ue tube joint
(the upper hose clamp).
6. Remove the three screws securing the inducer to the cold-
end header box. Loosen clip at upper mount.
7. Pull the combuson inducer and elbow away from the vest
panel to move it free of the mounng legs on the cold-end
header box, while pulling the inducer elbow free of the ue
tube extension.
8. Pull the inducer and elbow out of the compartment.
6. The ue tube extension can be cleaned if necessary. Leave it
in place; do not remove it from the unit.
7. If replacing the inducer with a new part, be sure the correct
inducer orice is snapped in place.
8. For reassembly, follow the above steps in reverse order.
Combuson inducer orice
The combuson inducer orice meters the air ow needed for
proper combuson. Orices are unique to each heang input,
and the correct one must always be used. The orices are color-
coded as an aid. Refer to Table 3:
Refer to Figure 10 to remove the combuson inducer orice:
1. The combuson orice is held in place with snap-ts at the
inducer inlet and at the indicator tab at the inducer mounng
foot.
2. With the combuson inducer out of the unit, carefully pry
the round poron of the orice from the inducer inlet.
3. Remove the indicator tab from the inducer mounng foot.
Model Orice color
HWC9N22 Blue
HWC9N33 Black
HWC9N44 Gray
HWC9N55 Brown
Table 3
4. For reassembly, follow the above steps in reverse order.
Furnace condensate drain
The condensate drain ensures proper evacuaon of furnace
condensate from the collector box and inducer out of the cabinet.
If hoses are disconnected or if the drain is removed and replaced,
the drain must be primed as described in the procedure outlined
in the “Start-up” secon. To remove the condensate drain:
1. Disconnect the upper and lower drain hoses at the condensate
drain.
2. Remove the two screws that secure the drain to the vest
panel.
3. For reassembly, follow the above steps in reverse order.
4. Prime the condensate drain as described in the procedure
outlined in the “Start-up” secon.
Heat exchanger inspecon
The heat exchanger should be inspected periodically and cleaned
if necessary. The assembly can be inspected in place, but cleaning
requires accessing both ends of the primary and secondary tubes,
which can only be accomplished by removing the heat exchanger
assembly from the furnace cabinet. To access the primary heat
exchanger tubes for inspecon:
1. Remove the burner & manifold assembly as described
previously.
2. Remove the control board mounng bracket as described
previously.
3. Check the tubes for evidence of soot. If the tubes are clean,
reassembly is the reverse of the above procedure. If there
is noceable soot, connue with the heat exchanger removal
procedure to remove and clean the heat exchanger.
Combuson
Inducer
Snap into
place
rst (visible
aer
reinstalled
in unit)
Inducer
Orice
----en
Snap into
place
Figure 10

Page 19 of 21507389-01 Issue 1504
Heat exchanger removal and cleaning
1. Remove the heat exchanger access panel
2. Remove the combuson inducer as described previously.
3. Disconnect the two orange leads from the primary limit
switch at the vest panel.
4. Disconnect the upper and lower drain hoses from the
condensate drain.
5. Remove the four screws at the rear vest panel ange.
6. Remove the three screws at the boom vest panel ange.
7. Remove the three screws on the top panel of the unit that
secure the vest panel.
8. Disconnect the supply air duct if it cannot be lied slightly
to allow the top panel to be lted upward.
9. Remove the two screws closest to the front of the unit on
each side of the top panel so it can be lted upward.
10. Tilt the front edge of the top panel upward and remove the
heat exchanger assembly from the cabinet. Take care to avoid
damaging insulaon or other components.
11. With the heat exchanger assembly out of the cabinet, remove
the twelve screws securing the hot end header box to the
rear end sheet.
12. Remove the turbulators from the secondary coil tubes.
13. Back wash the heat exchanger with soapy water soluon
or steam. If steam is used its temperature must be below
275°F (135°C).
14. Thoroughly rinse and drain the heat exchanger. Soap
soluons can be corrosive. Take care to rinse the enre
assembly.
15. For reassembly, follow the above steps in reverse order.
Cooling Chassis
The refrigeraon system contained in the cooling chassis normally
requires no maintenance since it is a closed, self-contained
system. System is charged with R410A refrigerant. Periodic
maintenance is limited to:
• Cleaning the air lter. Follow direcons noted on the lter
and label aached to the access panel.
• Cleaning the condenser coil if covered with any foreign
material, lint, leaves, or other obstrucons.
If servicing or major repairs are required, the complete chassis
can be removed from the unit. To remove the chassis:
1. Shut o the main power supply.
2. Remove filter access panel and panel covering cooling
controls.
3. Remove drain hose from the drain pan.
4. Disconnect the plug-in electrical connections. Do not
seperate the connector by pulling on this wire; instead, grasp
the connector handle.
5. Disconnect two power leads at contactor (leads come from
Grommet in unit paron).
6. Remove screws from panel directly in front of blower and
remove panel. Also remove addional screws located near
top edge of control panel.
7. Drape power wires and wire harnesses out of cabinet and
tape to upper panel.
8. Slide out the chassis, being careful not to damage any seals
or parts. Parcular care should be taken to insure wiring is
not damaged during removal/reinstallaon process.
To reinstall the chassis, reverse the procedure outlined above.
Be sure that the chassis is inserted as far back as it will go before
replacing the screws. Side anges on the chassis must be engaged
with sealing strips on the unit sides to prevent water and air
leakage. Reconnect the wire harness, reconnect the power
leads, and replace both access panels before turning on the main
electrical power. Tubing is not to be used as a handle.

Page 20 of 21 507389-01Issue 1504
Figure 11
This manual suits for next models
1
Other Magic-Pak Heat Pump manuals
Popular Heat Pump manuals by other brands

Estia
Estia HWS-1501CSHM3-UK Installation and service manual

Dimplex
Dimplex SI 5CS Installation and operating instructions

Calorex
Calorex AW631 Owners & installation manual

Bryant
Bryant Evolution 284ANV Series manual

Carrier
Carrier 38YRA Installation and start-up instructions

evoheat
evoheat EVO ULTRA 32 Installation & operation manual

Nibe
Nibe VVM 500 Installer manual

York
York F3EH090 installation manual

Dimplex
Dimplex LA 17TU Installation and operating instructions

Panasonic
Panasonic WH-UDZ03KE5 installation manual

Viessmann
Viessmann Vitocal 350-G Installation and service instructions for contractors

Sanyo
Sanyo KHS0922 instruction manual