Maxsys PC4204CXCF User manual

PC4204CXCF
Power Supply / Relay Output / Combus Repeater Module
v 3.0 • Installation Instructions
®
1.0 Introduction
The PC4204CXCF is a power supply/relay output module for use
with PC4010CF and PC4020CF Maxsys fire/security systems. The
PC4204CXCF provides one power output for system devices and 4
programmable relay outputs. Relay 1 can be used to repower the
Combus. This module will also regenerate the Combus data signal to
allow for longer wire runs. This module is not to be used for fire alarm
bells.
The PC4702BP must be used.The PC4702BP must be used.
The PC4702BP must be used.The PC4702BP must be used.
The PC4702BP must be used.
NOTE:NOTE:
NOTE:NOTE:
NOTE: The PC4204CXCF is the only power supply which can repower the
Combus on PC4010/PC4020CF systems. See the control panel
Installation
Manual
for details.
The PC4204CXCF is the only power supply unit for PC4010CF/PC4020CF
system devices which has UL/NFPArequired supervision integrated
into the control panel. Primary power for the PC4204CXCF must be
connected to the same branch circuit as the PC4020CF.
2.0 Specifications
• Transformer 16.5VAC - 40VA (DSC Part No. PTD1640U)
• Transformer 16VAC-80VA (BEI Part No. AS16N)*
*For commercial fire use only the 80VA transformer
• Backup battery: 4Ah to 38Ah sealed lead-acid (not provided)
• Current draw: 30 mA (from Combus)
• Connects to control panel via 4-wire Combus
• Selectable battery charging current (400mA or 1.2A)
• Auxiliary power output: 900mA, 12VDC (nominal)
• 4 programmable relay outputs: Form C; contact rating: 2A, 30VDC
• Tamper connection
3.0 Installing the PC4204CXCF
3.1 Unpacking
The PC4204CXCF package should include the following parts:
• One PC4204CXCF circuit board
• One PC4055CR cabinet with space for one 38Ah battery
• Five plastic standoffs
• 16VAC, 80VA transformer
3.2 Mounting
The PC4204CXCF should be located inside the PC4055CR cabinet,
mounted in a dry, secure location.
NOTE:NOTE:
NOTE:NOTE:
NOTE: The PC4204CXCF must be
installed within a fire enclosure, as defined in EN60950. The cabinet must
comply with the battery manufacturer’s installation instructions.
NOTE: The cabinet should be mounted in a safe and reliable manner. A
safety factor of 4 or higher must be provided.
Perform the following steps to mount the unit:
1.1.
1.1.
1. Press the five plastic standoffs through the mounting holes at the
back of the cabinet.
2.2.
2.2.
2. Secure the cabinet to the wall in the desired location. Use
appropriate wall anchors when securing the cabinet to drywall,
plaster, concrete, brick or other surfaces.
3.3.
3.3.
3. Press the circuit board onto the plastic standoffs to secure the
module to the cabinet.
Once the unit is mounted, wiring may be completed.
3.3 Installation and Wiring
NOTE: The PC4204CXCF is intended to be PERMANENTLY
CONNECTED and should be installed by service personnel only.
Before beginning to wire the unit, ensure that all power (AC
transformer and battery) is disconnected from the control panel.
Perform the following steps to complete wiring:
1. Connect the four panel-originating Combus wires to the
PC4204CXCF. Connect the red, black, yellow and green Combus
wires to the RED, BLK, YEL and GRN Combus In terminals,
respectively.
If Relay 1 is being used for Combus power, connect the Combus
wires according to the diagram below. Note that for this option,
jumper Con3 must also be set for “Repower Relay 1.”
Additional modules repowered by the PC4204CXCF should have
the black, yellow and green Combus wires connected to the BLK,
YEL and GRN Combus Out terminals respectively.
2. Complete all output wiring.
3. Connect the external tamper switch, if used.
Consult the wiring diagrams for further information.

Current Ratings
In order for the system to operate properly, the power output of the
PC4204CXCF module cannot be exceeded. For the maximum available
AUX current, refer to the Battery Selection Charts based on 24h/60h
standby power time. The maximum available AUX supply current is
dependent on the size of the transformer used as well as the selected
battery charge current. Use jumper J2 to control the supply current
(see below).
