mercor MCRP 054 Operator's manual

Gdańsk, ver. 1.7 - 2007.04.26 10:37:00
Weather Monitoring Unit -
MCRP 054
Technical and Operating Documentation
User Instruction Manual
MERCOR SA
Ul. Grzegorza z Sanoka 2
80-408 Gdańsk
tel. (+48) 058 341 42 45, fax (+48) 058 341 39 85

Page 2 of 12
Table of Contents
1. USER INFORMATION ................................................................... 2
2. INTRUDUCTION............................................................................ 3
3. ABOUT THE MCRP054 WEATHER MONITORING UNIT ............ 4
3. OPERATION.................................................................................. 6
4. WARRANTY TERMS AND CONDITIONS..................................... 7
5. SERVICE........................................................................................ 7
6. ASSEMBLY AND START UP........................................................ 8
7. TECHNICAL SPECIFICATIONS.................................................... 8
1. User information
Thank you for selecting the MCR 9705 weather monitoring unit.
Please, read these instructions carefully and follow the guidelines.
This will ensure smooth and reliable operation of the device.
MERCOR SA reserves the right to modify the product or the
documentation without notice.
We wish to ensure your full satisfaction with our products and we
will be glad to provide professional service and assistance to you, if
necessary.
MERCOR SA
Please keep this Instruction Manual, so that the information
is always available when required.

Page 3 of 12
2. Intruduction
1. The MCRP 054 weather monitoring unit is used to control the
operation of actuators in the MCR-PROLIGHT and MCR PROLIGHT+
vents or in ventilation windows which should be closed in wind or rain.
2. To the weather monitoring unit smoke exhaust control units,
ventilation control units or electromechanical actuators powered by
230 V or 24 V voltage.
3. The closing signal is generated on the basis of readings from a WM1
wind sensor and the RS1/RS2 rain sensor.
4. Output: the device has four switches which are activated in the event
of wind/rain or when mains voltage is lost. The switch remains
activated for a pre-set time after the rain/wind has ceased.
5. The value of rain intensity which activates the alarm can be adjusted
by the user (drizzle – heavy rain).
6. The value of wind force which activates the alarm can be adjusted by
the user - from a gentle breeze (about 5 m/s) to a gale (about 15 m/s).
7. Additional input for a vent position sensor (the circuit is closed when
the vents are open) makes it possible to optically control the vent
status.
8. The device is equipped with the optical signals to indicate the
following status:
•230V~ power supply green LED
•“Wind” alarm red LED
•“Rain” alarm red LED
•“Vent open” signal amber LED
9. The device is equipped with the wind speed indicator – a line indicator
consisting of 7 amber LEDs and one red LED (for wind speeds over
15 m/s).
10. Wall-mounted plastic housing, H x W X D: 180 x 180 x 75 mm;
protection class IP54, colour: light grey (~RAL 7035), leads outlets
either on top or at the rear of the housing.
11. It is possible to connect the weather monitoring unit to a remote
control module which contains optical indicators and potentiometers
for setting the desired sensitivity of the wind/rain sensors.

Page 4 of 12
3. About the MCRP054 weather monitoring unit
Fig. 1 Monitoring unit’s front panel.
On the front panel, there are LEDs which indicate the status of the
control center:
#
Description Color Function
1
POWER SUPPLY green indicates presence of power
supply
2
WIND red wind alarm
3
RAIN red rain alarm
4
VENT OPEN amber indicates that smoke vents
(windows) are open
5
WIND SPEED 7 x amber
1 x red wind speed – LED line
indicator; scale from about
0 m/s to about 15 m/s
The interior of the weather monitoring unit is shown in Fig. 2.
At the bottom left section of the unit’s PCB, there are two
potentiometers (1,2).
Potentiometer 1 is used to set the sensitivity of the rain sensor:
from a drizzle (far left) to a heavy rain (far right).
Potentiometer 2 is used to set the sensitivity of the wind sensor:
from 5 m/s (far left) to 15 m/s (far right).
Above the potentiometers there are two jumpers: H2 (3) and H3
(4). They are used to switch the weather monitoring unit into the remote
control mode:
remote control mode
local control mode (factory settings)

