
5
SYSTEM SETUP AND INSTALLATION
1. Gas Supply
The most optimal method of fluidizing is to use an inert gas such as Argon,
alternatively compressed air can be used when properly treated, dried and filtered
When a compressed air source is used to supply air pressure to the fluidized fill shoe,
the gas control supply pressure should be between 30 and 60 psi The FFS control
cabinet will provide instrument quality air to the fluidized fill shoe as long as care is
taken to maintain a quality air supply, i e air that is free of oil, dirt, and moisture To
prevent moisture build up in the gas lines it is common practice to install an
appropriately sized after-cooler and moisture separator system on a shop air
compressor As an extra precaution, it is recommended that a secondary liquid
separator and trap be installed ahead of the FFS control cabinet as shown in Figure 2
During normal use, and especially during initial setup of a new system, the
quality of the air supply should be closely monitored for any oil, moisture, or solid
contamination
For systems equipped with a desi ant dryer
The functionality of a desiccant gas dryer can be readily checked by observing
the dew-point indicator particles which are mixed into the desiccant located inside the
dryer:
♦When the indicator particles color is blue, the dryer function is normal and it
is O K to operate the system
♦When the indicator particles color is pink, the outlet air is humid It is time to
replace the desiccant before you operate the system
For systems equipped with a membrane dryer (optional)
The desiccant dryer can be upgraded to a very low maintenance membrane
dryer With a membrane dryer you can readily check outlet moisture condition by
observing the dew-point indicator which is located on the top of the membrane dryer:
♦When the dew-point indicator is blue, the operation is normal
♦When the dew-point indicator is pink, the outlet air is humid
Note: It takes approximately 1 hour to hange the olor of the dew-point
indi ator from the start-up of supply air.