Mebay DC30D User manual

DC30D
GENSET CONTROLLER
USER MANUAL
Software Version
No.
Version
Date
Note
1
V1.0
2018-9-1
Original release.

DC30D GENSET CONTROLLER USER MANUAL
1
Symbol Description
Symbol
Description
Note
Remind operators to operate correctly, otherwise it may cause
the equipment not to work correctly.
Be care
It is indicated that potential hazards can damage equipment
without proper precautions.
Warning
It is indicated if appropriate preventive measures are not taken,
potentially dangerous situations may result in death, serious
personal injury or significant property losses.
Chongqing Mebay Technology Co.,Ltd
Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing.
Tel:+86-23-6869 3061
Fax:+86-23-6765 8207
Web:http://www.mebay.cn
http://www.cqmb.cn
E_mail:[email protected]

DC30D GENSET CONTROLLER USER MANUAL
2
Warning
1.The installation of this equipment must be carried out by professionals.
2.When installing and operating the controller, please read the entire instruction
manual first.
3.Any maintenance and commissioning of the equipment must be familiar with all the
equipmen
4.t, safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5.The engine must have an overspeed protection device independent of the
controller system to avoid casualties or other damage caused by engine out of
control.
6.After the installation of the controller is completed, please verify that all protection
functions are valid.
Be Care
1.Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2.During the operation of the engine, do not disconnect the battery,otherwise it may
cause damage to the controller.

DC30D GENSET CONTROLLER USER MANUAL
3
Catalogue
1、Summary………………………………………………………………………4
2、Main Features…………………………………………………………………4
3、Parameters Display…………… ……………… …………… ………………4
4、Parameters……………………………………………………………………4
5、Overall Dimension and Wiring Diagram…………………… … … … ……5
6、Installation Instruction…………………………… ………… ………………7
7、Panel and Display Instruction………………………………………………8
8、Control and Operation Instruction…………………………… ……………8
9、Parameters Setting…………………………………… ……………………10
10、Fault finding………………………………………………………………12
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form(including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.

DC30D GENSET CONTROLLER USER MANUAL
4
Summary
This Controller Series is specialized for small diesel, gasoline, gas generator
sets’start, stop,monitor and defaults checking as well as parameters setting.
The controller has a point array LCD screen, can display various faults in the same
time that the genset will be stopped once it can not work smoothly.
There are Chinese/English interface options, more language can be set
according to user’s request. All the parameters can be configured through
the front face buttons or use programmable interface by USB to adjust via
PC. It can be widely applied for all kinds of auto control system of gensets.
Main Features
32 units Micro-procession technology is used.
1.8 inches 128*64 LCD display with backlight, option language interface
(Chinese/English), user’s language set if necessary.
PC front face panel, which is water-proof, oil-proof, UV proof so that the durability
is longer.
USB Port: parameters can be set even without power.
All the parameters can be set through front panel buttons.
Collect and display a variety of engine and generator parameters.
Records function: relative faults shall be recorded in real time.
It has 5 relay outputs, 3 of which are configurable, and more than 10
functions can be selected for each channel.
1 switch value input, and each can be set as max 20 functions.
3 sensor simulation input connectors, various kinds of units can be set.
Sensor can be self-defined by front face button or PC software.
Various of crank conditions(RPM,Frequency, Oil Pressure) can be chosen
Control Protection:Auto Start/Stop of genset,load transfer and perfect
failure display and protection.
Standard water-proof rubber gasket. The waterproof can reach IP54.
Module design: All the connections are adapted with European connectors
so that installation, connection, repair and replacement can be more
easily.
Parameters Display
Engine RPM
Engine oil pressure
Engine temperature
Engine fuel level
Engine battery voltage
Generator voltage L-N
Generator current A

