MGE UPS Systems Comet EXtreme Series User guide

Comet EXtreme
4.5/6/9/12 kVA
Start-Up Guide

286-153721-01
Comet EXtreme Transformer Distribution Cabinet
Items included in 9/12 kVA tower configuration:
Items included in 4.5/6 kVA tower configuration:
battery module
electronics module
transformer (optional)
battery module
electronics module
transformer (optional)
battery module
NOTE:
Connection and operation for rack models
and tower models are the same.
1.0 Unpacking
4.5/6 kVA rack model configuration:

86-1537121-01 3
4
3
2.0 Installation of I/O Box
2.1 Install I/O Box. Verify the I/O box 1
is mounted properly to the UPS and
the mounting screws 2 are properly
torqued to 20.7 in. LB.
2.2 Verify the Bypass Rotary Switch, on
the I/O Box, is in the “NORMAL”
position. See Figure 1.
2.3 Remove terminal block cover 3 on
I/O Box.
2.4 Remove cable entry knockouts 4 at
rear of I/O Box.
2.5 Insert cables for input power (left)
and output power (right) thru
knockouts.
*Be sure cables are secured to I/O
box with a strain relief.
Before turning the switch,
see the manual
NORMAL BY-PASS
2
1
Figure 1
(output)
(input)
WARNING! Wiring to be done by qualified electrical personnel. Insure that all
external AC input line circuit breakers are open (off).

486-153721-01
3.0 Input/Output Connections
Always connect the earth ground wire first!
3.1 Connect the three wires of the equipment cable to the “OUTPUT” terminal block.
3.2 Connect the three wires of the power cable to the “INPUT” terminal block.
L1L2 L1L2
INPUT OUTPUT
L1L2 L3
INPUT OUTPUT
120
104
N
104
120
208VAC
FROM UTILITY
TO LOAD
208VAC
I/O BOX
TO LOAD
120VAC/208VAC/240VAC
OR
TO OPTIONAL POWER DISTRIBUTION MODULE (PDM)
- OR -
TO OPTIONAL
6 kVA ISO
TRANSFORMER
4.5/6 KVA CONFIGURATION
TERMINAL BLOCK LAYOUT
NOTE: UPS AND ISOLATION TRANSFORMER
ARE FACTORY CONFIGURED AT 208 VAC
Comet EXtreme Transformer Distribution Cabinet

4.5/6 kVA Schematic
OPTIONAL 240 VAC INPUT CONFIGURATION
4.5/6 kVA Schematic
L1
INPUT OUTPUT
4.5 /6 KVA UPS
L2
L1
L2
240 VAC INPUT
FROM UTILITY
4.5/6 KVA ISO TRANSFORMER
(240 VAC INPUT)
L1
L2
L3 NEUT OUTPUT
104A
104B
120A
120B
GND
208 240 208 VAC 240 VAC
L1
INPUT OUTPUT
4.5 /6 KVA UPS
L2
L1
L2
208 VAC INPUT
FROM UTILITY
4.5/6 KVA ISO TRANSFORMER
(208 VAC INPUT)
L1
L2
L3 NEUT OUTPUT
104A
104B
120A
120B
GND
208 240 208 VAC 240 VAC
86-1537121-01 5
Quick Start Guide

L1L2 L1L2
INPUT OUTPUT
L1 L2
INPUT OUTPUT
X3
N
X5 X6 X7X2X1
9/12 KVA CONFIGURATION
TERMINAL BLOCK LAYOUT
NOTE: UPS AND ISOLATION TRANSFORMER
ARE FACTORY CONFIGURED AT 208VAC
208VAC
FROM UTILITY
I/O BOX
TO LOAD
208VAC
TO LOAD
120VAC/208VAC/240VAC
OR
TO OPTIONAL POWER DISTRIBUTION MODULE (PDM)
- OR -
TO OPTIONAL
12 kVA ISO
TRANSFORMER
686-153721-01
Comet EXtreme Transformer Distribution Cabinet

