Metso LCP9H Series Operating and maintenance manual

Local Control Panels for VG9000H
LCP9H Series
Installation, Maintenance and
Operating Instructions
NOTE: Special version for Liwa-project
7 LCP9H 70 en Liwa • 5/2018

27 LCP9H 70 en Liwa
READ THESE INSTRUCTIONS FIRST!
These instructions provide information about safe handling and operation of the device.
If you require additional assistance, please contact the manufacturer or manufacturer's representative.
Addresses and phone numbers are printed on the back cover.
SAVE THESE INSTRUCTIONS!
Subject to change without notice.
All trademarks are property of their respective owners.
Table of Contents
1 LCP9H Local Control Panels for VG9000H .........3
1.1 General .....................................................................3
1.2 Technical description ..........................................3
1.3 System architecture .............................................3
1.4 Markings ..................................................................4
1.5 Technical specifications .....................................4
1.6 Recycling and disposal .......................................6
1.7 Safety precautions ...............................................6
2 TRANSPORTATION, RECEPTION AND
STORAGE ..............................................................6
3 MOUNTING ..........................................................7
3.1 Electrical connections .........................................7
4 LCP9H LAYOUT AND FUNCTIONALITY ..............7
4.1 Functionality ..........................................................8
5 MAINTENANCE .................................................... 9
5.1 LED test ....................................................................9
6 TROUBLE SHOOTING ...........................................9
7 TOOLS ...................................................................9
8 SPARE PARTS....................................................... 9
9 DIMENSIONS ......................................................10
10 EC DECLARATION OF CONFORMITY ................11
11 TYPE CODING .....................................................12

7 LCP9H 70 en Liwa 3
1 LCP9H Local Control Panels for
VG9000H
1.1 General
The Local Control Panels LCP9H-series are designed to be
used together with the VG9000H intelligent safety solenoid.
Later on in this manual LCP9H name is used when all device
versions are in question. LCP9HL name is used when loop
powered versions are in question.
Different versions of LCP9H are following:
LCP9H, LCP9HW
Externally powered with ATEX and IECEx Ex i and Ex e
approvals
Use with VG9000H_L2
LCP9HL, LCP9HWL
Loop powered with ATEX and IECEx Ex i and Ex e
approvals
Use with VG9000H_L3
LCP9HE, LCP9HEW
Externally powered with ATEX and IECEx Ex d and tb
approvals
Use with VG9000H_L2
LCP9HEL, LCP9HEWL
Loop powered with ATEX and IECEx Ex d and tb
approvals
Use with VG9000H_L3
See the details of different types of LCP9H in the type cod-
ing at the end of this document.
This manual only describes the Local Control Panel wiring,
configurations and functions. See the VG9000H manual
(7VG92H70en) for detailed information, functionality and
wiring connections and options for the VG9000H.
1.2 Technical description
LCP9H permits the emergency isolation valve to be closed
(or opened) locally (close/open functionality, see 4.1.1 for
details). LCP9H permits the valve to be returned to the nor-
mal operating position when the trip initiators are normal
(manual reset functionality, see 4.1.2 for details). There is
also the option for functional testing (PST) of the emer-
gency isolation valve (test functionality, see 4.1.3 for
details).
Trip-functionality is removed in the W versions of the
LCP9H.
See the details of different types of LCP9H in the type cod-
ing at the end of this document.
LCP9H has also indicators (LEDs) for the valve position
(open/close), ready to reset, testing and alarm status (see
4.1.4-7 for LED details).
All the buttons are lockable with e.g. padlock (max. shackle
dia. 5 mm).
1.3 System architecture
The Local Control Panel LCP9H is connected to the
VG9000H with a dual pair cable. Communication between
the devices is handled by a current loop. The LCP9H needs
also a supply power. For the loop powered LCP9H versions
(LCP9H_L) the supply power is taken from the input loop for
the VG9000H, which needs to be 8 mA or more. For the
other LCP9H versions the power supply is external 24 VDC.
