owner’s manual
12
ǃ
噝
噝
噝
噝
Installation
Instructions
RELIEF VALVE
WARNING:
TO FILL THE WATER HEATER
WARNING:
CAUTION:
ELECTRICAL CONNECTIONS
WARNING:
Water heater junction box
Ground screw
Junction box cover
240V
L2
L1
CAUTION:
˛
A new combination temperature and pressure-relief
valve, complying with the Standard for Relief Valves and
Automatic Gas Shut-Off Devices for Hot Water Supply
Systems, ANSI Z21.22, is supplied and must remain
installed in the opening provided and marked for the
purpose on the water heater. No valve of any type
should be installed between the relief valve and the tank.
Local codes shall govern the installation of relief valves.
The pressure rating of the relief
valve must not exceed 150 PSI, the maximum working
pressure of the water heater as marked on the rating plate.
The BTUH rating of the relief valve must not be less than the
input rating of the water heater as indicated on the rating label
located on the front of the heater (1 watt=3.412 BTUH).
Connect the outlet of the relief valve to a suitable open drain so
that the discharge water cannot contact live electrical parts or
persons and to eliminate potential water damage.
Piping used should be of a type approved for hot water
distribution. The discharge line must be no smaller than the
outlet of the valve and must pitch downward from the valve to
allow complete drainage (by gravity) of the relief valve and
discharge line. The end of the discharge line should
not be threaded or concealed and should be protected
from freezing. No valve of any type, restriction or reducer
coupling should be installed in the discharge line.
Do not mis-wire electrical connections. 240V AC must be
applied to L1 and L2 wires as shown in illustrion to the right.
Failure to do so will VOID the warranty, and can result in 120V
applied to water heater, which may damage the compressor or
other electrical components.
To reduce the risk of excessive pressures and temperatures in
this water heater, install temperature and pressure protective
equipment required by local codes and no less than a
combination temperature and pressure relief value certified by
a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or
materials, as meeting the requirements for Relief Valves and
Automatic Gas Shut-Off Devices for Hot Water Supply
systems,ANSI Z21.22. This valve must be marked with a
maximum set pressure not to exceed the marked maximum
working pressure of the water heater. Install the valve into an
opening provided and marked for this purpose in the water
heater, and orient it or provide tubing so that any discharge
from the valve exits only within 6 inches above or at any
distance below,the structural floors and does not contact any
live electrical part. The discharge opening must not be blocked
or reduced in size under any circumstances.
A separate branch circuit with copper conductors, overcurrent
protective device and suitable disconnecting means must b e
provided by a qualified eldctricianAll wiring must conform to local codes or latest edition of
National Electrical Code ANSI/NFPA 70.
The water heater is completely w ired to the jun ction box at
the top of the water heater. An opening for 1/2” or 3/4”
electrical fitting is provided for field wiring connection.
The voltage requirements and wattage load for the water
heatr are specified on the rating label on the front of the
water heater.
The branch circuit wiring should include either:
1. Metallic conduit or metallic sheathed cable approved
for use as a grounding conductor and installed with fittings
opproved for the purpose
2. Nonmetallic sheathed cable, metallic conduit or metallic
sheathed cable not approved for use as a ground conductor
shall include a separate conductor for grounding. It should be
attached to the ground terminals of the water heater and the
electrical distribution box.
Proper ground connection is
essential. The presence of water in the piping and water
heater does not provide sufficient conduction for a
ground.Nonmetallic piping,dielectric unions,flexible connectors,
etc., can cause the water heater to be electrically isolated.
ˈ
0'9,8I
The tank must be full of water before heater is turned
on. The water heater warranty does not cover damage
or failure resulting from operation with an empty or
partially empty tank.
Make certain the drain valve is completely closed.
Open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to allow the air to
vent from the water heater and piping.A stady flow of
water from the hot water faucet(s ) indicates a full water
heater.
/