11
2.0 Setup Sequence
d) Change the unit of measure by pressing or .
e) Exit the menu system by pressing and holding for several seconds. The PV and SP
for all zones (except any offline zones) will be displayed in the selected unit of measure.
Other temperature values previously entered while a different unit of measure was in use
will be converted automatically.
4) If the factory settings listed in subsection 3.6 are not appropriate for your application, you can
change a parameter value for one or all zones.
a) To select one zone, press repeatedly until only that zones PV and SP are displayed.
To select all zones, press repeatedly until the PV and SP for all zones are displayed
with asterisks between the PV and SP for zones 3 and 4 (refer to the image below) on
an iB6 unit. (On an iB12 unit, asterisks will also be displayed between the PV and SP for
zones 9 and 10.)
b) Press and hold to enter the menu system.
c) Step through the menus by pressing repeatedly until the name of the menu you want
is displayed.
d) Step through the menu items by pressing until the parameter you want is displayed,
alternating with its current value.
e) Change the value by pressing or . When changing a numerical value, you can hold
down an arrow button for fast changes.
f) Exit the menu system by pressing and holding for several seconds.
Note that the default High [Temperature] Safety [Limit] (a Supervisor parameter) is Off
by default. If you want the controller to turn off the output to a zone that exceeds the high
limit, change the value of the High Safety parameter.
5) iB6 and iB12 units are shipped with the Supervisor password set to 100, which disables
password protection. If you want to limit access to the Superv [Supervisor] Config menu, change
the Supervisor password from the default 100. As long as the password is 100, no password will
be required to access all functions (except settings on the Factory Config menu).2
6) Change Normal mode (closed loop) setpoints or Manual mode (open loop) output percentage by
selecting a zone, and then pressing or to change the setpoint or output percent. A few
seconds after you stop pressing an arrow button, the main display (PV and SP) will return.
Tip: If all zones are in the same mode (Normal or Manual), you can select all zones as described
above, and then change the setpoint temperature or manual mode output percentage for all
zones simultaneously.
7) Autotune all zones that will operate in Normal (closed loop) mode; see Section 6. When
Autotuning has been completed successfully for all Normal zones, the controller is ready to use.
The appropriate green status LED in the column of LEDs for each zone will be lit:
for Normal (open loop)
250
250
248
250
2The Factory Configuration password is available only from Mastip Technical Support.