maxem Maxem 5 User manual

SMART CHARGING CONTROLLER
English -Installation manual
Maxem 5

2
Safety warnings
• Onlytobeinstalledbyacertiedelectrician.
• Completelyfollowtheinstructionsgiven.
• Use this device only for the purpose it is designed for, as described in this
manual.
• Maxemworksonlyafteronlinecommissioningbytheinstaller.
• FailuretofollowtheabovewarningscanleadtoanincorrectMaxeminstallation.
This can lead to over current on the grid connection, damage to installations
andchargingstations,electricshocksorre.
Cohere is not responsible for the installation of Maxem and for any damage arising from not
following the installation manual correctly. Nor for damage resulting from typographical
errorsormisinterpretationsoftextorimages.
Tip
Warning
Safety Information
Symbols in this document
Liability
Installation manual for Maxem Home
Publication date: 1 April 2018
See for the most latest information on
www.maxem.io

3
EN
All information in this document is the copyright and intellectual property of Cohere Energy
SolutionsB.V.Materialinthisdocumentmaynotbemodied,reproducedorcopied,inpart
orinwhole,withouttheexplicitwrittenconsentofCohereEnergySolutionsB.V.Additional
informationisavailableuponrequest.
MaxemisaregisteredtrademarkofCohereEnergySolutionsB.V.
SMART CHARGING CONTROLLER
CHARGE SMARTER
©2018COHEREENERGYSOLUTIONSB.V.
Product symbols statements
Installandusethisproductonlyaftercarefulreadingofthemanual.
Thisproductisdoubleinsulated.
Indooruseonly.
Productcontainselectronics.Donotthrowitinthehouseholdwaste.
ThisproductisdesignedforovervoltagecategoryIII.
This product meets all the requirements set by the EU for
productsafety.
English

4
Index
What is Maxem? 29
Productspecications30
What do I need for the installation? 32
Installation steps
01 - Mounting of Maxem 34
02 - Connecting current transformers
Option2.1-Connecting current transformers on the grid connection 36
Option2.2-Connecting current transformers on the solar panels 36
03-ConnectingMIDkWh-meters 38
04 - Connecting charging station
Option4.1-ConnectingTesla Wall Connector 40
Option4.2-ConnectingKEBAcharging station 42
Option4.3-ConnectingICU charging station 44
05 - Commissioning by installer 45
ECDeclarationofConformity 70

5
EN
What is Maxem?
From the meter cabinet, Maxem measures the energy use in the house and the energy
generation of solar panels. Based on this information, it manages the charging station,
batteryorheatpumpsmartly.Thus,ithelpstheusertomakeeasierandcheaperuseof
sustainableenergy.
Maxem intelligently manages the charging
speed based on home energy use and solar
production, preventing over current on the
grid connection.
Charging station
Today you can monitor the energy use of
your heat pump. In the near future Maxem
manages the power of your heat pump or
e-boiler in order to store solar energy in hot
water.
Heat pump or e-boiler
Maxem optimizes power consumption on
the main grid connection to prevent over
current. This makes it unnecessary to get an
expensive grid upgrade.
Grid
Maxem measures the energy production of
your solar panels. Soon available: let
Maxem manage your charger on the basis
of solar production. This way you use 100%
of your own solar energy.
Solar panels
Battery
Future vision: through intelligent
measuring and management Maxem
makes sure that all solar power is stored in
the home battery. This way you use all your
solar energy locally.

6
01-Voorbereidingenvooraf
Content of the box
MIDkWh-meterextension
Maxem including mounting plate 6x split core
current transformer
RS485 cable
Networkcable
Power cable
4x Screws 3x20 1x Phoenix connector
Productspecications
2x Tie-wrap
SET
OK
1 2 3
MIDkWh-meter
DenitionsLEDindicators
On/o
Internet
Data
connection
Current
measurement
Charging station
1x Phoenix connector

7
EN
P1
port
Ethernet port
to charging station
Ethernet port to Internet
Router
230Vpower
supply
Current transformers
solar panels
Multi functional
USB port
Current transformers
grid connection
RS485
port 1
RS485
port 2
Denitionsinput/outputports
Specications
Dimensions 184mm(L)x167mm(W)x55mm(H)
Weight 700g
Working temperature 10°C to 35°C
Storage temperature 0°C to 60°C
Maximal humidity 80%
Protection class II (double insulated)
Seal IP20
Working height 0 to 2,000 m
EMC EN61326-1(2013),EN61000-3-2,61000-3-3
Safety EN61010-1(2010),EN61010-2-30(2010)
Immunity EN61326-1(2013)
Overvoltage category 300V/CATIII
Input power 110-240V.50/60Hz.Maximum2,75W
Power coils Up to 50A
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4

