milleteknik NOVA FLX M User manual

SSF1014 CERTIFIED BATTERY BACKUP WITH COMMUNICATION
NOVA FLX M
NOVA FLX M is available in 12 V - 24 V and can be mounted on a wall or in a 19 "rack.
Name, article number, e-number and certificate number
Name Article number E-number Certified according to Certificate
number
NOVA 24V 5A
FLX M FM01P30024P050-SSF 5213565 Fulfils the requirements in Alarm Class 4
according to SSF 1014, utgåva 5 No20-117
NOVA 24V 10A
FLX M FM01P30024P100-SSF 5213566 Fulfils the requirements in Alarm Class 4
according to SSF 1014, utgåva 5 No20-117
About
is mainly used in safety systems where SSF 1014 approved battery backup is required or where the
requirements are higher. Requirements such as better flexibility, more alarm functions, longer backup
operating times or where the battery backup needs to handle higher loads.
The NOVA series is system certified according to SSF1014 together with most systems on the Swedish
market. Milleteknik has the right to sell two different systems on the Swedish market; Sentrion NOVA
The series has communication via RS485 to Sentrion S4, S4 DUO and CISS. Integra. Together with
MOVEO kit (optional) there is RS232 communication with Integra MOVEO and MOVEO XL.
• SSF1014, Alarm class 1-3 approved battery backups / power supply.
• Controlled charging function.
• Qualified battery capacity test.
• Can be supplemented with several different optional cards.
• Mounted on a wall or in a 19 ”rack.
• Flexible battery capacity with battery boxes increases backup operating time.
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

FLEXIBILITY
NOVA FLX S can have an extra battery box. NOVA FLX M and NOVA FLX L with 1-4 extra battery
boxes *. NOVA FLX M and NOVA FLX L with battery shelves in 19 ”rack *. * The battery boxes and
shelves are connected via a 9-pin connector. The battery box has room for up to 2 pcs. 45 Ah batteries
per battery box. Battery shelves have room for 2 pcs. 45 Ah batteries (Medium) and up to 2 pcs. 150 Ah
batteries (Large) per each battery shelf.
FIXED INSTALLATION
The product is intended for fixed installation. The battery backup must be installed by a qualified
installer.
Area of use
is mostly used for: Access control systems, fire alarms, burglar alarms, (integrated security systems), in
public environments such as schools, offices and commercial properties.
The unit meets the requirements for installation in systems that must be SSF 1014 approved. SSF 1014
certificate is only valid for certification together with a higher-level system.
IMPORTANT
In order for the SSF 1014 certificate to be valid, only one (1) load output may be used.
Installation video
https://www.milleteknik.se/nova-24-v-5-a-10-a-flx-m-in-
stallation-och-driftsattning/
REGULATIONS AND CERTIFICATIONS
Standards that product (s) meet and are approved for
Standards
ONE: EN50131-6
SSF: SSF1014 Alarm class 1-4 (burglary alarm)
SSF1014, Meets alarm class 3
SSF1014, edition 5
2022-10-11
www.milleteknik.se Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

