EM-0471 Rev.2 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
OUTPUT ISOLATOR MODEL 18KYS
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%,
approx. 30mA with voltage output
approx. 50mA with current output
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
Specifications
Front Cover
(Connection diagram
behind)
■FRONT VIEW (with cover open)
• Without Power Switch
Span Adj.
Zero Adj.
1
78
56
2
34
• With Power Switch
Power Switch
Span Adj.
Zero Adj.
1
78
56
2
34
ON
OFF
INSTALLATION
Use Standard Rack (model: 18KBXx).
18KYS
EM-0471 Rev.2 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram behind the front cover.
■EXTERNAL DIMENSIONS unit: mm (inch)
110 (4.33 )
93 (3.66)
24 (.94)
7 (.28)
78 (3.07)32 (1.26)
8–M3.5
SCREW
7 (.28)
2–M3
SCREW
■CONNECTION DIAGRAM
5
6
1
2
DCS OUTPUT
+
−
INPUT MONITOR
1
2
OUTPUT
+
−
Use either of module or external field terminals.
To External
Field Terminals
(Section A)
Module
Field Terminals
(Section A)
CONNECTOR
Section A. Field Terminals
POWER
■TERMINAL ASSIGNMENTS
12
34
78
56
18KYS
EM-0471 Rev.2 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage supplied to the rack
(model: 18KBXx). For the DC power source, be sure that
the ripple level is within 10% p-p.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Popular Relay manuals by other brands

TECO SG2 Series user manual

TECO

TECO SG2 Series user manual

ABB Relion 615 series Applications manual

ABB

ABB Relion 615 series Applications manual

Chenzhu CZSR8001-3A1B user manual

Chenzhu

Chenzhu CZSR8001-3A1B user manual

Rockwell Automation Guardmaster Allen-Bradley 440R-S35001 Reference manual

Rockwell Automation

Rockwell Automation Guardmaster Allen-Bradley 440R-S35001 Reference manual

Emerson White-Rodgers 829A-832 installation instructions

Emerson

Emerson White-Rodgers 829A-832 installation instructions

Idem SCR-73-i manual

Idem

Idem SCR-73-i manual

LSIS GIPAM 2200 manual

LSIS

LSIS GIPAM 2200 manual

Woodward MFR 12 manual

Woodward

Woodward MFR 12 manual

Sel SEL-787 instruction manual

Sel

Sel SEL-787 instruction manual

Moeller NZM-XDMI 612 installation instructions

Moeller

Moeller NZM-XDMI 612 installation instructions

Leuze MC3 Series Original operating instructions

Leuze

Leuze MC3 Series Original operating instructions

Schweitzer Engineering Laboratories SEL-321-3 instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-321-3 instruction manual

GE 750 instruction manual

GE

GE 750 instruction manual

Siemens SIRIUS 3RB3.3 Series manual

Siemens

Siemens SIRIUS 3RB3.3 Series manual

Contrel ELRC-B user manual

Contrel

Contrel ELRC-B user manual

Theben TR 608 top quick start guide

Theben

Theben TR 608 top quick start guide

frako RM 2106 operating instructions

frako

frako RM 2106 operating instructions

Megacon Iso4-DIN instruction manual

Megacon

Megacon Iso4-DIN instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.