
87D0058 5
SB50HB Series Woodburning Fireplace
When an AK4 combustion air assembly and a combustion
air duct are attached to the connecting point on the left or
right side of the replace, combustion air may enter the
rebox through a dampered opening behind the left or
right side brick. This feature is designed for your benet
to reduce the room air used for combustion and to prevent
excessive loss of heat from the room. When the replace
is in use, this damper should be open. When the replace
is not in use, the damper should be closed to prevent cold
air from entering the rebox. The combustion air damper
is open when the lever, located on the left and right side
of the rebox near the top of the rebrick, is up and closed
when the lever is down.
Outside air for combustion is optional unless required by
federal, state or local building codes. See the section of
this manual providing the instructions for installation of
the combustion air assembly. The design of the replace
allows the routing of the combustion air duct up, down,
or horizontally to obtain the outside combustion air. This
permits exibility in planning your installation. Refer to Page
19 for typical installation methods. Review the precautions
and recommendations in this manual pertaining to outside
combustion air installation.
Glass doors should be installed to receive the maximum
benet from your replace. For large res, the maximum
heating benet from the replace will be obtained with the
doors open due to the high amount of radiant heat being
emitted out of the front opening of the replace. With a
small re, or before retiring in the evenings, it is best to
operate the replace with the doors closed to prevent
excessive room air form being drawn up the chimney.
When the doors are open, the mesh screens should be
closed to help keep burning embers from popping out of
the rebox.
The replace also is equipped with a ue damper, which
must be open when the fireplace is in use. The flue
damper control lever is located inside the replace. The
counterweighted damper is operated by simply pushing
up to open or pulling down to close the damper. When
the replace is not in use, the damper should be closed
to prevent cold air form entering the chimney as well as
preventing warm air in the room from escaping up the
chimney.
It is normal for a small amount of smoke to be
released from the upper portion of the replace the rst
few times you use your new replace. This results from an
oil residue on the metal. Open a door or window to allow
the smoke to escape.
The grate included with this replace helps to appropriately
locate and contain the burning wood. Failure to use this
grate may cause overheating of parts of the replace and
allow large pieces of burning wood to roll forward out of the
rebox. If the grate becomes warped or damaged, it must
be replaced with grate number 072954 only.
Fireplaces equipped with doors should be
operated only with the doors fully open or doors fully
closed. If doors are left partly open, gas and ame may be
drawn out of the replace opening, creating risks of both
re and smoke.
All replace chimneys are in direct contact with cold air
on the exterior of the structure. Consequently, when the
replace is not in use, cold air can fall down the chimney of
the replace to cool off the replace chase. Therefore, the
replace chase must be insulated to minimize the risk of
cold air inltration to the home. Even if the replace chase
is adequately insulated, this cannot completely ensure that
cold air inltration into the structure will be eliminated. Cold
air inltration is a possibility with any replace or device
that freely communicates with the air on the outside of
the structure. Today’s homes are more energy-efcient
and, therefore, better insulated and tightly constructed.
Unfortunately, when air is removed from the house, as by
a bathroom fan, or consumed by a furnace, additional air is
needed to replace the air consumed. Unless the additional
air is supplied, this can cause a negative pressure in the
home. When this happens, the house will draw in outside
air form the cracks in the windows, down the replace ue
or other locations of air leakage in the home. Because
cold air inltration may be unavoidable in some structures,
MHSC is not responsible for heat loss or air inltration
through or around the replace.