Requirements that the product meets
EMC: EMC Directive 2014 / 30EU
Electricity: Low voltage directive: 2014/35 / EU
EN 60950-1
CE: CE directive according to: 765/2008
Emission: EN61000-6-: 2001 EN55022: 1998: -A1: 2000, A2: 2003 Klass B, EN61000-3-2: 2001
Immunity: EN61000-6-2: 2005, EN61000-4-2, -3, 4, -5, -6, -11
SS-EN 50 130-4: 2011 Edition 2, EN50131-6
Environment REACH Regulation: Directive 1907/2006, WEEE Regulation: Directive 20021961E, RoHS Regulation: Directive
2015/863
SPARE OPERATING TIMES, POWER OUTLET AND LOAD OUTPUT POWER
Charging current for batteries and battery capacity
The unit reads the connected system load and charges the batteries with available residual current
from the power supply. The device performs qualified* battery tests and notifies when batteries need
to be replaced. The batteries are charged gently to extend their life and protection is available against
overcharging.
12 V / 24 V Maximum charging current for batteries
NOVA FLX M 6 A
The battery backup has controlled charging ** (controlled charging) which prevents batteries from being
overcharged and extends their service life significantly. The NOVA series must be used with AGM
batteries.
Battery capacity in 24 V units
24 V Battery ca-
pacity Maximum battery
capacity with 1
battery box
Maximum battery ca-
pacity with 2 battery
boxes
Maximum battery ca-
pacity with 3 battery
boxes
Maximum battery ca-
pacity with 4 battery
boxes
NOVA
FLX M,
24 V
20 Ah (2 x
20 Ah 65 Ah (4 x 20 Ah) 110 Ah (2 x 20 Ah + 2 x
45 Ah) 155 Ah (6 x 20 Ah + 2 x
45 Ah) 200 Ah (2 x 20 Ah + 8 x
45 Ah)
* Battery test is done with power resistor and the unit is tested and certified together with UPLUS 10+ Design life AGM batteries according
to SSF1014. It is these batteries that must be used to maintain the certificate.
** Controlled charging means that when the batteries are fully charged, they will be disconnected electronically for standby mode for up to
20 days or when the batteries have reached 26.7 V (24 V). By discharging the batteries and charging them continuously (instead of never
using them), the system extends the battery life by up to 50%. The batteries connect automatically in less than 50 microseconds.
Power outlet
Unit without
battery box Unit with
1 battery box
Unit with
2 battery boxes
Unit with
3 battery boxes
Unit with
4 battery boxes
Battery 2 pcs. 20 Ah 2 st 45 Ah /
2 st 20 Ah +
2 st 45 Ah
4 st 45 Ah /
2 st 20 Ah +
4 st 45 Ah
6 st 45 Ah /
2 st 20 Ah +
6 st 45 Ah
8 st 45 Ah /
2 st 20 Ah +
8 st 45 Ah
Max battery capacity 20 Ah 45 Ah / 65 Ah 90 Ah / 110 Ah 135 Ah / 155 Ah 180 Ah / 200 Ah
According to.
SSF1014, Alarm Class
1-2
1.6 A 3.7 A / 5.3 A 7.4 A / 9.1 A 11.2 A / 12.8 A 14.9 A / 16.6 A
According to.
SSF1014, Alarm Class
3-4
0.65 A 1.5 A / 2.1 A 3.0 A / 3.6 A 4.5 A / 5.1 A 6.0 A / 6.6 A
Imax A (max discharge
current) 5 A 5 A / 5 A 5 A / 5 A 5 A / 5 A 5 A / 5 A
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