Refer to the general wiring of the LCP9H versions in Fig. 1 &
2. See detailed wiring information in Section 3.2.
If the LCP9H is used in intrinsically safe installations, an iso-
lator will be needed for the 24 V DC power supply, see Sec-
tion 1.5 for compatible isolators.
Fig. 1 General wiring of LCP9H / VG9000H_L2
Air supply
1. ValvGuard VG9000H_L2
2. Pneumatic actuator
3. Local Control Panel LCP9H
AO (mA)
from safety system (or from RCI9H)
24 V DC supply
(via isolator if required)
Serial
communication

47 LCP9H 70 en Liwa
1.4 Markings
The Local Control Panel is equipped with an identification
plate (Fig. 2 or 3).
1.5 Technical specifications
VG9000H compatibility
LCP9H 24 VDC powered versions are compatible with
VG9_H_L2_ versions. LCP9H loop powered versions
(LCP9H_L) are compatible with VG9_H_L3_ versions.
See the LCP9H type coding for further details of different
LCP9H versions.
See the VG9000H type coding for further details of different
VG9000H versions.
Temperature range
-20° to 85 °C (Ex ia, ic)
-20° to 65 °C (Ex d, e)
Electronics
Electrical connection: max. 2.5 mm2
LCP9H 2 pcs. conduit entry, dia. 21 mm, cable
glands for cable with with ext. dia. 8-
12 mm included
LCP9HE 2 pcs. conduit entry, M20x1.5
Power consumption: 400 mW
Power supply: Externally powered versions; 11–
24 V DC, 50 mA. Short circuit
protected. Maximum distance
1200 m
Loop powered versions: power taken from VG9000H input
signal, minimum 8 mA.
Interface values for externally powered versions:
Ex ia IIC T4/T5/T6 Gb
Input values for the power supply:
Ui ≤25.2 V
Ii ≤150 mA
Pi ≤650 mW
Ci ≤30 nF
Li ≤252 µH
Output values for the communication interface:
Uo ≤9.8 V
Io ≤47 mA
Po ≤120 mW
Co ≤3.3 µF
Lo ≤15 mH
Fig. 2 General wiring of LCP9H_L / VG9000H_L3
Fig. 3 Example of identification plate, LCP9H
Fig. 4 Example of identification plate, LCP9HE

7 LCP9H 70 en Liwa 5
Ex ic IIC T4/T5/T6
Input values for the power supply:
Ui ≤25.2 V
Ii ≤150 mA
Pi ≤650 mW
Ci ≤25 nF
Li ≤201 µH
Output values for the communication interface:
Uo ≤8.8 V
Io ≤42 mA
Po ≤93 mW
Co ≤45 µF
Lo ≤45 mH
Interface values for externally and loop powered versions:
Ex eb mb [ib] IIC T6...T4
Maximum input value for the power supply:
U = 24 V
The Intrinsically Safe parameters of the current loop
communication interface are:
Uo = 9,8 V
Io = 47 mA
Po = 120 mW
Co = 3,3 F
Lo = 15 mH
Ex d IIB+H2 T6 Gb
Ex tb IIIC T85 °C Db
Input values for the power supply:
Ui ≤25.2 V DC
Ii ≤50 mA
Pi ≤1.26 W
Output values for the communication interface:
Uo ≤8.8 V DC
Io ≤42 mA
Po ≤0.37 W
Interface values for loop powered versions:
Ex ia IIC T6...T4 Gb
Input values for the power supply:
Ui ≤ 28 V
Ii ≤ 120 mA
Pi ≤ 1 W
Li ≤ 313 H
Ci ≤ 33 nF
Output values for the communication interface:
Tx: Uo ≤ 8.3 V
Io ≤ 5.8 mA
Po ≤ 12 mW
Lo ≤ 50 mH
Co ≤ 3.6 F
Rx: Uo ≤ 8.3 V
Io ≤ 12.7 mA
Po ≤ 26 mW
Lo ≤ 50 mH
Co ≤ 3.6 F
Ex ic IIC T6...T4 Gc
Input values for the power supply:
Ui ≤ 28 V
Ii ≤ 120 mA
Pi ≤ 1 W
Li ≤ 313 H
Ci ≤ 27.5 nF
Output values for the communication interface:
Tx: Uo ≤ 8.3 V
Io ≤ 5.8 mA
Po ≤ 12 mW
Lo ≤ 50 mH
Co ≤ 3.6 F
Rx: Uo ≤ 6.5 V
Io ≤ 1.8 mA
Po ≤ 3 mW
Lo ≤ 50 mH
Co ≤ 152 F
ATEX and IECEx approvals are valid under these conditions.
