ModPac PDS 1/2013 Rev. 10
2
M5 Configuration
The M5 configuration of the ModPac II air conditioner features the following as standard.
PC Board
Each ModPac air conditioner has a PC board that controls the operation of the indoor blower and
the compressor while providing high refrigerant pressure and low refrigerant protection. User
selectable pins and potentiometers permit multi-function control. LED’s indicate operational status
and fault conditions. A dedicated relay controls allows control of the two position motorized fresh
air damper (Ventilation Configurations “B” & “Z”).
LED Indicator Lights
COLOR TYPE STATUS DESCRIPTION
Green Power Constant On 24 VAC power has been applied
Red Status
Constant On Normal Operation
1 Blink High pressure switch has opened twice
2 Blinks Low pressure switch has opened twice
3 Blinks Freeze stat (optional) - indoor coil temperature is below 35°F (1°C)
Modes of Operation
Normal Start-up: On a call for cooling, and the with the high pressure switch closed, the cooling
system
(compressor, indoor blower motor and outdoor fan motor) will be energized. (Note: See the Delay
on Make feature). The cooling system will remain energized during the three minute low pressure
switch bypass cycle. If the low pressure is closed, the cooling system will continue to operate after
the three-minute bypass. If the low pressure switch is open after the three-minute bypass, the
cooling system will be de-energized.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling,
the control board enters into and indicates the lockout mode. In the lockout mode, the compressor
is turned off, the alarm output is energized and the status LED’s will blink to indicate which fault
has occurred. If there is a call for air flow, the indoor blower will remain energized. When the
lockout condition has cleared, the unit will reset if the demand of the thermostat is removed or
when power is reset. The lockout circuit is factory wired for normally open contacts. The user can
select either normally closed or normally open remote alarm dry contacts.
Delay on Make: On initial power up or on resumption of power, the air conditioner will wait .03 to
10 minutes from a call for cooling before allowing the contactor to energize.
In addition to the PC board, the M5 configuration has high and low refrigerant pressure switches
and foil backed insulation lines the indoor air path. A low ambient fan cycle control is available as
an option.
Ease of Installation
•Factoryinstalleddisconnectmayeliminate
need of outside disconnect.
•Built-inmountingflangeseliminateneedfor
side brackets.
•Slopedtopshedswaterandminimizes
chance of water leaks.
•Designedforinstallationinamodular
builder's facility.
•SinglePointPowerEntrycomplieswithlatest
edition of U.L. Standard 1995.
Attractive and Built for Long Term
Operation
•Choiceofcolors-beige,white,grey,light
brown.
•Decorativecoilguard.
•Highefficiencycompressorsprovidereliable
and quiet operation.
Ease of Service
•Serviceaccessvalves.
•Allcomponentsaccessibleforfieldservice.
•Nationwidenetworkofservicecenters.
Quiet
•Twinblowerssizedtoacceptfullduct
system.
•Highandlowrefrigerantswitches
•Highdensity,foilbackedinsulationcomplies
with codes that require a cleanable surface
for the indoor air path.
Standard Features