Metro Therm SHK 200S User manual

Installation and
operating manual
SHK 200S
SHK 200S-6
Indoor unit Cooperating with
air heat pumps
EKSPERTER I VARME OG VARMT VAND
30147


3List of contents |SHK 200S
SHK 200S-6
List of contents
1 Important information _____________ 4
Information regarding safety __________________________4
2 Supply and operation______________ 6
Transport _________________________________________6
Assembly_________________________________________6
Included items _____________________________________6
Removal of the covers_______________________________6
3 Indoor module structure _________ 7
SHK 200S / SHK 200S-6_____________________________7
4 Pipe connections____________________ 9
General pipe connections ____________________________9
Pipe connections __________________________________12
Other information__________________________________12
Connection options ________________________________13
Connection options ________________________________17
DHW circulation___________________________________18
5 Outdoor unit METROAIR L _____19
Transport and storage ______________________________19
Assembly________________________________________19
Lift from the street to the set up location ________________19
Lift from the pallet to nal positioning __________________20
Scrapping _______________________________________20
Condensation run off _______________________________20
Recommended alternative for leading off condensation water20
Dimensions ______________________________________22
Installation area ___________________________________24
Sound pressure levels______________________________24
6 Electrical connections ___________25
General information________________________________25
Connections______________________________________26
Settings _________________________________________27
7 Start-up and regulation __________28
Preparations _____________________________________28
Filling and venting _________________________________28
Circulation pump __________________________________29
Start____________________________________________29
Start guide _______________________________________29
8 Control - Introduction____________ 31
Display unit ______________________________________31
Menu system _____________________________________32
9 Control _________________________________34
Menu 1 - INDOOR CLIMATE_________________________34
Menu 2 - HOT WATER _____________________________35
Menu 3 - INFO____________________________________35
Menu 4 - MY SYSTEM _____________________________36
Menu 5 - SERVICE ________________________________37
Start guide _______________________________________38
Settings for the user _______________________________40
Cooling settings___________________________________49
Submenu SERVICE _______________________________49
10 Service _______________________________56
Service actions ___________________________________56
11 Disturbances in comfort _______60
Troubleshooting___________________________________60
Additional heating only _____________________________61
12 Accessories ________________________62
13 Technical data _____________________63
Dimensions and layout of connections _________________63
Technical data ____________________________________64
Performance _____________________________________65
Energy labelling___________________________________66
Data for energy efciency of the package _______________66
Energy labelling___________________________________67
Diagram of electrical connections _____________________70

4SHK 200S
SHK 200S-6
1 Important information
Information regarding
safety
Serial number
Symbols
Marking
SHK 200S / SHK 200S-6 features
the CE mark and water protection
IP21.
The CE mark con rms that METRO-
THERM has taken care for product
conformity with applicable regulations
of relevant EU Directives. The CE is
required for most products sold in the
EU, regardless of their place of man-
ufacture.
IP21 means that items with the di-
ameter greater or equal to 12.5 mm
cannot access inside causing dam-
age, and that the product has been
secured against vertically falling wa-
ter drops.
The device can be operated by chil-
dred aged over 8 and persons with
physical, sensoric, or mental disa-
bilities, and without any experience
or knowledge about its operation, if
supervised or trained in safe opera-
tion, and if they understand the risks
related to its operation. The device
must not serve as a toy for children.
Activities related to cleaning and ba-
sic maintenance must not be per-
formed by unsupervised children.
Rights to implement design changes
are reserved.
©METROTHERM 2020
This manual contains installation
and maintenance procedures for
specialists.
The serial number is located at the
bottom of the rating plate, on the
top cover SHK 200S / SHK 200S-
6 and consists of 14 digits.
IMPORTANT
This symbol informs about the
risk to the device or a person
CAUTION
This symbol points to im-
portant information to be
noted when operating the
device easier.
ADVICE
This symbol shall mean
tips to make product oper-
ation easier.
Serial
number
(PF3)
Chapter 1 | Important information