Compatible isolators for the power supply (not loop pow-
ered models)
MTL 5021
P&F KFD0-SD2-Ex1.1045
STAHL 9176/.0-14-0
ABB V17132-520
Communication cable
The communication cable between LCP9H and VG9000H
must be a shielded, twisted pair, 4-wire cable. The shield
must be connected to housings in both ends. The maxi-
mum recommended distance between VG9000H and
LCP9H is 60 m.
Cable requirements:
Signals and corresponding ground
wires twisted
Wire thickness min. 0.8 mm
Shield coverage > 85 %
Test voltage > 1500 V
Ex requirement)
Resistance < 50 Ω/km
Capacitance < 50 pF/m
Material and weight
LCP9H 316L stainless steel, 2.8 kg
LCP9HE Copper-free aluminium alloy with
epoxy coating, 14.6 kg
Dimensions
LCP9H
With buttons and cable glands (approx.):
270 mm x 200 mm x 137 mm
(h x w x d)
LCP9HE
With buttons: 364 mm x 317 mm x 252 mm
(h x w x d)

67 LCP9H 70 en Liwa
APPROVALS
Intrinsically safe
IECEx Ex ia IIC T6...T4 Gb
Ex ic IIC T6...T4 Gc
Ex eb mb [ib] IIC T6...T4 Gb
IEC 60079-0: 2011
IEC 60079-11: 2011
IEC 60079-18: 2014
IEC 60079-7: 2015
ATEX II 2G Ex ia IIC T6...T4 Gb
II 3G Ex ic IIC T6...T4 Gc
II 2G Ex eb mb [ib] IIC T6...T4 Gb
EN 60079-0: 2012,
EN 60079-7: 2015,
EN 60079-11: 2012,
EN 60079-18: 2015
INMETRO
Ex ia IIC T6...T4 Gb
Ex ic IIC T6...T4 Gc
ABNT NBR IEC 60079-0:2013
ABNT NBR IEC 60079-11:2009
Flameproof and explosion proof
IECEx Ex d IIB+H2T6 Gb
Ex tb IIIC T85 °C Db IP66
IEC 60079-0: 2007,
IEC 60079-1: 2007,
IEC 60079-31: 2008
ATEX II 2GD
Ex d IIB + H2 T6 Gb
Ex tb IIIC T85°C Db IP66
EN 60079-0: 2009-10,
EN 60079-1: 2007-04,
EN 60079-31: 2009
INMETRO
Ex d IIB+H2 T6 Gb
Ex tb IIIC T85 °C Db IP65
ABNT NBR IEC 60079-0:2008 versão
corrigida 2011
ABNT NBR IEC 60079-1:2009 versão
corrigida 2011
ABNT NBR IEC 60079-31:2011
ABNT NBR IEC 60529:2009
Electromagnetic protection
Electromagnetic compatibility
Emission acc. to EN 61000-6-4: 2007
Immunity acc. to EN 61000-6-2: 2005
1.6 Recycling and disposal
Most local control panel parts can be recycled if sorted
according to material. Most parts have material marking. In
addition, separate recycling and disposal instructions are
available from the manufacturer.
The Local Control Panel may also be returned to the manufac-
turer for recycling and disposal. There will be a charge for this.
1.7 Safety precautions
2 TRANSPORTATION, RECEPTION AND
STORAGE
The Local Control Panel is a sophisticated instrument, han-
dle it with care.