DC30D GENSET CONTROLLER USER MANUAL
5
Generator Frequency Hz
Generator active power KW
Successful start Times
Current running time
Total running time
Classes maintenance notice
Protection
Over speed
Under speed
Low oil pressure
High temperature
Low fuel level
External emergency alarm
Sensor Open
Over Frequency
Under Frequency
Over voltage
Under voltage
Over current
Maintenance expire
Low water level alarm
Emergency Stop
Crank failure
Stop Failure
Over battery voltage
Under Battery voltage
Parameters
Options
Parameters
Operation Voltage
DC8-36V Continuous
Power Consumption
Standby:24V:MAX 1W
Working:24V:MAX 2W
AC Voltage Input
1P2W(L-N input) 30VAC-360VAC(ph-N)
Rotate speed sensor
Frequency
50-9000Hz
Generator Frequency input
50/60Hz
MAX Accumulating Time
9999.9Hours(Min Store time:6min)
Fuel Relay Output
1Amp DC+VE Supply voltage
Start Relay Output
1Amp DC+VE Supply voltage
Programmable Relay output 1
1Amp DC+VE Supply voltage

DC30D GENSET CONTROLLER USER MANUAL
6
Programmable Relay output 2
1AMP Non-contact-Normal open--Normal close output
Programmable Relay output 3
1AMP Non-contact Normal Open output
Switch value input
Available if connecting with Battery -
Insulation strength
Apply AC1.5kV voltage between high voltage terminal
and low voltage terminal; The leakage current is not
more than 3mA within 1min.
Working condition
-25-65℃
Storage condition
-40-85℃
Protection Level
IP54:when waterproof rubber gasket is added between
controller and its panel
Overall dimension
106mm×86mm×45mm
Panel cutout
78mm×66mm
Weight
0.25Kg
Overall Dimension and Wiring Diagram
Overall Dimension:
106
86
86 65
8.8 36.2
106
8.8
36.2
77 78
66
Descriptions of terminal connection

DC30D GENSET CONTROLLER USER MANUAL
7
No.
Function
Description
Cable
cross
sectional
area
1
Battery Negative Input B-
Controller power supply input B-.
1.5mm2
2
Battery Negative Input B+
Controller power supply input B+.
1.5mm2
3
Emergency Stop Input
B+ voltage input is active, and connected
to emergency stop normal closed button.
1.0mm2
4
Fuel Output
Rated current 1A; power supplied by PIN 2.
1.0mm2
5
Crank Output
Rated current 1A; power supplied by PIN 2.
1.0mm2
6
Remote Start Input
Ground connected is active (B-)
1.0mm2
7
Aux. Input
Connect t fuel level sensor or switch input
according to function selection
1.0mm2
8
Oil Pressure Input
Connect t Oil Pressure sensor or switch
input according to function selection
1.0mm2
9
Engine Temp. Input
Connect temperature sensor or switch
input according to function selection
1.0mm2
10
Magnetic Pickup
Connect to speed sensor, and shielded
wire is recommended. The other end of
speed sensor is connected to B-.
0.5mm2
11
Generator Voltage L
Gens voltage Input,AC30-360V.
12
Generator Voltage N
1.0mm2
13
Load CT Secondary I* (in)
Current Transformer Secondary Rated 5A.
1.5mm2
14
Load CT Secondary I (out)
1.5mm2
15
Aux. Ouput1
Rated current 1A; power supplied by PIN 2.
1.0mm2
16
Aux. Ouput2
Rated current 1A; power supplied by PIN 2.
1.0mm2
17
Aux. Ouput3
Rated current 1A; power supplied by PIN 2.
1.0mm2

DC30D GENSET CONTROLLER USER MANUAL
8
Typical Wiring Diagram
4
5
3
21
1211
L
15 17
- VE
+ VE
16
L
N
10
N
13 14
I* I
6 7 8 9
Remote Start
EM. STOP
WL
Aux. Input
OP Input
Temp. Input
Crank
Fuel
Aux. Output 1
Magnetic
GEN VOLTS
FROM GENERATOR
TO LOAD
ALT
Aux. Output 2
Aux. Output 3
Pickup
MAX 1A
MAX 1A
MAX 1A
MAX 1A
MAX 1A
Note:Please don’t move battery during running status or it may cause the
controller broken!
WARNING:When generator is on-load, C. T. secondary must not be open
circuit, Otherwise, the high voltage generated will pose a danger to personal safety.