5SHK 200S
SHK 200S-6
Waste disposal
Disposal of the packaging
shall be the responsibility
of the installation techni-
cian installing the product,
or a special waste man-
agement facility.
Description Notes Signature Date
Heating medium
Installation rinsing
Installation venting
Diaphragm expansion vessel
Particulate lter
Safety valve
Cut-off valves
Pressure in the heating system
Connection according to the drawing
Hot water
Cut-off valves
Mixing valve
Safety valve
Power supply
Communication connection
Circuit fuses
Fuses, internal module
Building fuses
Temperature sensor outdoor
Room sensor
Energy meter
Emergency switch
Switch differential
Thermostat emergency mode setting
Miscellaneous
Connected to
Installation acceptance
The heating system must be accepted before start-up. Acceptance must be done by a person with appropriate
qualications. Complete the card in the operating manual by entering the installation data.
CHECKLIST
Chapter 1 | Important information
Do not dispose of decommissioned
products together with regular
household wastes. Hand them over
to a specialist facility dealing with
waste disposal or salesperson of-
fering such services.
Incorrect disposal of the product by
the user is subject to administrative
penalties under applicable regula-
tions.

6SHK 200S
SHK 200S-6
2 Supply and operation
Transport Included items
Assembly
SHK 200S / SHK 200S-6 heat pump must be transport-
ed and stored vertically in a dry place. SHK 200S / SHK
200S-6 can be, however, carefully placed on the rear side
of the casing when carrying the device into the building.
Leave 800 mm free space at the front of the heat
pump. All maintenance works on SHK 200S / SHK
200S-6 can be done from the front.
The side covers and rear wall of the housing are per-
manently attached, therefore it is not possible to dis-
mantle them.
• SHK 200S / SHK 200S-6 must be set on a solid
waterproof base that would keep the weight of the
indoor unit. The regulated legs of the heat pump
allow for levelling and stable setting of the device.
• Because SHK 200S / SHK 200S-6 is equipped
with condensate drain, indoor unit installation site
must be furnished with a oor drain with a dis-
charge to the sewer system.
1. Remove screws at the bottom edge of the front cover.
2. Open the cover at the lower edge, taking care to
not damage the connecting cables, and then re-
move the front cover by lifting it up.
3. Disconnect the cable connecting the front cover
to the unit.
Installation site
Removal of the covers
3
Chapter 2 | Supply and operation
20-40 mm
Wrench size 13
IMPORTANT
When using an additional heat source, leave behind
the device the space necessary for non trouble free
connections and subsequent maintenance.
25-30 mm
800 mm
IMPORTANT
The opening pressure of the safety valve is 3 bar.
Safety group with safety
valve (3 bar), pressure
gauge and automatic air
vent (1 pc.)
Temperature sensor
Outdoor / indoor
(2 pcs)
Connection p.27
• Safety group (1 pc.)
• Outdoor / indoor temperature sensor (1 pc.)
• Instalation and user manual

7SHK 200S
SHK 200S-6
3 Indoor module structure
Chapter 3 | Indoor module structure
SHK 200S / SHK 200S-6
XL11 XL10 XL4 XL13 XL14 XL3
AA27
AA8
AA2:X4AA2:X15
AA2
K2
XL2
XL1
BT6
BT7
X0
BT30
X1
FD1
EB1
FA2
FA1
K1A-K3A
AA23
AA3
X2
AA7
EB2
SF1
GP12BT64
EP2QN12
BT12CM1
BP4EB1
BT15BT63
BT3
BT71
XL5 BT25
QN10

8SHK 200S
SHK 200S-6
LEGEND
Pipe connections
XL1 Connection, heating medium, supply
XL2 Connection, heating medium, return
XL3 Connection, cold water
XL4 Connection, hot water
XL5 Connection, hot water circulation
XL10 Connection, cooling
XL11 Connection, safety group,manometer
XL13 Connection, liquid cooling medium
XL14 Connection, gas cooling medium
HVAC elements
CM1 Diaphragm expansion vessel, closed
QN10 Isolation valve, domestic hot water / cen-
tral heating
QN12 Isolation valve, cooling/heating
GP12 Circulation pump
EP2 Heat exchanger
Czujniki
BP4 Pressure sensor, high pressure
BT3 Temperature sensor, heating medium re-
turn
BT6 Temperature sensor, hot water loading
BT7 Temperature sensor, top of the hot water
heater
BT12 Temperature sensor, condenser outlet
BT15 Temperature sensor, liquid
BT25 Temperature sensor, heating medium
supply
BT63 Temperature sensor, heating medium sup-
ply downstream the submersible heater
BT64 Temperature sensor, cooling medium
supply
BT71 Temperature sensor, heating medium re-
turn
Electrical elements
X0 High voltage terminal block 400V~/230V~
X1 Low voltage terminal block 230V~
X2 Low voltage terminal block 230V~
AA2:X4 Low voltage terminal block
AA2: X15 Low voltage terminal block
K1A-K3A Submersible heater switch
K2 Alarm relay
BT30 Thermostat - emergency mode
AA2 Main card
AA3 Sensor card
AA23 Communication card
AA7 Relay card
AA8 Titanium anode card
AA27 Relay card
FD1 Temperature limiter
FA1 Circuit breaker (to internal module)
FA2 Circuit breaker (AMS outdoor unit)
EB1 Submersible heater
Other
EB15 SHK 200S / SHK 200S-6
SF1 Controller switch
PF3 Serial number
EB2 Domestic hot water tank
Chapter 3 | Indoor module structure