Page 5 of 12
Fig. 2. View of the unit’s interior.
At the left edge of the board, there’s a set of time coding jumpers
H1 (5) used to code the desired time during which the alarm will remain
on after the cause of the alarm (i.e. wind or rain) has ceased:
Minimum alarm duration
4 minutes
6 minutes
8 minutes
10 minutes
Along the top edge of the module's PCB there are terminal strips
(6) which are used to connect the elements of the system:
Description Function
P1 … P4 input for remote control module
P5 input for vent opening sensor
P6 … P7 input for wind/rain sensor
P9 output 1 from the unit (switch)
P10 output 2 from the unit (switch)
P11 output 3 from the unit (switch)
P12 output 4 from the unit (switch)
P13 auxiliary output 230 V, 50 Hz, max 5 A
P14 power supply input 230 V, 50 Hz
On the board there is an circuit breaker FS1 (7) - 125 mA quick.
PW1 contact (8) is used to connect the indicator board mounted in
the unit’s cover.
2
1
3
4
5
6
7
8

Page 6 of 12
3. Operation
3.1. Normal operation
Description of optical LED indicators on the front panel (fig. 1):
POWER SUPPLY
WIND
RAIN
VENT OPEN
UNIT STATUS
+ +
VENT OPEN
+ +
ALARM - WIND
+ +
ALARM - RAIN
+ - -
NO ALARM
- - -
NO POWER SUPPLY
MCRP 054 is a maintenance-free device. It requires uninterrupted
230 V mains power supply. Should there be power outage caused by
mains failure, the unit will generate the vent closing signal on output
terminals.
3.2. Alarm
The wind/rain sensor will automatically close smoke vents (or
prevent the vents from being opened by using the ventilation
pushbutton) if the wind or atmospheric precipitation is too strong/heavy.
When the weather monitoring unit is in the alarm mode, the red
LED will light up on its door, and the alarm signal will be generated on
output terminals.
In the alarm mode, the NO contact is open and NC contact is
closed with the COM contact.
The alarm will switch off automatically when the factor which
released the alarm ceases, after a period of time set by adjusting the
H1 (5) jumpers.
ANY STATUS
+ON
-OFF

Page 7 of 12
4. Warranty terms and conditions.
1. MERCOR SA gives twelve-month warranty for the purchased equipment, unless the "delivery
contract" or "delivery and assembly contract" stipulates otherwise.
2. If during the warranty period any fault resulting from a latent defect in equipment occurs,
MERCOR SA undertakes to eliminate the fault within 21 days from the notification date. In the
case of a fault resulting from incorrect operation of equipment or from other reasons not being on
the part of MERCOR SA, the buyer shall bear the costs of eliminating the fault.
3. MERCOR SA reserves the right to extend the repair time in the case of complicated repairs or
repairs which require a purchase of non-standard subassemblies [elements] or spare parts.
4. In accordance with generally accepted practice, the warranty does not cover:
•equipment damage and failure caused by incorrect operation, or lack of maintenance, or lack of
periodical inspections.
•equipment damage due to reasons other than those being on the part of MERCOR SA and, in
particular, events of a fortuitous nature in the form of torrential rainstorm, flood, hurricane,
•inundation, lightning, overvoltage in electrical system, explosion, hail, aircraft fall, fire,
avalanche, landslide and consequential damage resulting from the above mentioned reasons.
A torrential rainstorm shall mean rainfall of intensity factor not lower than 4. The hurricane shall
mean a wind of a speed of at least 17.5 m/s.
•damage arising from omission of the duty to report promptly any noticed defect.
•deterioration in the quality of coating caused by a process of natural decay (fading out,
oxidisation).
•defects caused by application of abrasive or aggressive cleaning agents.
•parts which normally wear out during operation (for example gaskets), unless a manufacturing
defect did occur in them.
5. Any defect covered by the warranty should be reported to MERCOR SA immediately.
6. The buyer is obligated to operate and maintain the purchased equipment correctly, to carry out
periodical service inspections (at least twice a year) and to enter each service inspection in the
"construction facility book"..
7. The warranty expires with immediate effect:
1. if the buyer or user make structural modifications on their own without prior agreement
with MERCOR SA;
2. if the maintenance or periodical service inspection was not performed within specified
time limits or was performed by a service unit not authorized by MERCOR SA, or the
equipment was operated incorrectly;
3. in the case of any interference by unauthorized persons, excluding the activities within the
scope of normal operation of equipment.
As regards matters not regulated by these "Warranty terms and conditions", relevant regulations in
the Civil Code, and in particular Art. 577-581 shall apply.
5. Service.
1. Periodical service inspections of the equipment should be carried out during the whole service
life of the equipment.
•every 6 months if the equipment represents a component of a smoke exhaust system
•every 12 months if the equipment represents a stand-alone control system for daily
ventilation, not connected to a smoke exhaust system
2. The service inspections should be carried out by a firm properly authorized by Mercor SA.
3. For service-related issues, please contact the Service Department, phone no. +48 58 341 4245
ext. 127 or fax: +48 58 341 3985, 8 am – 4 pm (Monday-Friday).