DC30D GENSET CONTROLLER USER MANUAL
9
Installation instruction
The controller should be installed by four accessories and screw.
Panel Cutout:W78mm*H66mm.
78
66
Note: If the controller is installed directly in the genset shell or other fluctuated
equipment, the rubber pad must be installed.
Battery Voltage Input
DC30D controller is suitable for 98-18 VDC battery voltage. Battery negative must be
reliably connected to the enclosure of the engine. The controller power supply B+
and B- must be connected to battery positive and negative, and the wire size must
not be less then 1.5mm2.
NOTE:
In case of floating charger connect charger output to battery positive and negative
directly, then, connect battery positive and negative poles to controller positive and
negative power supply
AC current input
Current transformer with rated secondary current 62.5mA must be externally
connected to the controller current input.
WARNING:When generator is on-load, C. T. secondary must not be open
circuit, Otherwise, the high voltage generated will pose a danger to personal safety.
Withstanding voltage test
If withstanding voltage test is conducted after the controller has already been
installed onto the control panel, please unplug all controller terminal connections in
order to prevent high voltage from damaging it.

DC30D GENSET CONTROLLER USER MANUAL
10
Panel and display
Panel Operation
Key Function Description
Button
Name
Main function
Stop
Reset
Revert
Can stop generator under manual/auto mode.
Can reset shutdown alarm.
During stop procession, pressing this key again can
stop generator immediately.
Pressing this key can cancel the setting and back to
upper class under edition.
Under the setting mode with checking data, the data
can be saved and system will exit after pressing.
In standby mode, press the button for more than 3
seconds to check the alarm records under stop mode.
Manual
Start
Decrease
Start the genset.
Under edition mode, to decrease the numbers.
Under records mode, pressing this key to change the
page.
Auto
Increase
Pressing this key will set the module into auto mode.
Under edition mode, to increase the numbers.
Under records mode, pressing this key to change the
page.
Page
change
Confirm
Page change.
Confirm the change under edition mode.
In standby state, press for 3 seconds to enter the
parameter setting mode.
Choose alarm records under records checking mode.
+
Setting
Mode
Pressing “Page” and “Stop” simultaneously to come
into setting mode.
LCD
Manual start
Alarm indicator
Stop mode
Auto mode
Page change

DC30D GENSET CONTROLLER USER MANUAL
11
Alarm records checking
DC30D controller can save three group of alarm records which contains the alarm
record data includes detailed data such as alarm time, generator parameters, engine
parameters, etc.
How to check the alarm records:
1)Press the button for more than 3 seconds to check the alarm records under
stop mode.
2)In the history alarm list browsing interface, press to move up the cursor, and
press to move down the cursor to choose the record you need. Press to
confirm the record and come into history records checking page.
3)Press or to change the alarm record data. Press to return to the
history alarm list browsing interface.
4)In the history alarm list browsing interface, press to exit.
Control and operation instruction
Manual Start
In stop mode turn the starter key from OFF to ON position to power on the
controller, then change the starter key position to START to begin cranking; after the
engine fires, release the starter key(crank disconnect condition is gen
frequency>14.0Hz), then the controller can monitor and display the relevant
parameters of the generator set in real time.
Manual stop
Under any circumstances, if starter key is turned from ON to OFF position, it will
lead to shutdown.
Please note before manually start:
1) Please make sure if the connection is right and meet requests.
2) There is fuse in the DC power of controller and make sure if the battery + and - are
connected rightly.
3) Please make sure if all the parameters are right and the oil pressure indicators are
in normal light.
4) Please take appropriate measurement so that the genset shall be stopped under
emergency.
5) Manual start mode:
Press the "STOP" to ensure the stop gear before starting. Press "MANUAL"
manual gear indicator light on, at this time will detect the normal connection of
each sensor, if the sensor is open, then report the sensor open alarm, if normal, then
execute the start-up process of the unit. When the unit is running normally, press the
"STOP" and the controller will perform the parking process in the following
sequence:

DC30D GENSET CONTROLLER USER MANUAL
12
Manual start and stop process:
Warming-up
time
Man-
ual
Start
0RPM
Idle
Rated speed
0S 2S 8S 10S 0S 10S 0S 10S 30S
Pre-
heat
delay
Start
Crank
delay
Crank test
time
Safe
time
Start idle
time
rated
runn-
ing
Stop idle
time
Wait
Stop
ETS
solen-
oid
hold
6) After the manual start is successful, pressing the "automatic key" can be converted
into an automatic file. The specific working time is as follows:
0RPM 0S 2S 8S 10S 0S 10S 1S 10S 0S 10S 30S
Start idle
time
rated
running
Man-
ual
Start
Idle
Rated speed
Pre-
heat
delay
Start
Crank
delay
Crank test
time
Safe
time
Cooling
running time
Stop idle
time
ETS
solen-
oid
hold Wait
Stop
Warming-up
time Stop delay
7) Automatic starting mode:
Press the "STOP" to ensure the stop gear before starting. Press "AUTO"
automatic gear indicator light on, at this time will wait for the remote start signal to
be valid, the unit will execute the start process in the following sequence. When the
unit enters the normal rated operation, the power generation closing relay will output
and switch to the power supply of the generating unit.
The controller will detect the remote start signal in real time. When the remote
start signal fails, the " Stop delay" will be executed. After the completion of the stop
delay, the engine high-speed " Cooling time" and the subsequent shutdown process
will be executed.
Auto start and stop process:
Auto
Start
delay
0RPM
Idle
Rated speed
Pre-
heat
delay
1S 0S
Start
Crank
delay
2S
Crank test
time
8S
Crank rest
time
8S
Cranking
time
10S
Safety
time
10S
Start idle
time
0S 10S
rated
runn-
ing Stop delay
1S
Cooling
running time
10S
Stop idle
time
0S
ETS
solen-
oid
hold
10S
Fail to
stop
30S
Idle
Rated speed
Auto
Start
delay
Pre-
heat
delay
Warming-up
time

DC30D GENSET CONTROLLER USER MANUAL
13
8) Notices in Starting Process
Note 1: During the Cranking time, the controller automatically detects the speed
signal, frequency signal and oil pressure value (according to the parameter setting) to
reach the judgment condition of successful start, then the judgment is that the start is
successful and the motor relay is closed.
Note 2: Within the safety delay, only respond to emergency stop, immediate
stop, over speed, over frequency, other alarms are not responded to.
Note 3: No response to alarm and warning of underspeed, low frequency, under
voltage, over current during start idle time.
Note 4: No response to low frequency, under voltage, over current and over
power is required when entering the Warming-up time.
Note 5: After entering rated operation, the Gens load relay output.
Note 6: In the process of shutdown, if the remote starting signal is restored to
be valid within the " Cooling time", the rated operation will be entered again.
Note 7: If the stop key is pressed again during idle time, the idle time will be
cancelled and the stop operation will be executed directly.
Warnings and Shutdown Alarms
Warnings
Notes: Warning is a non-serious failure state, which will not harm the gensets
system for the time being. It only reminds operators to pay attention to the situation
that does not meet the requirements and solve it in time to ensure the continuous
operation of the system. When the warning occurs, the gensets does not stop. Once
the fault is removed, the warning is automatically canceled.
Low Fuel Level Sensor Warning
When the controller detects that the fuel level is lower than “Low fuel level warning”,
Then start warning delay and the duration (Normal alarm delay) have not returned to
normal, the warning of the engine low fuel level sensor is reported. "ALARM" lights
on, without stopping the engine, and displays "Low FL sensor " on the LCD screen.
Low Fuel Level Switch Warning
When the controller detects that the Low fuel level warning switch input is valid to the
ground, Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of Low fuel level switch is reported. "ALARM" lights
on, without stopping the engine, and displays " Low FL switch " on the LCD screen.
External Instant Warning
When the controller detects the validity of the "instant alarm switch input" at the
switch input port, Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of the External instant warning is reported.