9SHK 200S
SHK 200S-6
4 Pipe connections
General pipe connections
Pipe installation must be carried out in accordance
with current norms and directives.
The pipe dimension should not be less than the recom-
mended pipe diameter according to the table below.
However, each system must be dimensioned individu-
ally to achieve the recommended system ows.
The system can cooperate with a low- and medium
temperature heating system. Recommended temper-
ature of the heating medium at minimum designed
outdoor temperature DOT must not exceed 55°C on
supply, and 45 °C on return circuit from the heating
system, whereas HK 200S / HK 200S-6 can achieve
even 65 °C when using a ow-through heating mod-
ule or another peak heat source.
Excess medium owing out of the safety valve must
be discharged via a pipe to a oor drain. The over-
ow pipe must be slanted at the entire length from the
safety valve, and must be secured against freezing.
In order to achieve maximum system efciency, we
recommend the installation of HK 200S / HK 200S-6
as close to the heat pump as possible.
The HK 200S / HK 200S-6 module is not equipped with
cut-off valves, which must be installed outside the in-
door module to make future maintenance easier.
The HK 200S / HK 200S-6 module can be connected
to the central heating, cooling, and domestic hot wa-
ter installation. Install the supplied safety valve and
the manometer.
Air/water
heat pump
Minimum
ow during
defrosting
(100%
pump
speed (l/s)
Minimum
recom-
mended
pipe
dimension
(DN)
Minimum
recom-
mended
pipe
dimension
(mm)
SHK 200S-6 / L6 0,19 20 22
SHK 200S / L8 0,19 20 22
SHK 200S /
L12 0,29 20 22
IMPORTANT
Any high points in the climate system, must be
equipped with air vents.
IMPORTANT
The pipe systems need to be ushed out before
the indoor module is connected so that
any debris cannot damage component parts.
IMPORTANT
As long as heating circuits in the system have not been
lled with the heating medium, do not set the switch
(SF1) in the controller in position “I” or “ ”. The com-
pressor in the heat pump and the ow-through heating
module can be damaged.
MINIMUM SYSTEM FLOWS
The installation must be dimensioned at least to man-
age the minimum defrosting ow at 100% pump op-
eration, see table.
IMPORTANT
All connections require free ow, hence a discharge
valve must be installed.
IMPORTANT
An undersized system can result in damage to the
machine and lead to malfunctions.
Chapter 4 | Pipe connections
SHK 200S / SHK 200S-6
is equipped with a pres-
sure expansion vessel of
10 litres. The pre-pres-
sure of the pressure ex-
pansion vessel must be
dimensioned according to
the maximum height (H)
between the vessel and
the highest positioned
radiator, see gure. A
pre-pressure of 0.5 bar (5
mvp) means a maximum
permitted height differ-
Expansion vessel
Volume expansion
Minimum volume of the heating system
CAUTION
The diaphragm expansion vessel at the domestic hot
water installation is not required. It is, however, required
to install a safety valve with opening pressure of 3 bar.
ence of 5 m. The maximum system volume excluding
the boiler is 220 litres at the above pre-pressure.
Approx. 10 l/kW is required for connection to the heat
pump, and many heating systems do not have this
volume. To prevent operational problems, the volume
is then expanded using a UKV buffer vessel.
H
METROAIR L 6 8 12
Minimum volume of the heating system
during heating / cooling 50l 80l 100l
IMPORTANT
In order to achieve undisturbed ow of the heating sys-
tem, use a hydraulic coupling or open heating loops.
Remember to always keep the minimum required ow
in the installation - see the section "Minimal ow in the
installation".