Check the Local Control Panel for any damage that
may have occurred during transportation.
Store the Local Control Panel preferably indoors and
keep it away from rain and dust.
CAUTION:
Do not exceed the permitted values!
Exceeding the permitted values may cause damage to
the local control panel and to equipment attached to
the panel.
Damage to the equipment and personal injury may
result.
CAUTION:
During maintenance or commissioning when the
device cover is open, ensure that water does not go
inside the enclosure.
CAUTION:
Do not operate the device with the cover open or
removed!
Electromagnetic immunity is reduced.
Ex d WARNING:
Do not open the cover when an explosive atmosphere
may be present!
Ex d and Ex tb WARNING:
Use a cable gland with suitable Ex d IIC and Ex tb IIIC
certification. Use cable gland suitable for at least
-20 °C to 70 °C.
Ex d NOTE:
Only persons familiar with Ex d explosion protection are
allowed to work with the device. Special attention has to
be paid to careful handling and closing of the cover.
NOTE:
Avoid earthing a welding machine in close proximity to
the LCP9H.
Damage to the equipment may result.

7 LCP9H 70 en Liwa 7
3 MOUNTING
3.1 Electrical connections
There are two terminal blocks located in the circuit board
inside the LCP9H (see Fig. 4). LOOP terminals are for connec-
tion to the VG9000H and PWR terminals are for the 24 V DC
power supply or for the loop power.
NOTE: The VG9000H version to be used with LCP9H prod-
ucts needs to have type code option L2. The VG9000H ver-
sion to be used with LCP9H_L products needs to have type
code option L3.
In VG9000H the LCP connection terminals are located in the
upper housing.
See the VG9000H manual 7VG9H70EN for detailed electrical
connections in the VG9000H.
4 LCP9H LAYOUT AND FUNCTIONALITY
The LCP9H front panel layouts with push buttons and LEDs
can be seen in Fig. 5–8.
The push buttons (described in the Section 4.1) are as follows:
Open
PST
Close (not available in W version)
The LEDs (described in the Section 4.1) are as follows:
Ready-To-Open(amber)
PST (amber)
Open (green)
Closed (red)
FAULT (white)
NOTE:
The tightening torque for the cover screws of LCP9HE_
versions is 16 Nm.
NOTE:
The enclosure of the LCP9H meets the IP66 protection
class according to EN 60529 in any position when the
cable entries are plugged according to IP66.
Based on good mounting practice, the recommended
mounting position is with electrical connections placed
downwards. If these requirements are not met, and the
cable glands are leaking and the leakage is damaging the
LCP9H electronics, our warranty is not valid.
Fig. 5 LCP9H_ electrical connections
Fig. 6 LCP9H_L electrical connections
VG9000H_L2LCP9H_
LOOP_CHGND
LOOP_B-
LOOP_B+
LOOP_A-
LOOP_A+
PWR_IN_CHGND
PWR_IN-
PWR_IN+
24 V DC
supply
ground
ground
NOTE:
When installing the LCP9H, standard IEC 60079-14/12.2.4
should be considered. The circuits of the apparatus are
assumed to be earthed.
Fig. 7 LCP9H and LCP9HL front panel
Fig. 8 LCP9HW and LCP9HWL front panel
OPEN
PST
READY TO OPEN
CLOSE
FAULT
PST
CLOSED
OPEN
OPEN
PST
READY TO OPEN
FAULT
PST
CLOSED
OPEN

87 LCP9H 70 en Liwa
4.1 Functionality
The functionality of the LCP9H push buttons and purpose
of the LEDs are described below in 4.1.1-7.
Functionality of the LCP9H is lost in the following cases:
If the supply power (external 24 VDC or loop pow-
ered from VG) is disconnected.
If there is no communication between the LCP9H
and the VG9000H, e.g. the cable is broken or discon-
nected.
If the polarity of wires is incorrect.