8
• Acorrectcircuitbreakerorearthleakagecircuitbreakerwithproperfusingvalue. See
p.33todeterminefusing.
• Schukosocketsfor230VpowersupplyMaxem(ifnotalreadyavailable).
• UTP(CAT5orCAT6)datacableforconnectingchargingstationtoMaxem.
• RJ45(8P8C)connectorsforethernetconnectedchargingstations(ICU/Keba).
• CableendsleevesforUTPcores(onlyforTeslaWallConnector).
• Internetconnectedsmartphone,tabletorcomputer.
Required materials
01-Voorbereidingenvooraf
What do I need for the installation?
Wired Internet access
With Maxem compatible charging stations
Compatibility may change over time. See the website www.maxem.io for the current
overview of compatible charging stations.
Tesla Wall Connector ICUEVeminiKEBAP20/P30 ICUEVe
The following network settings are required. Don’t be alarmed by the jargon, these are
normalnetworksettings.Incorporatenetworkssomeoptionscanbeblocked:
• MaxemhastoreceiveanIPaddressviaDHCP.
• This IP address may not be in the following range: 10.50.0.0/16, 10.51.0.0/16, and
192.168.25.1/24.
• Incaseofarewalloutgoingtrachastobeallowedonthefollowingports:80,443,
1194t/m1200and9090.

9
EN
Fusing charging station
Maxemisacontrolsystemthatregulatestheloadofthechargingstation.Maxemmakes
surethatthereislessloadonthechargingstationwhenthereismoreloadonthehouse.
This reduces the diversity factor. The charging station can therefore be fused to a value
higherthannormal,butnothigherthanthethresholdvalueofthemaingridconnection.
FormoreinformationonthissubjectinrelationtotheNEN1010,seetheMaxemwebsite.
Power supply Charging station capacity Maximal fusing, charging station
3-phase 25A 3-phase 32A 3-phase 25A
3-phase 25A 3-phase 16A 3-phase 16A
3-phase 35A 3-phase 32A 3-phase 32A
1-phase 25A 1-phase 32A 1-phase 25A
1-phase 40A 1-phase 32A 1-phase 32A
Current transformers of kWh-meters
Maxem is standard supplied with current transformers with which the main grid connection
andsolarproductioncanbemeasured.Formoreaccuratemeasurementsitisalsopossible
to use MID certied kWh-meters. The kWh-meters Maxem works with can be ordered
separately.
There are situations when a kWh-meter is always required:
• Measurement of a Tesla Wall Connector
• Measurement of a heat pump

10
01-Voorbereidingenvooraf
01 - Mounting of Maxem
Mount Maxem on a clean, moisture-free wall. Use the supplied mounting plate and
screwsforthis.TakeintoaccountsucientspacearoundtheMaxem.
Wiring at the bottom
70mm
20mm
20mm
20mm
A.

11
EN
Connect Maxem with the supplied network cable to the modem or router connected
totheInternet.
Maxem has to be connected to a 230V wall socket. Prepare this already but do not
powerMaxemyet.
C.
B.
230Vconnection
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
Ethernet port to
Internet Router
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4