Page 8 of 12
6. Assembly and start up
Connection diagrams are show on pages 9 … 12.
1. Wind/rain sensor - 4 leads (YTKSY or YDY) from P6 … P8
terminals.
2. Vent opening sensor - 2 leads from P5 terminals. The contact is
closed when the vents are open (optional feature).
3. Remote control module - 8 leads from P1… P4 terminals (optional
feature).
4. Power supply 230 V, 50 Hz should be connected to the P14 terminal
strip. The power supply line for the unit should be protected by
means of a properly marked overload circuit breaker in the switching
station. The recommended circuit breaker: max. 6.3 A.
5. Start-up. Before switching on the power supply, check if the leads
are connected properly.
Note: the leads should be placed and connected in accordance with
relevant standards and basic rules for wiring. In order to connect the unit
you should use leads which satisfy the requirements of current
regulations.
7. Technical specifications.
Item Value
Power supply voltage 230 V
%10%15
+
−
50 Hz
Rated power 10 VA
Load for relay outputs max. 5 A, 230 V~
Number of control groups
(number of output terminals) 4
Load on auxiliary output terminal (P13) max. 5 A
Working temperature range -5ºC ÷ +50ºC
Climatic grade in accordance with
WBO/11/11/CNBOP/2002 I
Protection level for housing IP 54
Dimensions (H x W x D) 300 x 300 x 150 mm
Compatible sensors RS1-WM1 and RS2-WM1

Page 9 of 12
7. Wiring diagrams
Drawing 1. Connection for the MCRP 054 weather monitoring unit with a RS2-WM1 sensor .
output 1:
MCR9705/MCR0204
wind/rain
230 V, 50 Hz
power suppy
output 230 V, 50 Hz
max 5 A
vent open sensor
remote control module
(option)
wind sensor WM
heating of the rain sensor
rain sensor
ground
wind sensor WM
heating of the rain sensor
rain sensor
ground
connection to
RS1-WM1 wind/rain
sensor unit
connection to
RS2-WM1 wind/rain
sensor unit
MCRP054
MCRP054
output 2
output 3
output 4

Page 10 of 12
Drawing 2. Diagram for connection of 230 V~ ventilation actuators to the MCRP 054 weather monitoring unit.
N
L
P13
C
C
C
C
P9
P10
P11
P12
Terminal strip in MCRP054
Drivers in
the group 1
230 V AC output
terminal in MCRP054
or direct connection to
the network
NC
NC
NC
NC
NO
NO
NO
NO
Drivers in
the group 2
.
Drivers in
the group 3
.
Drivers in
the group 4
4.
Ventilation
pushbutton
D. U
w.
U
w.
D.
N
Ventilation
pushbutton
D.
U
.
U
w.
D.
Ventilation
pushbutton
D. U
w.
U
w.
D.
Ventilation
pushbutton
D
U
w.
U
w.
D.

Page 11 of 12
Drawing 3. Diagram for connection of pneumatic ventilation boxes (LUK) with the EA/EZ (230 V~) option to the MCRP 054 weather monitoring unit.
230 V AC output terminal
in MCRP054 or direct
connection to the network
Terminal strip in MCRP054
Electromagnets in
the group 1
Electromagnets in
the group 2
Electromagnets in
the group 3
.
Electromagnets in
the group 4
N
L
P13
CC
C
C
P9
P10
P11
P12
NC
NC
NC
NC
NO
NO
NO
NO
D
.
U
D
.
U
D
.
U
D
.
U
D
.
U
D
.
U
D
.
U
D
.
U
Ventilation
pushbutton
Ventilation
pushbutton
Ventilation
pushbutton
Ventilation
pushbutton

Page 12 of 12
Drawing 4. Diagram for connection of pneumatic ventilation boxes (LUK) with the EZ (230 V~) option to the MCRP 054 weather monitoring unit.
NLP13
230 V AC output terminal
in MCRP054 or direct
connection to the network
Terminal strip in MCRP054
P9
C
NO
NC
Electromagnets in
the group 1
Electromagnets in
the group 2
Electromagnets in
the group 3
Electromagnets in
the group 4
Table of contents