If the Loop A (7, 8) and Loop B (9, 10) wires are mixed
in the VG9000H.
These above-mentioned cases do not affect the valve posi-
tion. Alarm LED is blinking in those cases.
The buttons need to be pushed (0.2–10 seconds) and
released to perform the desired function.
4.1.1 Close button
This functionality is only available in LCP9H and
LCP9HE. LCP9HW and LCP9HEW do not have the
valve closing functionality.
The purpose of the Close button is to manually close
or open the valve depending on the assembly and
configuration of the valve. It means that this will
drive the valve to safety position.
4.1.2 Open button
The purpose of the Open push button is to return
the valve to the normal operating position after the
emergency trip.
The Open button is operational only when the mA
signal from the safety system to VG9000H is in 12.0-
15.0 mA.
The Ready-to-Open LED is lit when mA signal from
the safety system is 12.0 - 15.0 mA. The Open button
is then operational.
Push and release the Reset button to return the valve
to the normal operating position.
4.1.3 PST button
The purpose of the PST button is to start the partial
stroke test (PST) manually or to cancel the manual
partial stroke test of the emergency isolation valve.
The stroke size of the test can be set via HART (DTM,
EDD) or from the LUI (Local User Interface) of the
VG9000H. See VG9000H manual 7VG970en for details.
The manual test via LCP9H uses the same stroke size
than manual PST programmed into VG9000H itself.
To start the PST test, press and release the PST button
and the PST LED will be illuminated.
To stop the ongoing manual PST test, press and
release the PST button and the manual PST test will be
cancelled. The valve will return to its normal operating
position.
It is also possible to cancel the manual PST test with
this PST button even if the test is started via HART or
LUI.
4.1.4 Ready-To-Open LED
The Ready-To-Open LED is turned on when mA sig-
nal from the safety system to the VG9000H is 12.0-
15.0 mA and the Open button has not yet been
pushed. It indicates that the Open button can be
used.
Fig. 9 LCP9HE and LCP9HEL front panel
Fig. 10 LCP9HEW and LCP9HEWL front panel
NOTE:
When the button is pushed and released, the valve will be
driven to the safety position; i.e. it will close the valve if it is
the emergency shutdown valve and it will open the valve
when it is the emergency blowdown (venting) valve.
NOTE:
When LCP is used with VG9PST version the trip-functiona-
lity needs to be enabled in VG. It is disabled as default.
NOTE:
When the button is pushed and released, the valve will be
driven to the normal operating position; i.e. it will open the
valve if it is the emergency shutdown valve and it will close
the valve when it is the emergency blowdown (venting)
valve.
NOTE:
Make sure to push the Reset button only when it is safe to
return the valve to the normal operating position.
NOTE:
Make sure to push the Ready-To-Open button only when it
is safe to return the valve to the normal operating position.

7 LCP9H 70 en Liwa 9
4.1.5 Open and Closed LEDs
Open and Closed LEDs indicate the valve position
and whether the emergency isolation valve is open
or closed.
If the valve is in the intermediate state both LEDs are
turned off.
The position information is taken from the position
information of the VG9000H safety valve controller
and the triggering limits are user selectable. The limits
can only be seen and changed via HART (DTM, EDD).
4.1.6 PST LED
The function of the PST LED is to indicate when the
PST button is pushed and the PST test with VG9000H
has started. See Section 4.1.3. for the PST button
functionality.
The PST LED will be turned on when the PST button
is pushed and released. It will be on also during the
Test Warning Time. The Test Warning Time is the
VG9000H parameter and can only be seen and
changed via HART (DTM, EDD).
The PST LED will also be turned on during other
tests: pneumatics test, automatic or manual PST and
ETT. See the VG9000H manual for other test details.
The LED will blink few times if the test starting fails.
4.1.7 FAULT LED
The Fault LED indicates the alarm state in the
VG9000H.
If the Fault LED is turned on, it means that the Alarm
status is activated in the VG9000H.