12
02 - Connecting current transformers
Option2.2-ConnectingCT’sonsolarpanels
Click the supplied current transformer around the L1 phase wire of the main power
supply, after the main circuit breaker/main switch, such that the entire grid connection
ismeasured(seeg.1)
Connectthecurrenttransformercabletoport1ofMaxem.
Turnothemaincircuitbreakerofswitchofthefusebox.Andopenthefusebox.
RepeatthesestepsforL2andL3incaseofa3-phasegridconnection.Phase2is
connectedonport2.Phase3isconnectedonport3.
Makesurethecurrenttransformersareconnectedintherightdirection.
A.
B.
D.
E.
Option2.1-ConnectingCT’sonthegridconnection
Click the supplied current transformer around the L1 wire of the circuit breaker
tothesolarinverter(seeg.2).Nootherloadsmaybeconnectedtothiscircuit
breaker.
Turnothemainpowersupplyterminalofthefusebox.A.
B.
C.
Connect the current transformer to the corresponding circuit breaker in the fuse
box.Nootherloadsmaybeconnectedtothiscircuitbreaker.
Makesurethecurrenttransformersareconnectedintherightdirection.D.
B.
Connect the current transformer to port 4 of Maxem. Repeat these steps for
L2 and L3; connect L2 to port 5, connect L3 to port 6. Make sure each current
transformerofeachphaseisconnectedtotheassociatedportonMaxem.
C.
Connect the current transformer to the corresponding port on Maxem. For
instance;.port6,whensolarisconnectedtoL3onthegridconnection.Orport
5forL2.
C.
For 3-phase solar energy (see g. 2)
For 1-phase solar energy on a sub-panel (see g. 3)

13
EN
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar
Home
Grid / Solar Home
Grid / Solar
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
L1 L2 L3
Grid / Solar
Home
Grid / Solar
Home
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
L1 L2 L3
1.
Main circuit breaker/
main switch
Gridconnection
meter
Circuit breakers fuse
box
3.
Circuit breaker solar
inverter on sub-panel
2.
Circuit breaker solar
inverter
Connection current transformers grid connection Connection current transformers solar panels

14
03-ConnectingMIDkWh-meter
Maxemcanmeasuredierentelementsthroughan externalMIDcertiedkWh-meter.In
orderfortheautocongurationtofunctionproperly,thekWh-metermustbesettotheright
address.Thisisdoneasfollows:
Node/device Address
Solar #1 001
Solar #2 011
Charging station #1 002
Charging station #2 012
Heat pump #1 004
Heat pump #2 014
Locationofthe‘addressing’functioninthemenu
SET
OK
1 2 3
Addressing multiple elements
Numberofdevices
Devicetype
Standard addressing kWh-meter
Node/device Address
Gridconnection 100
Solar 001
Charging station 002
Heat pump 004
Addressing
ConguringanMIDkWh-meter
Holdthebuttonfor2sec.toenterthemenu,ortogoupinthemenu.
Scrolldownthroughmenuoradjustsettingvalue.
Presstogetintoamenuitemoracceptanadjustment.
Presstoadjustasetting.
NavigationthroughthemenuoftheABBB23/B24kWh-meter
If you see this icon in the display of the kWh-meter, there is an active
dataconnectionwithMaxem.

15
EN
PlacethekWh-meteronaDIN-railinthefusebox.
ConnectinganMIDkWh-meter
Conn ec tt heg re enPh oeni xconn ec tortop or tR S1o nMa xem.
Connect behind the main circuit breaker so that it measures the output of the
completegridconnection.NoticethatthiskWh-meterisfedfromthetopend.
SettheaddressofthekWh-metertocorrespondingnode.
SET
OK
1 2 3
Connection RS485 cable
on kWh-meter
A.
B.
D.
E.
RS1 port for
MIDkWh-meter
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
Connection RS485 cable
on Phoenix connector
C B A
Connect a 1-phase solar installation which supplies L3 of the main grid connection
also to L3 of the kWh-meter. The same goes for L2.
Connect the RS485 cable to the kWh-
meter and the supplied green Phoenix
connector as follows:
kWh-
meter
Wire
color
Phoenix-
connector
ABrown 1
BWhite 2
CGreen 3
C.
2
13

16
04 - Connecting the charging station
Option4.1-ConnectingaTeslaWallConnector
Install a circuit breaker and/or earth leakage circuit breaker for each
chargingstationatthemaximalpoweravailable.Seep.33.
Follow the installation instructions of the charging station. These
instructions can be found in the installation manual of the charging
station.
A.
B.
Set the Wall Connector to Slave mode
by placing the rotary switch in F
position.
On the Maxem side connect the
supplied green Phoenix connector
to the data cable. 2 wires need to be
connected:
• Connect wire 1 (orange-white) to
port2.
• Connectwire2(orange)toport1.
Connect the green Phoenix connector
toportRS2ofMaxem.
ConnectthedatacabletotheINportof
the clamp block of the Wall Connector:
• Connect wire 1 (orange-white) to
D+
• Connectwire2(oranje)toD-
Place a suitable UTP (CAT5 or CAT6) of the Wall Connector to Maxem. (To prevent
electromagnetic interference at the RS485 connection, it is recommended to use FTP
CAT6cableatdistancemorethan25m.Max:50m).
C.
F.
G.
E.
D.
Draaischakelaar
F
D+ D- D+ D-
In Uit
RS2 poort voor
laadstation
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
123