DC30D GENSET CONTROLLER USER MANUAL
14
"ALARM" lights on, without stopping the engine, and displays " Istant warn " on the
LCD screen.
Oil Pressure Sensor Opened Warning
When the safety delay is over, the controller detects that the Oil Pressure sensor is
disconnected, Then start warning delay and the duration (Normal alarm delay) have
not returned to normal, the warning of the Oil Pressure sensor opened is reported.
"ALARM" lights on, without stopping the engine, and displays "OP sensor open " on
the LCD screen.
Temperature Sensor Opened Warning
When the safety delay is over, the controller detects that the Temperature sensor is
disconnected, Then start warning delay and the duration (Normal alarm delay) have
not returned to normal, the warning of the Temperature sensor opened is reported.
"ALARM" lights on, without stopping the engine, and displays "WT sensor open " on
the LCD screen.
Fuel Level Sensor Opened Warning
When the safety delay is over, the controller detects that the Fuel level sensor is
disconnected, Then start warning delay and the duration (Normal alarm delay) have
not returned to normal, the warning of the fuel level sensor opened is reported.
"ALARM" lights on, without stopping the engine, and displays " FL sensor open " on
the LCD screen.
Maintenance expiration warning
When the action after the primary maintenance expired set as “warning”, When the
countdown to maintenance is detected as "0", Then start warning delay and the
duration (Normal alarm delay) have not returned to normal, the warning of
Maintenance expiration is reported. "ALARM" lights on, without stopping the engine,
and displays "Maintain end" on the LCD screen.
High Battery Voltage Warning
When the controller detects that the battery voltage is higher than “Over battery
voltage warning”, Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of High Battery Voltage is reported.
"ALARM" lights on, without stopping the engine, and displays " Over BATT volt " on
the LCD screen.
Under Battery Voltage Warning
When the controller detects that the battery voltage is lower than “Under battery
voltage warning”, Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of Under Battery Voltage is reported.
"ALARM" lights on, without stopping the engine, and displays " Under BATT volt "
on the LCD screen.
Starting fault
Fail to Start

DC30D GENSET CONTROLLER USER MANUAL
15
If the number of cranks exceeds the predetermined number of cranks, the failure of
start-up will be reported if the start-up of the generating unit is still unsuccessful.
"ALARM" lights on, without stopping the engine, and displays " Crank failure " on
the LCD screen.
Shutdown Alarms
Warning: After the Shutdown Alarm occurs, the system will be locked
immediately and the generator set will be stopped.Only after troubleshooting, press
key to clear the alarm, can it be re-operated.
Notes:When the shutdown alarm failure occurs, the "ALARM" lights flicker
and the generator unit automatically stops.
Over Speed Alarm
When the controller detects that the engine speed is higher than “ Over speed
alarm”, Then start alarm delay and the duration (Emergency delay) have not returned
to normal, the alarm of over speed is reported. "ALARM" lights flicker, Generator
stops running, and displays " Over Speed " on the LCD screen.
Under Speed Alarm
When the controller detects that the engine speed is under than “ Under speed
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of under speed is reported. "ALARM" lights flicker,
Generator stops running, and displays " Under Speed " on the LCD screen.
Oil Pressure Sensor Opened Alarm
When the safety delay is over, the controller detects that the Oil Pressure Sensor is
disconnected, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of the Oil Pressure Sensor opened is reported.
"ALARM" lights flicker, Generator stops running, and displays " OP sensor open" on
the LCD screen.
Temperature Sensor Opened Alarm
When the safety delay is over, the controller detects that the Temperature Sensor is
disconnected, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of the Temperature Sensor opened is reported.
"ALARM" lights flicker, Generator stops running, and displays " WT sensor open "
on the LCD screen.
Fuel Level Sensor Opened Alarm
When the safety delay is over, the controller detects that the Fuel Level Sensor is
disconnected, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of the Fuel Level Sensor opened is reported. "ALARM"
lights flicker, Generator stops running, and displays " FL sensor open " on the LCD
screen.