10 SHK 200S
SHK 200S-6
The SHK 200S / SHK 200S-6 indoor unit is equipped
with a coil water heater, diaphragm expansion vessel,
safety group, electric heating module (heater), isola-
tion valves, plate heat exchanger, metering instru-
ments, and an electronic circulation pump. Together
with the outdoor unit of air heat pump METROTHERM
L SPLIT), forms a complete heating system.
The METROAIR L outdoor unit provides heat for heat-
ing the domestic hot water and supplying the heating
system while using free energy in the outdoor air, ef-
Installation diagram ciently operating within the range of low temperatures
up to -20°C.
The connection of the outdoor unit and indoor unit
SHK 200S / SHK 200S-6, with a system of pipes
lled with a cooling medium secures the connection
against freezing in the event of any power outages.
The control of system operation is the function of con-
troller module.
Symbol Description
Cut-off valve
Non-return valve
Three-way valve
Safety valve
Temperature sensor
Diaphragm expansion
vessel
Manometer
Vent
Circulation pump
Electric module
Symbol Description
Particulate lter
Compressor
Heat exchanger
Cooling
Central heating
systems
Domestic hot water
Relief valve
Additional heat source
Basic connection diagram
Chapter 4 | Pipe connections
P
SHK 200S
SHK 200S-6
XL10
XL1
XL2
-EB101
-BT1
HS1-BP4
-BT15
-BT3
-GP12
-BT64 -BT25
-QN12
-BT63
-BT71
-QN10
-BT7
-BT6
P

11SHK 200S
SHK 200S-6
Indoor SHK 200S / SHK 200S-6 module
• It is recommended that the SHK 200S / SHK
200S-6 module should be installed in a room with
a oor drain, at best in a utility room or a boiler
house.
• The oor must be solid, concrete at best.
• The SHK 200S / SHK 200S-6 module must be set
with its back to the outer wall, at best in a room
where noise is not a problem. If possible, do not
place the device near a wall of a bedroom or an-
other room where noise might be a problem.
• The device can be leveled using regulated legs.
• Pipes must be led in such a way that they are not
adjacent to the bedroom or living room.
• Remember to leave about 800 mm free space at
the front and 220 mm over the device to provide
for future maintenance.
1. Connect SHK 200S / SHK 200S-6 module to the
heating system, cold, and hot water pipelines.
2. Install the cooling medium pipes.
3. Connect the outdoor temperature sensor, and
cables between SHK 200S / SHK 200S-6 and
METROAIR L.
4. Connect power supply to module SHK 200S /
SHK 200S-6.
5. Proceed according to start-up instructions in
chapter Start-up and regulation.
Recommended order of assembly
P
SHK 200S
SHK 200S-6
XL10
XL18XL19
XL1
XL2
-EB101
-BT1
HS1 -BP4
-BT15
-BT3
-GP12
-BT64
-BT25
-QN12 -BT63
-BT71
-QN10
-BT7
-BT6
P
Scheme with the connection of an additional heat source
Chapter 4 | Pipe connections

12 SHK 200S
SHK 200S-6
Pipe connections
Pipe connections
XL1 Connection, Heating medium supply
Ø22 mm
XL2 Connection, Heating medium return
Ø22 mm
XL3 Connection, cold water Ø22 mm
XL4 Connection, hot water Ø22 mm
XL5 Connection, circulation Ø15 mm
XL10 Connection, cooling Ø22 mm
XL11 Connection, safety group
Ø22 mm, manometer
XL13 Liquid cooling medium
Connection ¼” (SHK 200S-6)
Connection ⅜” (SHK 200S)
XL14 Gas cooling medium
Connection ½” (SHK 200S-6)
Connection ⅝” (SHK 200S)
XL 18 Connection, return to an additional heat source
Ø22 mm
XL 19 Connection, supply from additional heat
source Ø22 mm
Other information
PF3 Serial number plate
Chapter 4 | Pipe connections
20-40
1589 115
XL11
XL10
XL4 XL5 XL3 XL2 XL1
XL14
XL13
PF3
600.5
610.5
300
156
93.5 92.5 87 63 55
65
155
44
152
XL11
XL18
XL10
XL19
XL4 XL13 XL14 XL3
XL2
XL1
103mm