The Fault LED will blink, if the communication
between the LCP9H and the VG9000H is discon-
nected or not functional, or if the External Devices -
parameter "LCP" in the VG9000H DTM (Metso Valve
ManagerTM) is not selected or it is disabled (diS) in
the VG9000H LUI. That parameter can only be
changed via HART or LUI.
5 MAINTENANCE
Under normal service conditions there is no requirement
for regular maintenance.
5.1 LED test
Push the PST button for more than 10 seconds. All the LEDs
will then be turned on and off after one another in the fol-
lowing sequence: open, closed, ready to open, PST, fault.
After the LED test, the LEDs which were turned on prior to
this testing will be turned on.
6 TROUBLE SHOOTING
If the LCP9H does not work, check the following:
Check the LCP parameter in the VG9000H:
The LCP parameter in the VG9000H needs to be ena-
bled. Go to the parameters menu in the VG9000H LUI
and check that LCP is enabled. For details see the
VG9000H IMO.
This can also be checked in Assembly Related view in
the VG9000H DTM. Check that LCP is selected in the
External Devices parameter. For details see the
VG9000H DTM help file.
Wiring:
Check that the wiring between the LCP9H and the
VG9000H is done according to the instructions in
this manual and/or in the VG9000H IMO.
Power supply:
Check that the power supply or the loop power for
the LCP9H is connected according to the instruc-
tions in this manual and it is turned on.
VG9000H:
Check that the VG9000H installation and setup is
done according to the instructions in the VG9000H
IMO.
If starting the PST fails:
Check that there are no alarms/warnings in the
VG9000H. See the VG9000H IMO (7VG9H70en) and/
or DTM help file for details.
The push of the PST button may be too short or too
long. You need to push the PST button for 0.2–10
seconds and then release.
If the reset function does not work:
Check that the mA signal to VG9000H is above
12 mA. See the VG9000H IMO (7VG9H70en) for
details.
Check that supply pressure to the VG9000H is turned
on and in the correct range.
The push of the PST button may be too short or too
long. You need to push the PST button for 0.2–10
seconds and then release.
If the trip function does not work:
Check that the mA signal to VG9_P is 20 mA and the
functionality is enabled in VG. See the VG9000H IMO
(7VG9H70en) for details.
7 TOOLS
Use the provided key for opening and locking the cover in
LCP9H_ versions. No other special tools are required.
Use 8 mm hex key for the cover screws in the LCP9HE_
versions.
8 SPARE PARTS
The following spare parts are available:
printed circuit board
push buttons
button covers
Contact the local Metso Flow Control office for ordering
spare parts.
NOTE:
LCP9H maintenance must only be carried out by Metso
certified service personnel.

10 7 LCP9H 70 en Liwa
9 DIMENSIONS
LCP9H, LCP9HW, LCP9HL, LCP9HWL
LCP9HE, LCP9HEL, LCP9HEW, LCP9HWL
OPEN
PST
READY TO OPEN
CLOSE
FAULT
PST
CLOSED
OPEN
Note: This button is only available in LCP9H or LCP9HL.
LCP9HW or LCP9HWL does not have this button.
Note: This button is only available in LCP9HE and LCP9HEL.
LCP9HEW or LCP9HEWL does not have this button.
Note: The tightening torque for
the cover screws is 16 Nm

7 LCP9H 70 en Liwa 11
10 EC DECLARATION OF CONFORMITY
EC DECLARATION OF CONFORMITY
Manufacturer:
Metso Flow Contro l Oy
01301 Vantaa
Finland
Product: Local Control Panel LCP9H_-series
As the products within our sole responsibility of design and manufacture may be used as parts or components in machinery and are not alone
performing functions as described in Article 6(2) in the Machinery Directive (2006/42/EC), we declare that our product(s) to which this Declaration of
Conformity relates must NOT be put into service until the relevant machinery into which it is to be incorporated has been declared in conformity
with the provisions of the Machinery Directive.
The product above is manufactured in compliance with the applicable European directives and technical specications/standards.