DC30D GENSET CONTROLLER USER MANUAL
16
Low Oil Pressure Sensor Alarm
When the controller detects that the engine Oil Pressure is lower than “ Low oil
pressure alarm”, Then start alarm delay and the duration (Normal alarm delay) have
not returned to normal, the alarm of low Oil Pressure is reported. "ALARM" lights
flicker, Generator stops running, and displays " Low OP sensor " on the LCD screen.
High Temperature Sensor Alarm
When the controller detects that the engine Temperatur is higher than “ High
temperature alarm”, Then start alarm delay and the duration (Normal alarm delay)
have not returned to normal, the alarm of High Temperature is reported. "ALARM"
lights flicker, Generator stops running, and displays " High WT sensor " on the LCD
screen.
High Temperature Switch Alarm
When the controller detects that the High temperature alarm switch input is valid to
the ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of High Temperature Switch is reported. "ALARM"
lights flicker, Generator stops running, and displays "High WT switch" on the LCD
screen.
Low Fuel Level Switch Alarm
When the controller detects that the Low fuel level alarm switch input is valid to the
ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Low fuel level switch is reported. "ALARM" lights
flicker, Generator stops running, and displays " Low FL switch " on the LCD screen.
External Instant Alarm
When the controller detects that the External instant alarm input input is valid to the
ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of External instant input is reported. "ALARM" lights
flicker, Generator stops running, and displays " Instant alarm" on the LCD screen.
Over Frequency Alarm
When the controller detects that the generator frequency is higher than “ Over freq
alarm”, Then start alarm delay and the duration (Emergency delay) have not returned
to normal, the alarm of Over Frequency is reported. "ALARM" lights flicker,
Generator stops running, and displays "Over frequency" on the LCD screen.
Under Frequency Alarm
When the controller detects that the generator frequency is lower than “ Under speed
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Under Frequency is reported. "ALARM" lights flicker,
Generator stops running, and displays "Under frequency" on the LCD screen.
Over Voltage Alarm

DC30D GENSET CONTROLLER USER MANUAL
17
When the controller detects that the voltage of the generator is higher than “Over
voltage alarm”, Then start alarm delay and the duration (Gens Abnormal Delay) have
not returned to normal, the alarm of Over Voltage is reported. "ALARM" lights flicker,
Generator stops running, and displays " Over Voltage " on the LCD screen.
Under Voltage Alarm
When the controller detects that the voltage of the generator is lower than “ Under
voltage alarm”, Then start alarm delay and the duration (Gens Abnormal Delay) have
not returned to normal, the alarm of Under Voltage is reported. "ALARM" lights flicker,
Generator stops running, and displays "under Voltage" on the LCD screen.
Over Current Alarm
When the controller detects that the Current of the generator is higher than “ Current
over-load alarm”, Then start alarm delay and the duration (Over current delay) have
not returned to normal, the alarm of Over Current is reported. "ALARM" lights flicker,
Generator stops running, and displays "Over Current" on the LCD screen.
Maintenance Expiration Alarm
When the action after the primary maintenance expired set as “alarm”, When the
countdown to maintenance is detected as "0", Then start warning delay and the
duration (Normal alarm delay) have not returned to normal, the warning of
Maintenance expiration is reported. "ALARM" lights on, Generator stops running, and
displays "Maintain end" on the LCD screen.
Low Water Level Switch Alarm
When the controller detects that the Low water level alarm switch input is valid to the
ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Low water level switch is reported. "ALARM" lights
flicker, Generator stops running, and displays " Low Water Level " on the LCD
screen.
Emergency Stop Alarm
When the controller detects that the input voltage of PIN 3 is less than 2V, Then start
alarm delay and the duration (Emergency delay) have not returned to normal, the
alarm of Emergency Stop is reported. "ALARM" lights flicker, Generator stops
running, and displays "Emergency stop" on the LCD screen.
Stop Failure With Speed Alarm
When the controller detects that the speed is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights flicker,and displays
"Stop fail-RPM" on the LCD screen.
Stop Failure With Frequency Alarm
When the controller detects that the frequency is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights flicker,and displays
"Stop fail-Hz" on the LCD screen.