13SHK 200S
SHK 200S-6
Chapter 4 | Pipe connections
Connection options
Compatible heat pumps air/water by
METROTHERM with unit SHK 200S /
SHK 200S-6
Connecting the heating system
Indoor SHK 200S units can cooperate with external
units of Split type. Compatible heat pumps METRO-
THERM SPLIT include:
An external heat source, eg a gas or oil boiler, can
be connected to the back of the SHK 200S / SHK
200S-6, removing the access block to the connection
sockets (picture below). Scheme on page 11.
The SHK 200S / SHK 200S-6 pmodule is equipped with
a condensate hose in the heat exchanger section. The
hose drains all condensate away from the device to
minimize the risk of damage. If necessary, the hose can
be extended.
Conden-
sate hose
Supply from
additional heat
source (XL 19)
Return to an
additional heat
source (XL 18)
Pipe connections of the heating system are to be
made at the top.
• All the required protections and cut-off valves
must be installed as close to the SHK 200S / SHK
200S-6 module as possible.
• Where necessary, install the vents.
• Safety valve with a nanometer at the central heat-
ing circuit and the safety valve at the hot water
system must be installed on relevant conductors
XL 11 and XL 4. In order to prevent air sockets,
the overow pipe must be slanted at the entire
length from the safety valve, and must be se-
cured against freezing.
• When connecting to the installation where all
heaters have been equipped with thermostat
valves, install a discharge valve or remove sever-
al thermostats to assure appropriate ow.
Symbol Application
L6 SHK 200S-6
L8 SHK 200S
L12
IMPORTANT
The term “heating system”, as used in this installation
and operation manual, shall mean the heating or cool-
ing system supplied with a hot or cold medium from
the SHK 200S / SHK 200S-6 module for heating or
cooling purposes.
Connection of the external heat source
Condensate elimination
More information about METROTHERM SPLIT to be
found at
www.METROTHERM.dk and in relevant installation
manuals for accessories used.
Chapter Accessories can serve to check the list of ac-
cessories to be used with SHK 200S / SHK 200S-6.
CAUTION
Suitable safety valve must be installed directly on the
cold water supply line to the hot water tank. Safety
valve will protect against excessive increase of pres-
sure.
Refrigerant pipes must be installed between the external
module METROAIR L and SHK 200S / SHK 200S-6 .
The installation must be executed according to the
applicable standards and directives.
Limitations
• Maximum pipe length, L6, L8, L12 is L=30 m.
• Maximum height difference (H): ±7 m.
Connecting refrigerant pipes
(not supplied)
CAUTION
The outdoor unit, factory-lled with refrigerant, enables
the use of refrigerant pipes (dimension L) between the
outdoor unit and the indoor unit measured with a length
of L = 15m. The maximum permissible length of the re-
frigerant pipes can be 30m, but this requires topping up
the installation with a refrigerant.
L
H
L
H
HK 200S
HK 200S
AMS 10
AMS 10
SHK 200S
SHK 200S

14 SHK 200S
SHK 200S-6
Pipe dimensions and materials
SHK 200S Gas pipe Liquid pipe
Pipe replacement Ø15,88 mm (5/8”) Ø9,52 mm (3/8”)
Connection Connection – (5/8") Connection – (3/8”)
Material Quality of copper SS-EN 12735-1 or
C1220T, JIS H3300
Minimum ma-
terial thickness 1,0 mm 0,8 mm
External diam-
eter, copper
pipe (mm)
B, using
R410A (mm)
B, using a
conventional
tool (mm)
Ø 9,52
0,0~0,5
0,7~1,3
Ø 15,88
Ø 6,35 1,0~1,5
Ø 12,7
External
diameter,
copper
pipe (mm)
Torque
(Nm)
Tightening
angle
(°)
Recom-
mended
tool length
(mm)
Ø6,35 14~18 45~60 100
Ø 9,52 34~42 30~45 200
Ø12,7 49~61 30~45 250
Ø 15,88 68~82 15~20 300
Pipe connection
• Execute the pipe installation with the mainte-
nance valves (QM35, QM36) closed.
METROAIR L6 / METROAIR L8
• Remove the side panel on METROAIR L during
the installation to make access easier.
Socket connections
Extension:
Shift:
METROAIR L12
• Remove the “to be removed” part from the exter-
nal panel at the METROAIR L mode where pipes
are to be led. The drawing below presents exem-
plary pipe outlets.
• Make sure that no water or dirt can permeate to the
pipes. Contamination of the pipes may damage
the heat pump.
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
IMPORTANT
When soldering, apply the shielding gas.
External diameter,
copper pipe A (mm)
Ø 6,35 9,1
Ø 9,52 13,2
Ø 12,7 16,6
Ø 15,88 19,7
SHK 200S
SHK 200S-6
• Bend pipes with maximum bending radius (at
least R100~R150). Do not bend pipes many
times. Use a bending machine.
• Connect the socket connection and tighten with
appropriate torque. Apply the appropriate tight-
ening angle if the torque wrench is not available.
SHK 200S-6 Gas pipe Liquid pipe
Pipe replace-
ment Ø12,7 mm (1/2”) Ø6,35 mm (1/4”)
Connection Connection – (1/2") Connection – (1/4”)
Material Quality of copper SS-EN 12735-1 or
C1220T, JIS H3300
Minimum ma-
terial thickness 1,0 mm 0,8 mm
Front
Elements to be removed
Chapter 4 | Pipe connections