Unit without
battery box Unit with
1 battery box
Unit with
2 battery boxes
Unit with
3 battery boxes
Unit with
4 battery boxes
Imax b (max charging
current) 5 A 5 A / 5 A 5 A / 5 A 5 A / 5 A 5 A / 5 A
Imin is always 0 A.
Not all devices may be certified, see device certificate.
Unit without
battery box Unit with
1 battery box
Unit with
2 battery boxes
Unit with
3 battery boxes
Unit with
4 battery boxes
Battery 2 st 20 Ah 2 st 45 Ah /
2 st 20 Ah +
2 st 45 Ah
4 st 45 Ah /
2 st 20 Ah +
4 st 45 Ah
64 st 45 Ah /
2 st 20 Ah +
6 st 45 Ah
8 st 45 Ah /
2 st 20 Ah +
8 st 45 Ah
Max battery capacity 20 Ah 45 Ah / 65 Ah 90 Ah / 110 Ah 135 Ah / 155 Ah 180 Ah / 200 Ah
According to.
SSF1014, Alarm Class
1-2
1.6 A 3.7 A / 5.3 A 7.4 A / 9.1 A 11.2 A / 12.8 A 14.9 A / 16.6 A
According to.
SSF1014, Alarm Class
3-4
0.65 A 1.5 A / 2.1 A 3.0 A / 3.6 A 4.5 A / 5.1 A 6.0 A / 6.6 A
Imax A (max discharge
current) 10 A 10 /10 10 /10 10 /10 10 /10
Imax b (max charging
current) 10 A 10 /10 10 /10 10 /10 10 /10
Imin is always 0 A.
Not all devices may be certified, see device certificate.
Power outlet
Info NOVA TERRA 24V 5A UT
Battery 2 pcs. 45 Ah
Max battery capacity 45 Ah
According to. SSF1014, Alarm Class 1-2 3.7 A
According to. SSF1014, Alarm Class 3-4 1.5 A
Imax A (max discharge current) 5 A
Imax b (max charging current) 5 A
Imin is always 0 A.
Permitted average load according to SSF1014 Alarm class 1-4:
NOVA 24 V FLX M
Permitted average load according to SSF1014 Alarm
class 1-4: NOVA 24V
5A FLX M NOVA 24V
10A FLX M NOVA 24V 25A
FLX M NOVA 24V 25A
FLX L
FLX M without battery box according to Alarm class 1-2 / 3-4 1.6 A / 0.55
A1.6 A / 0.55 A 1.6 A / 0.55 A 1.6 A / 0.55 A
Including 1 pc. Battery box FLX M, according to Alarm class
1-2 / 3-4: 3.7 A / 1.5 A 3.7 A / 1.5 A 3.6 A / 1.4 A 3.6 A / 1.4 A
Including 2 pcs. Battery box FLX M, according to Alarm class
1-2 / 3-4: - 7.4 A / 3A 7.3 A / 2.9 A 7.3 A / 2.9 A
Including 3 pcs. Battery box FLX M, according to Alarm class
1-2 / 3-4: - - 11.1 A / 4.4 A 11.1 A / 4.4 A
Including 4 pcs. Battery box FLX M, according to Alarm class
1-2 / 3-4: - - - 14.8 A / 5.9 A
Reserve operating times for different alarm classes - overview
Alarm class Spare operating time in the event of a power
failure Maximum number of hours of battery re-
charging (80%)
EN54-4 - 24 h
SBF110: 8 30 h + 10 min 24 h
EN50131-6 grades 1-2 12 h 72 h
EN50131-6 grade 3 24 h 24 h
SSF1014 Alarm class 1/2 12 h 72 h
2022-10-11
www.milleteknik.se Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

Alarm class Spare operating time in the event of a power
failure Maximum number of hours of battery re-
charging (80%)
SSF1014 Alarm class 3/4 30 h 24 h
The table shows the requirements for backup operating time and recharging of batteries for different
alarm classes.
CIRCUIT BOARDS - TECHNICAL DATA
Technical data, motherboard: PRO 3
Info Explanation
Short name: PRO 3
Product description Motherboard in battery backup with advanced functions and communication to parent sys-
tem.
Own consumption, with relay
card Less than 100 mA. All relays retracted on external alarm card in normal mode.
Switching time from mains volt-
age to battery operation When batteries are idle: <5 microseconds. When batteries are in charge cycle: 0 (none).
Batteries rest for 20-day cycles, after which a charging cycle picks up and charges the
batteries for 72 hours. If there is a power failure when batteries are in the charge cycle, there
is no switching time.
Incoming electricity network 230 V AC -240 V AC, 47-63 Hz.
Fuse on mains See table: Fuses.
Indication Indicator diode on circuit board / cabinet door
ALARM
Alarm displayed on indicator LED on the front of the cabinet.
• Cell fault in battery or unconnected battery.
• Charger fault, undervoltage.
• Charger fault, overvoltage.
• Low system voltage, system voltage below 24.0 V in mains operation.
• Low battery voltage, below 24.0 V DC, or mains interruption.
• Power failure alarm.
• Sabotage switch.
• Fuse fault.
• Aged battery
Expanding alarm functions are available via communication or with alarm cards.
Fuses
Fuses Type
5 A F5A
10 A F10A
Mains fuse for 24 V units up to 15 A T2.5AH250V. Ceramic.
Protection
Info Explanation
Deep discharge protection (Yes / No) Yes. 12 V units protection at 10V, +/- 0.5 V. 24 V units protection at 20, +/- 0.5 V.
Surge protection (Yes / No) Yes
Overtemperature protection (Yes / No) Yes
Short circuit protected = (Yes / No) Yes
Technical data, alarm card for PRO 3 / NEO3
Info Explanation
Card name: PRO 3
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