DC30D GENSET CONTROLLER USER MANUAL
18
Stop Failure With Pressure Alarm
When the controller detects that the Oil Pressure is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights flicker,and displays
"Stop fail-OP" on the LCD screen.
Parameter setting
Please set the parameters according to below steps:
1)In the stop mode, please and simultaneously, then loose so that
you can come to configuration mode.
2)Select the “Set Parameters” menu and press ,then you can come to enter
password interface,the default password is “07623”.
3)Under the parameter browsing interface,press to shift up the parameters,
press to shift down the parameters, press to get into parameter changing
page.
4)Under the parameter modification interface, Press to add number 1, press
to reduce number 1, press to turn the digit into right and done.
5)Under the parameter modification interface, Press to cancer parameter
modification and return to parameter browsing interface.
6)Under the parameter browsing interface,Press to save the parameters and
exit from edition page.
Revert back to default: input password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can not be saved if the user didn’t press STOP to confirm the
setting.
Parameter list.
1) Basic setting
No
Parameter
Range (default)
Notes
0
Language
English
简体中文
Language option.
1
Gens poles
2/4/6/8(4)
When the flywheel teeth is set as 0,the RPM
will be resulted by frequency.
Pole 2: 50Hz---3000RPM.Pole 4: 50Hz---
1500RPM.
Pole 6: 50Hz---1000RPM.Pole 8: 50Hz---
750RPM
2
Gens AC system
Disable
1 phase 2 wire
2 phase 3 wire
3 phase 3 wire
3 phase 4 wire
Gens phases:
No gens parameters can be displayed if setting
as disable, which is applied to water pump
genset.
1P1W: Power*1. 2P3W: Power*2.

DC30D GENSET CONTROLLER USER MANUAL
19
3P3W: Power*2. 3P4W: Power*3.
3
CT rate
5-6000A/5A
(500A/5A)
Used for setting genset CT primary current,
secondary rated current 5A.
4
Rated frequency
40.0-80.0Hz(50.0Hz)
Calculate the alarm value.
5
Rated voltage
80-360V(230V)
Calculate the alarm value.
6
Rated current
5-6000A(500A)
Calculate the alarm value.
7
Rated battery
voltage
8.0-36.0V(24.0V)
Calculate the alarm value. One battery gens
should be set as 12V, two batteries gens
should be set as 24V.
8
Rated RPM
500-4500RPM(1500)
Calculate the alarm value.
9
Flywheel teeth
0-300(0)
If the setting is 0, (RPM sensor Disabled), then
RPM is resulted by Hz.
10
Pressure/Temper
ature unit
℃/KPA
℃
/BAR
℃/PSI
F/KPA
F/BAR
F/PSI
Unit dissplay.
11
Power on Mode
STOP
Auto
Auto save
The mode of Controller after Power-on.
Note: Auto save function can not record the
mode with manual.
12
Manual crank
times
1-30 (1 time)
Crank times under mode and test mode.
13
Auto start crank
times
1-30 (3 times)
Crank times under auto mode.
14
E.T.S. hold times
1-10(2 times)
The max E.T.S. hold on power shall be
canceled once stop success under auto mode .
the output interval time is " Fail to stop ".
15
Crank disconnet
RPM
Hz
Oil pressure(delay)
RPM/Frequency
RPM/Oil Pressure
Frequency/Oil
Pressure
RPM/Frequency/Oil
press.
1.If there is no oil pressure sensor, please
don’t choose it.
2.Oil pressure switch input is not the crank
condition
3.Please check if the running status, stop
condition are according with crank condition.
4.Means either of the conditions can be
acceptable as crank condition. But all of them
should be meet together to regard as stop
condition.
16
Frequency
disconnect
0-200%(28%)
Rated frequency multiplying by this value is
regarded as crank success condition. When
the gens frequency is over the condition value,
then system regards it as crank success.
17
Oil pressure
disconnect
0-400kpa(200kpa)
When the engine oil pressure is over the
condition value, then system regards it as
crank success, motor escaped.