
13
BR/BC Series Woodburning Fireplaces
7412944
Firestop spacers are not available for nor are they re-
quired on vertical walls.
put any sealant around the area where the
outer pipe slides through the restop spacer. If you
seal this area,
In Canada, an attic insulation shield is required to
prevent attic insulation from contacting the chimney
section. If the attic insulation shield is used, the
restop is not required in the attic installation. Fram-
ing dimensions for the chimney hole should measure
14Z⁄₂" x 14Z⁄₂" (368 x 368 mm). An attic shield MUST
be installed on top of attic joists (above the oor level).
(Fig. 19)
In the U.S., it is a good idea, although not al-
ways required, to install an attic insulation shield where
blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the anges on its
base extending down into the framing hole. Nail each
corner of attic insulation shield to the framing members
of the ceiling hole using 8d nails. Attic shields are not
required at the roof.
A chimney support is 2Z⁄₂" (64mm) long when installed.
Consider this dimension when determining how many
straight chimney sections are needed.
Chimney supports are generally used in long
runs in a chase installation.
If you encounter additional ceilings, repeat same steps
required for rst ceiling installation. See restop illus-
tration on Page 12, Figure 18.
Run pipe to rooine. Since chimney system must be
vented to the out-of-doors, you use an approved
termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.
Use same procedure detailed in locating center point of
the ue system.
Drive a nail up through roof at the center point. This will
determine center point on outside of the roof.
Size of roof hole varies with the type of chimney
termination installed. Refer to installation instructions
provided with the chimney termination to nd correct
size of roof hole.
There must be a 1Z⁄₂" (38mm) air space between out-
ermost portion of chimney sections and any adjacent
combustible surfaces. (Combustible surfaces include
burnable materials such as: ceiling members, joists,
ooring, combustible insulation and roof structures.)
Mark an outline of the roof hole around the center of the
point nail. Hole dimensions given in the chimney
top installation instructions are dimensions;
therefore, the hole size must be marked on the roof ac-
cordingly.
Cover the opening of the installed chimney so debris
cannot get into the system.
Cut and frame the hole. It is good practice to use fram-
ing lumber that is the same size as the rafters. Install
the frame securely because the chimney top and ash-
ing anchored to the frame must be able to withstand
heavy winds.
FP263
MBUF
5/9/96
Attic
Insulation
Shield
Base
Flanges
Ceiling
Attic Joist
Nails
(4 required)
FP263
Attic shield installlation (Canadian requirement).
Continue attaching pipe sections to complete system
to next level always being careful that the pipe is rmly
snapped locked in place before proceeding to next pipe
section.
If chimney supports are required, they are installed the
same as elbows. Nail chimney support straps to ad-
jacent structural framing, as shown on Figure 9, Page
8. Bend straps as necessary and make sure they are
secure so they will support the weight of the chimney.