Info Explanation
Version: 1.2
Product description Motherboard in battery backup with advanced functions and communication to
superior systems.
Recommended environment Indoors, class 1. Ambient temperature: + 5 ° C - 40 ° C.
Protection class IPX0
Recommended installation NOVA Series (only 5 A and 10 A)
Input voltage 13.6 VDC, 27.3 VDC
Self-consumption 40 mA
Alarm via Alternating relay
Number of alarm outputs 4 st.
Certified according to EN 50131-6, SBF 110: 8, SSF1014, Meets alarm class 4, SSF 1014, edition 5
Certificate number (SBSC) 20-117
The product meets the requirements ac-
cording to CE directive according to: 765/2008, EMC Directive 2014 / 30EU, Emission:
EN61000-6-: 2001, EN55022: 1998: -A1: 2000, A2: 2003 Class B, EN61000-3-2:
2001, Immunity: EN61000- 6-2: 2005, EN61000-4-2, -3, 4, -5, -6, -11. SS-EN 50
130-4: 2011 Edition 2 & SSF1014 Alarm class 1-4 (Burglar alarm).
Producer Milleteknik AB
Country of origin Sweden
Alarm overview
Alarm overview in alpha-
betical order Relay 1 * /
Alarm out-
put 1
Relay 2 * /
Alarm out-
put 2
Relay 3 * /
Alarm out-
put 3
Relay 4 * /
Alarm out-
put 4
Communi-
cation (P5:
1-9)
Indicator
LED on
main card
and LED on
door.
Network outages X - - - X X
Fuse fault - X - - X X
Sabotage switch - - - X X X
Fan fault - - - - X -
Charger fault, overvoltage - X - - X X
Charger fault, undervoltage - X - - X X
Cell fault or unconnected
battery - X - - X X
Low system voltage. ** - - X - X X
Low battery voltage (<24.0
V DC) or power failure - X - - X X
Overtemperature - - - - X -
Undertemperature - - - - X -
Undertemperature - - - - X -
Short battery life left - - - - X -
Aged battery - X ** - - X ** X **
Overcurrent 100%, minute
average - - - - X -
Overcurrent 80%, daily
average - - - - X -
Overcurrent 175%, second
average - - - - X -
* Alarm on potential-free relay contact.
*** Not on NEO battery backups.
P4
RS-485 on P4: 1-4 Explanation
P4:1 GND
P4:2 RX
P4:3 TX
P4:4 +5V
2022-10-11
www.milleteknik.se Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

POWER SUPPLY
Power supply - Technical Data LRS-150-24
In:
NOVA 24V 5A FLX M
Info Explanation
Output voltage 27.3 V
Output current: 0 A - 6.5 A
Output voltage, ripple 200 mVp-p
Overvoltage 28.8 V - 33.6 V
Voltage recharge, ripple / current limitation Less than 0.6 Vp-p
Efficiency 89%
Current limitation 110% - 140%
Constant voltage +/- 0.5%
Regulatory accuracy + / - 1.0%
Input current (230 V) 1,7 A
Mains voltage frequency 47 Hz- 63 Hz
Mains voltage 230 V AC - 240 V AC
Brand effect 156 W
Temperature range -30°C - +70°C
Humidity range 20% - 90% RH non-condensed
The power supply is adapted and calibrated with the battery / hardware of the battery backup. Only power and calibrated power supplies may be used. Contact support when
changing power supplies. Use of power supplies coming from another source may cause damage not covered by the warranty. Warranty is canceled if power supplies (from a
source other than support / designated by support) that are not correctly calibrated are used.
Power supply - Technical Data RSP-320-24
In:
NOVA 24V 10A FLX M
Info Explanation
Output voltage 27.3 V
Output current 0 A - 13.4 A
Output voltage, ripple 150 mVp-p
Overvoltage 27.6 V - 32.4 V
Voltage recharge, ripple / current limitation Less than 1.2 Vp-p
Efficiency 89%
Current limitation 105% - 135%
Constant voltage +/- 0.5%
Regulatory accuracy +/- 1.0%
Input current (230 V) 2 A
Mains voltage frequency 47 Hz- 63 Hz
Mains voltage 230 V AC - 240 V AC
Brand effect 321.6 W
Temperature range -30°C - +70°C
Humidity range 20% - 90% RH non-condensed
The power supply is adapted and calibrated with the battery / hardware of the battery backup. Only power and calibrated power supplies may be used. Contact support when
changing power supplies. Use of power supplies coming from another source may cause damage not covered by the warranty. Warranty is canceled if power supplies (from a
source other than support / designated by support) that are not correctly calibrated are used.
TECHNICAL DATA ENCLOSURES
Enclosures - Technical Data FLX M
Info Explanation
Name FLX M
Enclosure class IP 32
Measure Height: 224 mm, width 438 mm, depth 212 mm
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