MaximumMaximum
MaximumMaximum
Maximum AUX Supply CurrAUX Supply Curr
AUX Supply CurrAUX Supply Curr
AUX Supply Currentent
entent
ent
BB
BB
BAA
AA
ATTERTTER
TTERTTER
TTERYY
YY
YCC
CC
CHARGEHARGE
HARGEHARGE
HARGE 40V40V
40V40V
40VAA
AA
A80V80V
80V80V
80V
AA
AA
A
CC
CC
CURRENTURRENT
URRENTURRENT
URRENT TT
TT
TRANSFORMERRANSFORMER
RANSFORMERRANSFORMER
RANSFORMER TT
TT
TRANSFORMERRANSFORMER
RANSFORMERRANSFORMER
RANSFORMER
HI-CHRG (400mA) 600mA 900mA
ON
HI-CHRG (1.2A) 150mA 900mA
OFF
NOTE: All devices connected to the AUX output must be UL Listed for fire
protective signaling service as well as burglary protective signaling service.
NOTE: When using the PC4204CXCF to repower additional Combus modules,
current calculations must be made to ensure that the maximum AUX supply
current is not exceeded.
Module Ratings
The current draw of compatible modules is listed below:
DeviceDevice
DeviceDevice
Device Current Draw (mA)Current Draw (mA)
Current Draw (mA)Current Draw (mA)
Current Draw (mA)
Keypad (LCD45XX) ............................................................................. 50
PC4108A Zone Expander .................................................................... 30
PC4116 Zone Expander ....................................................................... 30
PC4164 Wireless Receiver ................................................................. 110
PC4701 Fire Module ............................................................................. 35
PC4702BP Dual Bell Output Module ................................................. 75
PC4204CXCF Relay Output Module ................................................. 30
PC4216 Low Current Output Module ............................................... 15
ESCORT4580 Audio Assistant ..........................................................150
PC4400 Printer Module .......................................................................30
PC4820 Access Control Module ......................................................... 35
PC4936 Audio Interface Module ........................................................65
PC4401 Serial Interface Module ......................................................... 35
PC4850 Telephone Entry Module .....................................................135
Calculating Total Current Requirement
Once you have determined which modules will draw power from the
main panel, use the following chart to calculate the Combus current.
Combus Current Calculation Chart
Item Current (mA) x Quantity Total (mA)
Keypad 50 x
PC4108A* 30 x
Current required for connected devices =
PC4116* 30 x
Current required for connected devices =
PC4164 110 x
PC4701 35
PC4702BP 75 x
PC4204CXCF 30 x
PC4216* 15 x
Current required for connected devices =
Escort4580 150
PC4400/4401 30/35 x
PC4820 35 x
PC4850 135 x
PC4936* 65
Alt. Comm.
TT
TT
Total Combus Currotal Combus Curr
otal Combus Currotal Combus Curr
otal Combus Current =ent =
ent =ent =
ent =
NOTE: * These modules draw current from the Combus to power devices
external to the module. This current must be added to the total Combus current.
See manufacturer’s specifications for the current draw of each device. Each
LED assembly draws up to 20mA of current.
Combus Operation and Wiring
The Combus is used by the control panel and the modules to
communicate with each other. When the PC4204CXCF is used to
repower the Combus, please refer to the wiring diagram for the exact
wiring procedures. Note: Please follow the diagram exactly.
Modules can be home-run, connected in a daisy chain or T-tapped
anywhere on the Combus.
The following rules MUST be followed when wiring the Combus:
1.1.
1.1.
1. The Combus must be run in minimum 18-gauge wire.
2.2.
2.2.
2. No module can be more than 1000' (305m) in cable length from
the PC4204CXCF (see below ‘Combus Extensions’).
3.3.
3.3.
3. Shielded wire should only be used in areas that present excessive
RF noise or electromagnetic interference. If shielded wire is used,
the maximum distance a module can be located from the
PC4204CXCF is significantly reduced. Check the capacitance rating
of the wire to calculate the maximum distance (see “Capacitance
Limits” below). NOTE: Shielded wire is not recommended.
4.4.
4.4.