Protection from e.g. static electricity caused by the process or connected equipment must be considered by the user ( EN 60079-14 §6 ).
The product do not possess any residual risk according to hazard analyses made under the applicable directives providing that the procedures
stated by the Installation, Operation and Maintenance manual are followed and the product is used under conditions mentioned in the technical
specications.
Vantaa 16th F ebruary 2017
Ralf Liljestran d, Quality Manage r
Authorized person of the manufa cturer within the Europe an Com munity
Applicable directives:
EMC 2004/108/EC Electrical
ATEX 2014/34/EU
Approved and Ex marked types
ATEX Notied Bodies for EC Type Examination Certicate:
SIRA (Notied body number 0518)
Sira Certication Service
Rake Lane, Eccleston,
Chester, CH4 9JN
England
VTT (Notied body number 0537)
VTT, Expert Services
Otakaari 7B, Espoo
P.O.Box 1000, FI-02044 VTT
Finland
ATEX Notied Body for Quality Assurance:
ISO 9001:2008 Certicate No: 73538-2010-AQ-FIN-FINAS
ATEX 94/9/EC Annex IV Certicate No: DNV-2006-OSL-ATEX-0260Q
Det Norske Veritas AS (Notied body number 0575)
Veritasveien 1
1322 Høvik, Oslo
Norway
Type Product Approval EC Type examination Certicate
Ex i
LCP9H, LCP9HW
ATEX II 2G Ex ia IIC T6...T4 Gb VTT 09 ATEX 047X, Issue 5
EN 60079-0: 2012, EN 60079-11: 2012
ATEX II 3G Ex ic IIC T6...T4 Gc VTT 11 ATEX 048X , Issue 5
EN 60079-0: 2012, EN 60079-11: 2012
LCP9HL, LCP9HWL
ATEX II 2G Ex ia IIC T6...T4 Gb VTT 16 ATEX 057X
EN 60079-0: 2012, EN 60079-11: 2012
ATEX II 3G Ex ic IIC T6...T4 Gc VTT 16 ATEX 058X
EN 60079-0: 2012, EN 60079-11: 2012
Ex m
LCP9H, LCP9HW, ATEX II 2G Ex eb mb [ib] IIC T6...T4 Gb VTT 16 ATEX 043X
LCP9HL, LCP9HWL
EN 60079-0: 2012, EN 60079-7: 2015
EN 60079-11: 2012, EN 60079-18: 2015
Ex d
LCP9HE, LCP9HEW, ATEX 2 IIG Ex d IIB+H2 T6 Gb SIRA 11 ATEX 1170 , Issue 3
LCP9HEL, LCP9HEWL ATEX 2 IID Ex tb IIIC T85°C Db IP66 EN 60079-0: 2009, EN 60079-1: 2007,
Ta -20° to +65 °C EN 60079-31: 2009
EMC LCP9H, LCP9HW (EMC 2004/108/EC) EN 61000-6-2 (2005), NEMKO 135608
EN 61000-6-4 (2007)
LCP9H_L (EMC 2004/108/EC) EN 61000-6-2 (2005), SGS 285215-1
EN 61000-6-4 (2007)

Metso Flow Control Inc.
Europe, Vanha Porvoontie 229, P.O. Box 304, FI-01301 Vantaa, Finland. Tel. +358 20 483 150. Fax +358 20 483 151
North America, 44 Bowditch Drive, P.O. Box 8044, Shrewsbury, M A 01545, USA. Tel. +1 508 852 0200. Fax +1 508 852 8172
South America, Av. Independéncia, 2500-Iporanga, 18087-101, Sorocaba-São Paulo, Brazil. Tel. +55 15 2102 9700. Fax +55 15 2102 9748
Asia Pacic, 238B Thomson Road, #17-01 Novena Square Tower B, Singapore 307685. Tel. +65 6511 1011. Fax +65 6250 0830
China, 11/F, China Youth Plaza, No.19 North Rd of East 3rd Ring Rd, Chaoyang District, Beijing 100020, China. Tel. +86 10 6566 6600. Fax +86 10 6566 2583
Middle East, Roundabout 8, Unit AB-07, P.O. Box 17175, Jebel Ali Freezone, Dubai, United Arab Emirates. Tel. +971 4 883 6974. Fax +971 4 883 6836
www.metso.com/valves
12 7 LCP9H 70 en Liwa
11 TYPE CODING
OPTIONAL DEVICE FOR VG9000H
LCP9H_
Externally powered Local Control Panel (LCP)
Versions for Ex i/e: LCP9H, LCP9HW.