Info Explanation
Height units 5 HE
Mounting Wall or 19 "rack
Ambient temperature + 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.
Environment Environmental class 1, indoors. 20% ~ 90% relative humidity
Material Powder coated sheet
Color Black
Cable entries, number 4
Batteries that fit 2 pcs. 12 V, 20 Ah
Fan Yes
LINK TO THE LATEST INFORMATION
Products and software are subject to updates, you will always find the latest information on our website.
NOVA series
WARRANTY, SUPPORT, COUNTRY OF MANUFACTURE AND COUNTRY OF
ORIGIN
Warranty 5 years
The product has a five-year warranty, from the date of purchase (unless otherwise agreed). Free
230. Compensation for travel and or working hours in connection with the location of faults, installation
of repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information.
Milleteknik provides support during the product's lifetime, however, no later than 10 years after the
date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not
possible. Support may be added (at Millteknik's desrection) after the warranty period has expired.
Support
Do you need help with installation or connections? Our support phone is available: Monday-Thursday
08: 00-16: 00 and Fridays 08: 00-15: 00. Telephone support is closed between 11: 30-13: 15.
You can also send e-mail, we respond, on weekdays, usually in 24 hours.
Phone: +46 31-340 02 30
SPARE PARTS
Support handles questions about spare parts, see contact information above.
Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.
Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB
PRODUCT LIFE CYCLE, ENVIRONMENTAL IMPACT AND RECYCLING
The product is designed and constructed for a long service life, which reduces the environmental
impact. The product's service life depends on, among other things, environmental factors, mainly ambi-
ent temperature, unforeseen load on components such as lightning strikes, external damage, handling
errors, and more. Products are recycled by being handed over to the nearest recycling station or sent
2022-10-11
www.milleteknik.se Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

back to the manufacturer. Contact your distributor for more information. Costs that arise in connection
with recycling are not reimbursed.
BATTERIES - RECOMMENDED, NOT INCLUDED
Batteries are not included they are sold separately
Batteries are sold separately.
Battery combinations
Battery capacity (Ah) Battery type Number of batteries Batteries in unit
20 Ah 20 Ah 2 pcs 2 in Battery Backup
45 Ah 45 Ah 2 pcs 0 in Battery Backup
2 in Battery Box 1
65 Ah 20 Ah +
45 Ah
4 st 2 in Battery Backup
2 in Battery Box 1
90 Ah 45 Ah 4 st 0 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
110 Ah 20 Ah +
45 Ah
6 st 2 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
135 Ah 45 Ah 6 st 0 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
2 and Batteribox 3
155 Ah 20 Ah +
45 Ah
8 st 2 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
2 and Batteribox 3
180 Ah 45 Ah 8 st 0 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
2 and Batteribox 3
2 and Batteribox 4
200 Ah 20 Ah +
45 Ah
10 pieces 2 in Battery Backup
2 in Battery Box 1
2 and Batteribox 2
2 and Batteribox 3
2 and Batteribox 4
14 Ah, 12 V AGM battery
Battery type V Ah
Maintenance-free AGM, lead-acid battery. 12 V 14 Ah
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

