Feature
ZL-7850A is a temperature and humidity controller with rich display. IP65 level front panel protection,
convenient operation and easy installation. Suitable for control of incubator, climate chamber,
greenhouse, warehouse, and so on.
Specification
Power supply: 100 ~ 240Vac, 50/60 z
Input: One humidity and temperature sensor, wire length 2 meter
Sensor precision: umidity ±3%/25℃ (ZL-SHr03A), ±2%/25℃ (ZL-SHr05B); Temperature ±1%
Setting range: umidity 0 ~ 80%R ; Temperature 0 ~ 65
℃
Display range: umidity 0 ~ 99%R ; Temperature -20 ~ 80
℃
Output: Temp. Output ≤ 5A,
umi. Output and Fan Output ≤ 3A,
2 Egg turns ≤ 1A
Working environment: -10 ~ 45
℃
; ≤ 90% R without dew
Case dimension: L78 x W34.5 x D71 (mm)
Drilling size: L 71 x W29 (mm)
Case materials: PC + ABS, fireproof
Protection level: IP65 (Front panel only)
Key Function
eat/cool control
umidify/dehumidify control
Timer air exhaustion
Timer and manual egg turning
Temperature and humidity calibration
Temperature and humidity high limit protection
Temperature and humidity limits alarm
Alarm and protection when sensor fails
Restore control when power supply returns
Display

Suzhou Lily Tech. Co., Ltd.
Page 2. Total 5 pages
Icon
Function On Blink Off
eat output (R3) Energized
Deenergized because
of delay protecting (ref.
【t2】, 【h2】)
Deenergized
Cool output (R3) Energized Deenergized
umidify output (R2) Energized Deenergized
Dehumidify output (R2) Energized Deenergized
Multifunction fan output (R1) Energized
periodically
Energized because of
high limit protection Deenergized
Egg left turn output (R4) Energized Turn counter’s value ≥
Turn times’ set value
Deenergized
Egg right turn output (R5) Energized Deenergized
Celsius temperature value Celsius value Setting Celsius value
Relative humidity value R value Setting R value
Alarm Alarming No alarming
Maintenance as fault No fault
E01
Sensor failure Sensor failure warn
t i Temperature high warn point igh temperature warn
tLo Temperature low warn point Low temperature warn
h umidity high warn point igh humidity warn
hL umidity low warn point Low humidity warn
Lo Keypad locked Keypad locked
Un Keypad unlocked Keypad unlocked
UnL
Restore to factory default
settings
Restoring to
default settings
Firmware Version
After power on reset, display the model name (7850A) and firmware version (A1.2):
Setting Operation
Temperature and humidity setting
Keep〖S〗depressed for 2 seconds to enter into/exit temperature and humidity setting status.
Press〖P〗to switch between temperature setting (TP) and humidity setting ( P).
Press〖▲〗or〖▼〗 to set the value (keep depressed make fast set).
Note: The status will exit if no key operation for 15 seconds, and the setting will not be saved.
The temperature setting range 0 ~ 65℃ (factory default setting is 37.8℃).
The humidity setting range 0 ~ 80%R (factory default setting is 60%R ).
Parameter setting
Keep〖P〗depressed for 2 seconds to enter into/exit parameter setting status.
Press〖S〗or〖P〗to select the code.
Press〖▲〗or〖▼〗to set the value of the code (keep depressed make fast vale set).
Note: The status will exit if no key operation for 15 seconds, and the setting will not be saved.

Suzhou Lily Tech. Co., Ltd.
Page 3. Total 5 pages
Code parameter table:
Code
Function Range Remark Factory
Default
t0 Temp. control mode H/C H: heat; C: cool H
t1 Temp. hysteresis 0.1 ~ 20
℃
0.1
t2 Time delay protection for Temp. load 0 ~ 30 min 0
t3 Temp. calibration -9.9 ~ 9.9
℃
0
t4 Temp. high limit (relative value, R1) 0 ~ 20 If 0, no high temp. limit 0.2
t5 Temp. low limit (relative value, R1) 0 ~ 20 If 0, no low temp. limit 0.1
t6 Temp. high warning point (relative value) 0 ~ 65 If 0, no high temp. warn 0
t7 Temp. low warning point (relative value) 0 ~ 65 If 0, no low temp. warn 0
h0 Humidity control mode H/P H: humidify; P: dehumidify H
h1 Humidity hysteresis 1 ~ 20 % 2
h2 Time delay protection for Humi. Output 0 ~ 30 min 0
h3 Humidity calibration -20 ~ 20% 0
h4 Humidity high limit (relative value, R1) 0 ~ 20 % If 0, no high humidity limit 5
h5 Humidity low limit (relative value, R1) 0 ~ 20 % If 0, no low humidity limit 2
h6 Humidity high warning point (relative value) 0 ~ 80 % If 0, no high humidity warn 0
h7 Humidity low warning point (relative value) 0 ~ 80 % If 0, no low humidity warn 0
u0 Egg turn (R4, R5) deenergized time 0 ~ 999 min If 0, no turn function 60
u1 Egg turn (R4, R5) energized time 0 ~ 999 sec If 0, no turn function 30
u2 Egg turn times 0 ~ 999 If 0, turn without shop 0
u3 Exhaustion fan (R1) deenergized time 0 ~ 999 min If 0, no exhaustion 120
u4 Exhaustion fan (R1) energized time 0 ~ 999 sec If 0, no exhaustion 30
u9 Sensor selection 0/1 0: ZL-SHr03A
1: ZL-SHr05B 0
Control Function Instruction
Temperature control
eat mode【t0 = 】
When Room temp. ≤ Set temp. (TP) –【t1】, and Temp. Output (R3) has stopped for【t2】,
Temp. Output (R3) will be energized.
When Room temp. ≥ Set temp. (TP), Temp. Output (R3) will be deenergized.
Cool mode【t0 = C】
When Room temp. ≥ Set temp. (TP) +【t1】, and Temp. Output (R3) has stopped for【t2】,
Temp. Output (R3) will be energized.
When Room temp. ≤ Set temp. (TP), Temp. Output (R3) will be deenergized.
Over high temperature limit protection (only for heat mode)
When Room temp. ≥ Set temp. (TP) +【t4】, Fan Output (R1) will be energized.
When Room temp. ≤ Set temp. (TP) +【t4】-【t5】, Fan Output (R1) will be deenergized.