Stainless steel 316L, IP66.
Versions for Ex d: LCP9HE, LCP9HEW.
Anodized aluminum, IP66
All versions include LEDs, Manual Reset and PST buttons.
Trip button removed in W versions. Buttons are lockable in
all versions.
Power consumption 400 mW. Power supply 11-30 V DC,
50 mA
ATEX and IECEx certifications:
LCP9H, LCP9HW:
II 2 G Ex ia IIC T6...T4 Gb
Temperature range: T4; -20° to +85 °C, T5; -20° to +80 °C,
T6; -20° to +65 °C.
II 3 G Ex ic IIC T6...T4 Gc
Temperature range: T4; -20° to +85 °C, T5; -20° to +80 °C,
T6; -20° to +85 °C.
II 2G Ex eb mb [ib] IIC T6...T4 Gb
Temperature range: T4; -20° to +65 °C, T5; < +65 °C,
T6; < +60 °C.
LCP9HE, LCP9HEW:
II 2 GD
Ex d IIB+H2T6 Gb
Ex tb IIIC T85°C Db IP66
Ta -20° to +65 °C.
INMETRO certifications:
LCP9H, LCP9HW:
Ex ia IIC T6...T4 Gb
Tamb: T6; -20 ... +50 °C, T5; -20 ... +65 °C, T4; -20 ... +65 °C
Ex ic IIC T6...T4 Gc
Tamb: T6; -20 ... +60 °C, T5; -20 ... +65 °C, T4; -20 ... +65 °C
LCP9HE, LCP9HEW:
Ex d IIB+H2T6 Gb
Ex tb IIIC T85°C Db IP65
Ta -20° to +65 °C
NOTE: 7. sign "L2" in VG9000H type coding needs to be
selected for additional conduit entries and terminal strip.
NOTE: See manual 7VG9H70en for further VG9000H details.
OPTIONAL DEVICE FOR VG9000H
LCP9H_L
LOOP POWERED Local Control Panel (LCP)
Versions for Ex i/e: LCP9HL, LCP9HWL.
Stainless steel 316L, IP66.
Versions for Ex d: LCP9HEL, LCP9HEWL.
Anodized aluminum, IP66.
All versions include LEDs, Manual Reset and PST buttons.
Trip button removed in W versions. Buttons are lockable in
all versions.
Power taken from VG input signal (min 8mA).
ATEX and IECEx certifications:
LCP9HL, LCP9HWL
II 2 G Ex ia IIC T6...T4 Gb
Temperature range: T4; -20° to +65 °C, T5; -20° to +65 °C,
T6; -20° to +50 °C.
II 3 G Ex ic IIC T6...T4 Gc
Temperature range: T4; -20° to +65 °C, T5; -20° to +65 °C,
T6; -20° to +60 °C.
II 2G Ex eb mb [ib] IIC T6...T4 Gb
Temperature range: T4; -20° to +65 °C, T5; -20° to +63 °C,
T6; -20° to +48 °C.
LCP9EHL, LCP9HEWL:
II 2GD
Ex d IIB+H2 T6 Gb
Ex tb IIIC T85°C Db IP66
Ta -20°C to +65°C
NOTE: 7. sign "L3" needs to be selected in VG9000H type
coding for additional conduit entries and terminal strip.
NOTE: Minimum input signal for VG9000H is 8 mA.
Other manuals for LCP9H Series
3
This manual suits for next models
7
Table of contents
Other Metso Control Panel manuals