15SHK 200S
SHK 200S-6
Pressure test and leakage test
Vacuum pump Insulation of cooling medium pipes
Filling the system with a cooling medium
A
B
Vacuum
pump
Serviceventil, gas
Mätuttag
Manometer
Serviceventil, vätska
Zawór serwisowy,
ciecz
Zawór serwisowy,
gaz
Wyjście pomiarowe
Manometr
Pompa
próżniowa
Both SHK 200S / SHK 200S-6 and METROAIR L are
factory-tested for pressure and leakage, but pipe con-
nections between the devices must be checked when
the installation has been completed.
When executing pipe connections, pressure tests,
leakage tests and vacuum tests, maintenance valves
(QM35, QM36) must be closed. To ll the pipes and
SHK 200S-6 / SHK 200S with a refrigerant medium
maintenance valves should be opened again.
Connections:
Principle:
• Cooling medium (both gas and liquid) pipes must
be insulated to provide thermal insulation and
prevent condensation.
• Apply insulation that can sustain at least 120°C.
Use a vacuum pump to remove all air. Turn on ex-
traction for at least one hour. Final pressure, after
emptying, must total 1 mbar (100 Pa, 0.75 Tr or 750
microns) of absolute pressure. If the system is still
moist or is leaking, negative pressure will grow after
the end of emptying.
IMPORTANT
Pipe connections between devices must undergo a
pressure test and leakage test after completing the in-
stallation process, according to applicable regulations.
Use nitrogen only for system compression and rinsing.
ADVICE
In order to achieve a better nal effect and to acceler-
ate emptying, follow the following sections.
• Pipelines should have the largest diameter possi-
ble, and be as short as possible.
• Empty the system to 4 mbar and ll it with dry ni-
trogen to atmospheric pressure to end emptying.
IMPORTANT
In the case of systems with cooling medium pipes with
the length of up to 15 m, the supplied volume of the
cooling medium is sufcient.
Wires for connecting indoor
and outdoor units Exterior tape
Gas piping
Insulation
Liquid piping
Okablowanie
Rura z cieczą
Taśma
Rura gazowa
Izolacja
Przyłącza:
Band (accessory) Pipe cover (accessory)
Zworka Zabezpieczenie rury
Wires for connecting indoor
and outdoor units Exterior tape
Gas piping
Insulation
Liquid piping
Okablowanie
Rura z cieczą
Taśma
Rura gazowa
Izolacja
Przyłącza:
Band (accessory) Pipe cover (accessory)
Zworka Zabezpieczenie rury
Chapter 4 | Pipe connections
Measurement output
Maintenance
valve - liquid
Maintenance
valve - gas
Manometer
Vacuum
pump
Cabling Tape
Gas pipe
Insulation
Pipe for liquid
Jumper Pipe protection
CAUTION
All connections and work related to the refrigeration
system must be made by a person with appropriate
authorizations and certicates.
METROAIR L is supplied together with a cooling me-
dium for cooling medium of max. length of 15 m. If the
length of the cooling medium pipes exceeds 15 m,
supplement the cooling medium in the volume of 0.06
kg/m for SHK 200S and 0,02 kg/m for SHK 200S-6.
CAUTION
The maximum permissible length of the refrigerant pipes
can be 30m, but this requires topping up the installation
with a refrigerant after exceeding 15m.