17
EN
TopLEDisgreen;theWallConnectorisreadytocharge.
Correct LED
indication
See installation manual Tesla Wall Connector for more information.
Top LED is green, center LED blinks red 4x; the Wall
Connector is set to Slave, but is not communicating
withMaxem..
Incorrect LED
indication

18
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
Option4.2-ConnectingaKEBAchargingstation
Install a circuit breaker and/or earth leakage circuit breaker at the
maximalpoweravailable. Seep.33.
Follow the installation instructions of the charging station. These
instructions can be found in the installation manual of the charging
station.
Place a suitable UTP (CAT5 or CAT6) cable from the charging station to Maxem and
clenchRJ45connectorsonbothsides.
Connect the UTP cable to the Ethernet
port of the charging station and the
ETHportofMaxem.
It is advisable to test the network cable with the help of a cable tester.
DSW1-Power(paragraphabove)
DSW2-Addressing(paragraphbelow)
DataactivityonETHport
Maxem
DataactivityonETHport
KebaP20orP30
UTP cable with RJ45 connectors
A.
B.
C.
D.
ETH port for
charging station
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4

19
EN
PutDSW1.3ONtoactivatesmartcharging.
SettheDIPswitchesofDSW1onthemaximalavailablepower.Andleavetherestofthe
DIPswitchesonOFF.
E.
F.
Example 10A
DSW1.6OFF
DSW1.7OFF
DSW1.8OFF
10A
13A
16A
Maximal current strength
20A
25A
32A
SettingsonDSW1
1 of 3-phase
SeeinstallationmanualKEBAP20/P30formoreinformation
SwitchotheKebaP20/P30(theDIPswitchsettingsonlybecomeactiveafterareset
ofthechargingstation).
G.

20
Option4.3-ConnectinganICUchargingstation
Connect the UTP cable to the Ethernet
port of the charging station and the
ETHportofMaxem.
It is possible to update the charging station rmware. This can be done via ICU
Connect, as soon as the charging station is online. ICU Alfen can assist you with this.
It is advisable to test the network cable with the help of a cable tester.
Data activity on
ETH port ICU
UTP cable with RJ45 connectors
D.
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
Install a circuit breaker and/or earth leakage circuit breaker for each
charging station at the maximal power available.Seep.33.
Follow the installation instructions of the charging station. These
instructions can be found in the installation manual of the charging
station.
Place a suitable UTP (CAT5 or CAT6) cable from the charging station to Maxem and
clenchRJ45connectorsonbothsides.
A.
B.
C.
DataactivityonETH
port Maxem
ETH poort voor
laadstation
REVISION
TITLE:
A4
DWG NO.
SCALE:1:2 SHEET 1 OF 2
WEIGHT:
A A
B B
C C
D D
E E
F F
4
4
3
3
2
2
1
DATESIGNATURE
DO NOT SCALE DRAWING
MATERIAL:
NAME
1
DRAWN
LINEAR:
CHK'D
APPV'D
MFG
Q.A
ANGULAR:
FINISH:
TOLERANCES: EDGES
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN MILLIMETERS
SURFACE FINISH:
DEBURR AND
BREAK SHARP
Maxem5-R4
Table of contents
Popular Measuring Instrument manuals by other brands

Eastern Energy
Eastern Energy PMS-714 Operation manual

C-LOGIC
C-LOGIC 290 instruction manual

Viavi
Viavi SmartClass OLP-87 operating manual

Troxler
Troxler EGauge 4590 Manual of Operation and Instruction

RKC INSTRUMENT
RKC INSTRUMENT LE100 General description

Kobold
Kobold Heinrichs KDS-K operating instructions

Factair
Factair Safe-Air F8100 operating manual

sauter
sauter HK-D instruction manual

Rosemount
Rosemount 1054A pH instruction manual

Johnson Controls
Johnson Controls EM-3000 Series Installation and operation manual

Dranetz
Dranetz hdpq xplorer user guide

Powerfix Profi
Powerfix Profi 280231 Operation and safety notes