4. The total capacitance of the Combus wiring must not exceed 80nF
between the control panel and PC4204CXCF module or between
two PC4204CXCF modules (see “Capacitance Limits” below).
Long Distance Combus Extensions
The length of Combus from a PC4204CXCF Combus Regenerator can
be extended beyond 1000’, providing the following conditions are met:
• Combus must be regenerated and repowered at both ends of the wire
run using PC4204CXCF and modules.
• No other modules are to be connected along the long distance wire run.
• A maximum distance of 4000’ can be achieved between two
PC4204CXCF devices. To extend further, additional PC4204CXCF
devices should be used.
NOTE: The wiring used to connect this equipment must be insulated with
PVC, TFE, PTFE, FEP, neoprene or polymide.
Line Loss
When current is drawn through a piece of wire, voltage will be lost
due to the wire’s resistance. This voltage loss must be considered for
all installations.
To ensure proper operation, at least 12.5VDC must be applied to all
modules on the system (when AC is applied and the battery is fully
charged). If less than 12.5VDC is applied, system operation will be
adversely affected.

To correct the problem, try any or all of the following:
1. Connect another PC4204CXCF power supply near the module to
provide power to the Combus.
2. Reduce the length of the Combus run to the module.
3. Increase the gauge of wire.
Capacitance Limits
An increase in capacitance on the Combus will affect data transmission
and will cause the system to slow down. Capacitance will increase for
every foot of wire added to the Combus. The capacitance rating of the
wire used will determine the maximum length of the Combus, between
two PC4204CXCF Combus Repower/Regenerator modules.
The following chart indicates the total Combus wire allowed depending
on the capacitance rating of the wire used:
Wire Capacitance per
1000’(300m)
TOTAL Combu s Wire
Length
15nF 5300’/1616m
20nF 4000’/1220m
2 5n F 32 00’ /97 6m
3 0n F 26 66’ /81 0m
3 5n F 22 80’ /69 3m
4 0n F 20 00’ /60 8m
Wires run in parallel also increase Combus capacitance. For example,
when using 20nF wire, the following would be some of the
combinations allowed:
• Four wire runs at 1000'/305m each
• Six wire runs at 666'/203m each
• Eight wire runs at 500'/152m each
• 10 wire runs at 400'/122m each etc…
Contact the wire manufacturer for the capacitance ratings of the wire
being used.
3.4 Regenerating Combus
This module will regenerate the Combus signal as it passes from one
side to the other. The LEDs on the module will illuminate whenever
there is activity on either side of the input or ouput of the module.
LED 1LED 1
LED 1LED 1
LED 1 illuminates when the module transmits data on ‘Combus In’
LED 2LED 2
LED 2LED 2
LED 2 illuminates when the module transmits data on ‘Combus Out’
The PC4204CXCF module will isolate ‘Combus In’ from any short
circuit problems on ‘Combus Out’. In the event of a problem, the
PC4204CXCF module will generate a module fault along with the
modules on the disabled Combus. This information can be used to
determine which section of Combus is disabled on the system.
When connecting the PC4204CXCF to the Combus, care must be taken
to ensure that the ‘Combus In’ terminals are connected to the wires
originating from the control panel (or a module that may be situated
between the PC4204CXCF and the control panel).
3.5 Applying Power
NOTE: Do not connect power until all wiring is complete.
After all wiring is completed, apply power to the control panel.
Connect the battery leads to the battery, then connect the AC
transformer. Then, connect power to the PC4204CXCF: first connect
the battery leads, then the AC transformer.
12V 38Ah Battery
(Not supplied)
PC4204CX
PC4055C/CR
Cabinet
Power limited access Power limited access
IMPORTANT: A minimum of 1/4" (6.4mm) separation
must be maintained at all points between power limited
wiring and all other non-power limited wiring and
connections. Wire entry for power limited wiring must
be separate from non-power limited wiring.
For more information on control panel power specifications, see the
control panel
Installation Manual
.