Optional Transformer for 9/12 Floor mount:
9/12 kVA Schematic
L1
INPUT OUTPUT
9/12 KVA UPS
L2
L1
L2
208 VAC INPUT
FROM UTILITY
(or optional
240 VAC input,
configured with software)
9/12 KVA XFMR SCHEMATIC
(208 VAC) INPUT
H1
H2
OUTPUT AT
208 VAC TRANSFORMER INPUT
(L1)
(X7)
(X6)
(X1)
(X5)
(L2)
104
120
GND
N
104
120
104
120
GND
N
104
120
(X4)
(X3)
(X2)
NOT USED IN 208 VAC APPLICATION
a
a
a
b
b
b
NOT USED IN 240 VAC APPLICATION
OPTIONAL CONFIGURATION:
OUTPUT AT
240 VAC TRANSFORMER INPUT
86-1537121-01 7
Quick Start Guide
input output

L1L2L1L2
INPUT OUTPUT 9/12 KVA DUALTRANSFORMER CONFIGURATION
TERMINAL BLOCK LAYOUT
NOTE: UPS AND ISOLATIONTRANSFORMER
ARE FACTORY CONFIGURED AT208 VAC
L1L2L3
INPUT OUTPUT
120
104
N
104
120
TO LOAD
120VAC/208VAC/240VAC
OR
TO OPTIONAL
POWER DISTRIBUTION MODULE (PMM)
L1L2L3
INPUT OUTPUT
120
104
N
104
120
TO LOAD
120VAC/208VAC/240VAC
OR
TO OPTIONAL
POWER DISTRIBUTION MODULE (PMM
6KVA ISOTRANSFORMER 6KVA ISOTRANSFORMER
208VAC
FROM UTILITY
886-153721-01
Comet EXtreme Transformer Distribution Cabinet

9/12 kVA Dual Transformer Schematic
OPTIONAL 240 VAC INPUT CONFIGURATION
9/12 kVA Dual Transformer Schematic
L1
INPUT OUTPUT
9/12 KVA UPS
L2
L1
L2
240 VAC INPUT
FROM UTILITY
4.5/6 KVA ISO TRANSFORMER
(240 VAC INPUT)
L1
L2
L3 NEUT
104A
104B
120A
120B
GND
208 240
4.5/6 KVA ISO TRANSFORMER
(240 VAC INPUT)
L1
L2
L3 NEUT
104A
104B
120A
120B
GND
208 240
(240 VAC
INPUT)
OUTPUT
OUTPUT
L1
INPUT OUTPUT
9/12 KVA UPS
L2
L1
L2
208 VAC INPUT
FROM UTILITY
4.5/6 KVA ISO TRANSFORMER
(208 VAC INPUT)
L1
L2
L3 NEUT
104A
104B
120A
120B
GND
208 240
4.5/6 KVA ISO TRANSFORMER
(208 VAC INPUT)
L1
L2
L3 NEUT
104A
104B
120A
120B
GND
208 240
(208 VAC
INPUT)
OUTPUT
OUTPUT
86-1537121-01 9
Quick Start Guide

3.3 Make sure wires are secured properly.
3.4 Refit and secure the terminal block cover.
3.5 Battery-module connections
3.5.1 Comet EXtreme 4,5 and 6 kVA
3.5.1.1 Check that the battery circuit breaker is OFF.
3.5.1.2 Connect cable to the connectors of the electronic and battery modules.
Input
Battery CB
Battery Cable Connector
Battery Cable
BATTERY #3 BATTERY #2 BATTERY #1
UPS TRANSFORMER
Output
10 86-153721-01
Comet EXtreme Transformer Distribution Cabinet
output (front feed or bottom feed)
power connection knock-outs
input (front feed or bottom feed)