Suzhou Lily Tech. Co., Ltd.
Page 4. Total 5 pages
umidity control
umidify mode【h0 = 】
When Room humidity ≤ Set humidity ( P) -【h1】, and Humi. Output (R2) has stopped for【h2】,
Humi. Output (R2) will be energized.
When Room humidity ≥ Set humidity ( P), Humi. Output (R2) will be deenergized.
Dehumidify mode【t0 = P】
When Room humidity ≥ Set humidity ( P) +【h1】, and Humi. Output (R2) has stopped for【h2】,
Humi. Output (R2) will be energized.
When Room humidity ≤ Set humidity ( P), Humi. Output (R2) will be deenergized.
Over high humidity limit protection (only for humidify mode)
When Room humidity ≥ Set humidity ( P) +【h4】, Fan Output (R1) will be energized.
When Room humidity ≤ Set humidity ( P)】+【h4】-【h5】, Fan Output (R1) will be deenergized.
Turn egg control(R4, R5)
Egg-Turn Output will be energized (R4 and R5 alternatively) for【u1】after deenergized for【u0】,
periodically.
One full egg turn = one left turn (R4) + one right turn (R5).
There will be no egg turn after full egg turn has executed for【u2】times, and the egg turn signs will
blink.
Keeping【▲】depressed for 2 seconds starts manual egg right turning; keeping 【▼】depressed for
2 seconds starts manual egg left turning.
Pressing 【S】and【▼】simultaneously shows the full egg turn counter value.
Power on reset will reset the full egg turn counter value to zero.
Timer exhaustion control (R1)
Fan Output (R1) will be energized for【u4】after deenergized for【u3】, periodically.
Warning control
When there is warning, the buzzer will beep.
The buzzer warning could be stopped/restored by pressing【P】.
igh temp. warning: if Room temp. ≥ Set temp. (TP) +【t6】, Room temp./“t i” displays alternatively.
Low temp. warning: if Room temp. ≤Set temp. (TP) -【t7】, Room temp./“tLo” displays alternatively.
igh humidity warning: if Room humidity ≥ Set humidity ( P) +【h6】, Room humidity//“h ” displays
alternatively.
Low humidity warning: if Room humidity ≤ Set humidity ( P) -【h7】, Room humidity//“hL” displays
alternatively.
The warning Press【P】
Sensor
The Room temp. can be calibrated. If Room temp. is 0.2℃ lower than real temp., set 【t3】= 0.2.
The Room humidity can be calibrated. If Room humidity is 2%R higher than real, set 【h3】= -2.
When sensor fails, the Temp. and Humi. Output (R3, R2) will be deenergized, and “E01” will display.
Note: do not plug in/off the sensor when power supplied.

Suzhou Lily Tech. Co., Ltd.
Page 5. Total 5 pages
Keypad lock
Press〖S〗and〖P〗simultaneously for 3 seconds to lock the keypad, “Lo” displays for 3 seconds.
When keypad locked, any keypress will not executed, but display “Lo”.
Press〖S〗and〖P〗simultaneously for 3 seconds to unlock, “Un” displays for 3 seconds.
Restore to factory default setting
Press〖P〗and〖▲〗simultaneously for 3 seconds, “UnL” displays. Then press〖▼〗 twice, all
parameters will restore to factory default settings.
W
Wa
ar
rn
ni
in
ng
g
1. Do not connect wiring when power is supplied.
2. Electrical wiring must be manipulated by certified electrician.
3. Read this manual carefully. Connect according to electrical wiring diagram. Wrong connection will
damage the device.
4. Do not layout the sensor bundle together with power supply bundle.
5. Avoid working in erosive, wet and strong electrical-magnetic field environment, which could affect the
device works correctly.
6.
This device has been checked fully before shipment. The warranty time is one year, damaged by
wrong usage, such as wrong connection, is not warranted.
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
1. Insert the controller into hole
(step one)
2. Slide the bracket to fix the device
(step two)
Wiring Diagram