NOTE: It is the installer’s responsibility to provide adequate protection for
the transformer used in the primary and secondary circuit according to the
rated current of the transformer. The transformer used must be Class2, Fail
Safe as defined within EN61558-1 and must meet the applicable requirements
of the EN60950 Standard. A readily accessible disconnect device must be
incorporated into the fixed wiring and should disconnect both poles
simultaneously. The wiring connected to the PC4204CXCF must be
mechanically protected, routed, supported, clamped or secured in a manner
that prevents excessive strain on wire and terminal connections, loosening of
terminal connections and conductor insulation damage.
NOTE: Do not connect fully discharged (less than 10V) or damaged batteries
to the PC4204CXCF.
3.6 Battery Selection Charts
The charts below are to determine the battery required to support the
AUX output of the module for either 24 hours or 60 hours standby,
followed by 15 minutes of alarm.
38Ah
38Ah
Battery Selection for 24hr Standby and 15-minute Alarm
Battery Selection for 60hr Standby and 15-minute Alarm
24 Hr Standby Current (mA)
60 Hr Standby Current (mA)
150
60 125 190 220 285 380 600
0
300 450 550 700 940 1000
NOTE: If the required Ah (Amp hours) cannot be achieved with one battery,
two batteries may be connected in parallel to obtain a higher Ah rating.

©2002 Digital Security Controls Ltd.
Toronto, Canada • www.dsc.com
Technical Support 1-800-387-3630
Printed in Canada 29005815 R005
Direct all comments and suggestions
concerning DSC publications to
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security
Controls Ltd. could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and
used properly, in strict accordance with the manufacturer’s instructions, may cause
interference to radio and television reception. It has been type tested and found to
comply with the limits for Class B device in accordance with the specifications in
Subpart “B” of Part 15 of FCC Rules, which are designed to provide reasonable
protection against such interference in any residential installation. However, there is
no guarantee that interference will not occur in a particular installation. If this equip-
ment does cause interference to television or radio reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•Re-orient the receiving antenna
•Relocate the alarm control with respect to the receiver
•Move the alarm control away from the receiver
•Connect the alarm control into a different outlet so that alarm control and receiver
are on different circuits.
If necessary, the user should consult the dealer or an experienced radio/televi-
sion technician for additional suggestions. The user may find the following
booklet prepared by the FCC helpful: “How to Identify and Resolve Radio/
Television Interference Problems”. This booklet is available from the U.S. Gov-
ernment Printing Office, Washington, D.C. 20402, Stock # 004-000-00345-4.
PC4204CF Outputs Module Number: PC4204CFModule Number: PC4204CF
Module Number: PC4204CFModule Number: PC4204CF
Module Number: PC4204CF # I
______I
______I (1-16 = XX)
Partition
Output 1 2 3 4 5 6 7 8 Zone Schedule # Pulse Timer
[000702XX01] PC4204CF Relay 1 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX02] PC4204CF Relay 2 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX03] PC4204CF Relay 3 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
[000702XX04] PC4204CF Relay 4 I
______I
______II
______I
______I
______I
______I
______I
______I
______I
______II
______I
______I
______II
______I
______II
______I
______I
______I
4. Enrolling the Module
Once connected, the module must be enrolled on the system. To enroll
the module, perform the following:
1. Enter Installer Programming by pressing [*] [8] [Installer Code].
2. Scroll to “Module Hardware” and press the [*] key.
3. Scroll to “Enroll Module” and press the [*] key.
4. Scroll through the different modules until “PC4204” is displayed.
Press the [*] key.
5. The message “Create Tamper on Desired Unit” will be displayed.
To create the required tamper, secure the tamper zone on the
module and then open it. The transition from secure to violated
enrolls the module. After this is done, the keypad will display
the module number and will confirm enrollment (e.g., “PC4204
Mod 01 Enrolled”).
For more information regarding module enrollment, see the control
panel
Installation Manual
.
5. Programming the Module
To access PC4010CF/PC4020CF programming, enter [*][8] followed
by the Installer Code. Each relay output must be programmed. Please
see the control panel
Installation Manual
and
Programming Worksheets
for a detailed list of output options.
NOTE: Relay 1 must not be programmed if used for Combus power. Ensure
that Jumper CON3 is set to “Repower Relay1.”
NOTE: PC4204CXCF relay outputs cannot be used for fire system notification
appliances.
Other Maxsys Repeater manuals