86-1537121-01 11
Quick Start Guide
3.5.2 Comet EXtreme 9 and 12 kVA
3.5.2.1 Check that the battery circuit breaker(s) is OFF.
3.5.2.2 Connect cable to the connectors of the UPS and battery modules.
Input and output voltage of the UPS must always be the same.
Comet EXtreme products are factory configured at 208VAC, 60Hz input and output.
4.0 Start-up Procedure
This document provides an overview of the initial procedures that should be followed
before any devices are powered by your Comet EXtreme UPS.
Refer to your Comet EXtreme User Guide for safety, installation, and troubleshooting
information.
4.1 Battery Scan Test
This procedure is a test for each battery to verify it is in basic working order. To verify
it holds a charge, batteries should be charged for several hours before testing battery
levels.
The protected equipment connected to the UPS can be energized, whether AC input
power is available or not.
Prior to initial start-up, check the UPS voltage settings. If the protected equipment
voltage is other than 208 V/60 Hz, the UPS settings must be modified using the "UPS
Driver" software. See User Manual for instructions.
4.1.1 Verify that all AC and DC connections, input and output, are secure.
4.1.2 Set the battery circuit breaker(s) to “ON”. The buzzer will sound three times.
Battery CB's
Battery Cable Connectors
Battery Cables
Battery Set #3 Battery Set #2 Battery Set #1
UPS

4.1.3 Turn on external AC power.
4.1.4 Press the ON/OFF button 21 on UPS. After 30 seconds, LED 19 goes on.
All
connected equipment is energized.
If LED 19 does not go ON, or if LEDs 11 ,
12 , 13 or 14 flash, there is a fault (refer to section 4.1 of User Manual).
4.1.5 LEDs 11 to 14 provide three different indications:
◗Remaining backup time in percent (in ON-LINE mode).
◗Percent load drawn by the protected equipment,
when button 15 is pressed.
◗Operating faults (flashing LED and beeps):
11 Overload
12 UPS fault
13 Battery fault
14 Excessive ambient temperature
4.1.6 Allow the battery packs to charge for at least 10 minutes.
4.1.7 Remove power from the Comet EXtreme UPS by setting the
AC main circuit breaker supplying power to the UPS to “OFF.”
4.1.8 Set all battery circuit breakers, EXCEPT one, to the “OFF” position.
4.1.9 Verify that the Output Power ON/OFF switch on the UPS is in the “ON” position.
4.1.10 After approximately 30 seconds, at least one of the four yellow LEDs on the front panel
of the UPS should be lit. Additionally, the Battery Input LED 20 , on the front panel of
the UPS should be lit. This will indicate that the battery pack is operational.
4.1.11 Activate the next battery, if system has more than one battery set, by setting its circuit
breaker to “ON”. Deactivate the battery that was tested previously by setting its circuit
breaker to “OFF”. The battery test LEDs should still be illuminated.
4.1.12 Repeat step 4.1.12 until all batteries have been tested. Any battery that fails to light at
least LED 1 may need to be charged for a minimum of 3 hours. Repeat the scanning
procedure. If the battery pack again fails to light at least LED 1, it should be replaced.
4.1.13 Restore power to the Comet EXtreme UPS by setting the AC mains circuit breaker
supplying power to the UPS to “ON.” And set all battery circuit breakers to the “ON”
position.
12 86-153721-01
Comet EXtreme Transformer Distribution Cabinet
21
20
19
18
15
14
13
12
11

4.2 Power-Up Test
4.2.1 After performing the Battery Scan Procedure above, set all battery circuit breakers to
the “ON” position.
4.2.2 Allow the UPS to charge the batteries for at least 3 hours per battery pack. You may
use the UPS while the batteries charge, but the battery backup runtime will be reduced
until the batteries are fully charged.
4.2.3 Switch on the protected equipment, one load at a time. If the UPS beeps an alarm
when you start your equipment, the UPS may be overloaded.
4.2.4 The four LEDs on the right side of the front of the UPS show the percent of battery
capacity remaining. To verify the percentage of maximum load, depress the “Push for %
of load” button.
Successful completion of the procedures above will verify that the Comet EXtreme
UPS is properly configured and ready for use. Please refer to your user guide for
detailed information on the function of your UPS.
86-1537121-01 Rev A00 01/02 13
Quick Start Guide

www.mgeups.com