16 SHK 200S
SHK 200S-6
Connections
METROTHERM SPLIT can be connected in many
various ways.
More information on connections to be found at web-
site www.METROTHERM.dk.
L6 L8 L12
Max pressure, climate system 0,3 MPa (3 Bar)
Highest recommended supply/return temperature at dimensioned
outdoor temperature 55/45 °C
Max temperature in SHK 200S / SHK 200S-6 +65 °C
Max ow line temperature with compressor +58 °C
Min supply temperature cooling +7 °C
Max supply temp. cooling +25 °C
Min volume, climate system during heating, cooling* 50 l 80 l 100 l
Min volume, climate system during under oor cooling* 80 l 100 l
Max ow, climate system 0,38 l/s 0,57 l/s
Min ow, climate system, 100% circulation pump speed
(defrosting ow) 0,19 l/s 0,29 l/s
Min ow, heating system 0,12 l/s 0,15 l/s
Min ow, cooling system 0,16 l/s 0,20 l/s
*-Regards circulating volume
Chapter 4 | Pipe connections

17SHK 200S
SHK 200S-6
Connection to the heat pump
Connection when operating without a
heat pump
Connection of hot and cold water
SHK 200S / SHK 200S-6 is not equipped with cut-off
valves, which must be installed outside the indoor mod-
ule to make future maintenance easier.
When connecting to the installation where all heaters/
oor heating pipes have been equipped with thermo-
stat valves, in order to assure appropriate ow, install
a discharge valve or a buffer in the parallel layout, or
remove several thermostats.
No change is required to the hydraulic connections
conguration for the internal unit to operate individu-
ally, without an external unit.
The installation of the mixing valve is necessary
if factory settings are changed in a way where the
temperature can exceed 60 °C. When changing the
factory settings, follow the national regulations in this
respect. The setting is entered in menu 5.1.1.
Heating system connection
The system can be extended with additional heating cir-
cuits only when provided an additional expansion card
After using an AXC30 card or a ECS 41 kit, an additional
heating circuit can be activated in the controller.
Cooling system connection
Cooling is controlled by sensor BT64 and isolation
valve QN12. If cooling is needed, the isolation valve
changes the direction, and opens from the cooling
circuit side.
Connecting an additional heating circuit
Connection options
P
P
Additional accessories and options and how to connect
them are described in the AXC30 or ECS41 manual.
Chapter 4 | Pipe connections
P
P
IMPORTANT
Water supply uti lity must have necessarily installed
safety valve which will protect against excessive in-
crease of pressure.
IMPORTANT
Do not use the heater if there is a blockage of the safe-
ty valve.
P
P
P
P
P
P
IMPORTANT
Installation of any narrowing (e.g. reducers, lters etc.)
and shut-off valves between the heater and the safety
valve is not allowed. It is only permitted mounting three-
way adapter with drain valve that allows to empty the
tank and three-way adapter with expansion vessel.

18 SHK 200S
SHK 200S-6
IMPORTANT
In order to connect the DHW circulation pump control, an
additional accessory AXC 30 is required.
XL5
XL5
DHW circulation
The SHK 200S / SHK 200S-6 have possibility to
connect DHW circulation. The circulation connection
(XL5) is located at the top of the tank.
To connect the circulation:
1. Remove the XL5 plug from the top of the housing.
520
120
Dimensions of the
pipe for circulation
Elbow 15x15
2. Remove the front panel, then move the control
box to the right to gain access, to the hydraulic
connections.
3. Remove the plug from the circulation pipe (XL5).
4. Install the elbow, facing the rear housing, on the
circulation pipe.
5. Connect the pipe to the elbow, with the dimen-
sions shown in the gure below, leading pipe in
the top of the housing, in place of the XL5 plug.
6. At the output of the pipe from the SHK 200S / SHK
200S-6 unit, install the circulating pump, and then
connect its control to the expansion card.
7. Install the control box and the front panel.
Connection of the DHW circulation pump control
The DHW circulation pump should be connected to
the AA5 (NOT INCLUDED IN SHK 200S / SHK 200S-
6) expansion card on the AA5-X9:8 (230V), AA5-X9:7
(N) and X1: PE
1
0 PE 2
L
N
PE
3
2
3
4
5
6
7
8
9
Expansion Card External
GP11
X1
AA5-X9
Chapter 4 | Pipe connections