10+ Design life * battery
Article number E-number Article name Terminal Measure. Height
width depth Weight per
piece Make
MT113-12V14-01 5230537 UPLUS 12V 14Ah 10+
Design Life battery Flat pin 6.3
mm 151x98x101 mm 4.2 kg UPLUS
* Design Life is the durability this year for unused battery. Environmental factors such as heat and load affect service life. Batteries that
have a durability (+10 Design lLife) of 10+ years usually need to be replaced after 4-5 years.
Reserve operating times for different alarm classes - overview
The table shows the requirements for backup operating time and recharging of batteries for different
alarm classes.
IMPORTANT
This is a guide and all times are approximate and may differ from actual times. Load,
temperature and other factors come into play, which is why exact time can not be
provided.
Applies to new batteries.
Backup operating times 24 V units - without battery box
Medium current 7.2 Ah 14 Ah 28 Ah 45 Ah
Loading Backup operating time (approx.), Minutes
0.5 A 450 820 1650 2350
1 A 260 485 970 1460
2 A 150 280 560 920
4 A 90 165 335 550
6 A 67 125 245 405
8 A 57 105 210 350
10 A 44 80 160 270
12 A 38 70 140 235
14 A 33 60 120 200
16 A 28 50 100 170
18 A 25 45 89 150
20 A 23 42 84 142
Backup operating times 24 V units - with battery box, 28 Ah - 70 Ah
Medium current 28 Ah 42 Ah 65 Ah 70 Ah
- 4 batteries
(14 Ah)
6 batteries
(14 Ah)
4 batteries
(20Ah + 45 Ah)
10 batteries
(7 Ah)
Loading Backup operating time (approx.), Minutes
0.5 A 1650 2090 5574 3440
1 A 970 865 3252 2118
2 A 560 815 1770 1329
4 A 335 490 930 864
6 A 245 360 600 605
8 A 210 310 426 544
10 A 160 240 342 414
12 A 140 210 270 363
14 A 120 180 234 311
16 A 100 150 204 286
18 A 90 130 150 254
20 A 84 126 138 241
2022-10-11
www.milleteknik.se Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille

Backup operating times 24 V units - with battery box, 90 Ah - 155 Ah
Medium current 90 Ah 110 Ah 135 Ah 155 Ah
- 4 batteries
(45 Ah)
6 batteries
(20 Ah + 45 Ah)
6 batteries
(45 Ah)
8 batteries
(20 Ah + 45 Ah)
Loading Backup operating time (approx.), Minutes
0.5 A 4705 5796 7056 8215
1 A 2928 3582 4392 5070
2 A 1836 2247 2754 3230
4 A 1183 1438 1762 2018
6 A 788 959 1175 1345
8 A 748 861 1048 1150
10 A 570 689 839 920
12 A 499 603 699 765
14 A 427 516 629 655
16 A 404 499 592 590
18 A 359 444 526 520
20 A 340 420 498 495
Backup operating times 24 V units - with battery box, 180 Ah - 225 Ah
Medium current 180 Ah 200 Ah 225 Ah
- 8 batteries
(45 Ah)
10 batteries
(20 Ah + 45 Ah)
10 batteries
(45 Ah)
Loading Backup operating time (approx.), Minutes
0.5 A 9408 12972 11760
1 A 5856 7872 7320
2 A 3672 4548 4590
4 A 2365 2670 2945
6 A 1577 1780 1960
8 A 1500 1558 1800
10 A 1140 1246 1410
12 A 950 1038 1200
14 A 855 890 1055
16 A 810 902 995
18 A 715 802 885
20 A 680 722 840
2022-10-11
Milleteknik AB, Ögärdesvägen 8 B, 433 30 Partille www.milleteknik.se

Other manuals for NOVA FLX M
1
This manual suits for next models
4
Table of contents
Other milleteknik Camera Accessories manuals
Popular Camera Accessories manuals by other brands

Duracell
Duracell Lithium Manganese Dioxide none Specification sheet

Schwaiger
Schwaiger ULTIMATE SAT Finder SF 9003 BT user guide

black forest motion
black forest motion 3D-Photogrammetry Bundle quick start guide

Laing
Laing PTZ-FALCON user manual

Panasonic
Panasonic Lumix H-VS014140 operating instructions

Power-Blox
Power-Blox PBX-200 PB Installation and operating instructions