19SHK 200S
SHK 200S-6
5 Outdoor unit METROAIR L
Transport and storage
Assembly
Lift from the street to the set up
location
METROAIR L must be transported and stored vertically.
Do not place METROAIR L directly on the lawn or
other non solid surface.
If there is a risk of snow slip from roof, a protective
roof or cover must be erected to protect the heat
pump,pipes and wiring.
If the base allows, the simplest thing is to use a pallet
truck to move the METROAIR L to the set up location.
If METROAIR L needs to be transported across soft
ground,such as a lawn, we recommend that a crane
truck is used that can lift the unit to the installation lo-
cation. When METROAIR L is lifted with a crane, the
packaging must be undamaged and the load distrib-
uted with a boom,see the illustration above.
If a crane cannot be used METROAIR L can be trans-
ported using an extended sack truck. METROAIR L
must be used on the side marked "heavy side" and
two people are required to get the METROAIR L up.
• Place METROAIR L outdoors on a solid level
base that can take the weight, preferably a con-
crete foundation. If concrete slabs are used they
must rest on asphalt or shingle.
• The concrete foundation or slabs must be posi-
tioned so that the lower edge of the evaporator
is at the level of the average local snow depth;
however, a minimum of 300 mm. Stands and at-
tachments on the page are available in the MET-
ROAIR L instruction in the "Accessories" chapter.
• METROAIR L should not be positioned next to
noise sensitive walls, for example, next to a bed-
room.
• Also ensure that the placement does not incon-
venience the neighbours.
• METROAIR L must not be placed so that recircu-
lation of the outdoor air can occur. This causes
lower output and impaired efciency.
• The evaporator should be sheltered from direct
wind, which negatively affects the defrosting
function. Place METROAIR L protected from
wind against the evaporator
• Large amounts of condensation water, as well
as melt water from defrosting, can be produced.
Condensation water must be led off to a drain or
similar (see page13).
• Care must be exercised so that the heat pump is
not scratched during installation.
IMPORTANT
Ensure that the heat pump cannot fall overduring trans-
port.
IMPORTANT
The centre of gravity is offset to one side (seep print on
the packaging).
LEK
XX mm
300 mm
Chapter 5 | Outdoor unit METROAIR L

20 SHK 200S
SHK 200S-6
Lift from the pallet to nal posi-
tioning
Scrapping
Drain doors
Recommended alternative for
leading off condensation water
Condensation run off
Condensation runs out on to the ground below MET-
ROAIR L. To avoid damage to the house and heat
pump, the condensation must be gathered and
drained away. The condensation water is lead to an indoor drain
(subject to local rules and regulations).
Route the pipe downward from the air/water heat
pump.
The condensation water pipe must have a water seal
to prevent air circulation in the pipe.
• The condensation water (up to 50 litres / 24 hrs)
must be routed away by a pipe to an appropriate
drain, it is recommended that the shortest outdoor
length possible is used.
• The section of the pipe that can be affected by
frost must be heated by the heating cable to pre-
vent freezing.
• Route the pipe downward from METROAIR L.
• The outlet of the condensation water pipe must
be at a depth that is frost free or alternatively in-
doors (with reservation for local ordinances and
regulations).
• Use a water trap for installations where air circu-
lation may occur in the condensation water pipe.
• The insulation must be tight against the bottom of
the condensation water trough.
When scrapping, the product is removed in reverse
order. Lift by the bottom panel instead of a pallet!
Before lifting remove the packaging and the securing
strap to the pallet.
Place lifting straps around each machine foot. Lifting
from the pallet to the base requires four persons, one
for each lifting strap.
It is not permitted to lift anything other than the ma-
chine feet.
IMPORTANT
It is important to the heat pump function that condensa-
tion water is led away and that the drain for the conden-
sation water run off is not positioned so that it can cause
damage to the house.
IMPORTANT
Self regulating heating cables must not b econnected.
IMPORTANT
The electrical installation and wiring must be carried out
under the supervision of an authorised electrician.
Water seal
Joint
LEK
Frostfritt
Frost proof
depth
Joint
Water seal
Frost
proof
depth
Chapter 5 | Outdoor unit METROAIR L
This manual suits for next models
1
Table of contents
Other Metro Therm Heat Pump manuals
Popular Heat Pump manuals by other brands

WarmPool
WarmPool DC35 Installation & user guide

auer
auer HRC 70 PILOT-PREMIUM Installation and operating instructions

ICP
ICP CHS180 Installation, Start-Up and Service Instructions

Energie
Energie Aquapura 12 Installation and instruction manual

General
General WATERSTAGE WOHA060KLT Installation

Dimplex
Dimplex LA MI Setup guide