MistAway Gen III+ Manual

MistAway® Tankless Misting Unit – Gen III+
Copyright © 2010 by MistAway® Systems, Inc.
Visit us on the web at
www.mistaway.com
Set Up Instructions

• Pressing Green ►button will cycle through each of four System
Modes. The ▲at the top of the display points to the active
System Mode.
1.OFF – Unit will perform a daily agitation cycle and otherwise
sit idle.
2.ON – Unit will allow Remote and MANUAL MISTs, but no
AUTO MISTs.
Section 3
Setting Up the Unit
Using the Controller • With the display showing day, time
and level, press Green ►button to
position the ▲at top of display
pointing to the active System Mode:
• OFF - daily agitation cycle only
• ON – remote and manual, but no
programmed mist
• AUTO Everyday – program runs
daily. This is the usual mode.
• AUTO Custom – program runs on
days configured in CUSTOM PGM
11. Set System Mode
• Clear area
• Pres MIST button on transmitter
• Unit will FILL, DOSE, insecticide,
Agitate (AGT) and MIST.
12. Test by Activating
Remote Mist
• DATA Menu, read AFR (average
flow rate) value
13. Determine Nozzle
Flow Rate of Circuit
Section 3
Setting Up the Unit
3.AUTO-EVERYDAY – Misting program runs daily. This is the
most commonly used System Mode.
4.AUTO-CUSTOM – Misting program runs only on days set in
CUSTOM PGM menu.
• Pressing Red MENU/STOP button displays triangular cursor by
DAY/TIME position on left side of display. Use ▲or ▼buttons to
cycle through menu structure. Use Green ►button to select
menu item and view or change data element within that item.
• Within a menu item, the convention is that the flashing data
element can be changed with the ▲or ▼buttons. Move to the
next data element with the Green ►button.
• Exit the menu item by pressing the MENU button. The unit will
revert to previous System Mode in 3 minutes if the MENU button
is not pressed.
• Clear any error code by pressing the Red MENU/Stop button for
5 seconds. The System Mode will return to its previous state
(usually AUTO Everyday).
• To reset the controller to factory settings, unplug the unit, and
hold down MENU and the ▲buttons while plugging the unit
back in. Mist Cycles, remote duration and number of nozzles
must be reentered.
• Secure key in a safe location.
14. Close Lid and Lock
flow rate) value
• Enter that value as the nozzle flow
rate, NFR, to be used in system
error calculations
• DATA Menu, NFR. Press Green ►
button for 5 seconds, then use the ▲
or ▼buttons to adjust value to be
the same as read in AFR.
Flow Rate of Circuit

• On firm level surface.
• Free from flooding or sprinklers.
• Near GFCI outlet and faucet.
1. Position Gen III+ Unit
• Confirm faucet is able to deliver at
least 1 gal/min..
• Be careful not to introduce dirt or
other contaminants into line.
• Insert 3/8” tubing/filter assembly into
3/8” bulkhead fitting located at the
back right corner of unit.
• Thread adapter onto faucet (or
optional hose bib “Y”).
• Measure and cut 3/8” nylon tubing
• Run water to flush line before
connecting to filter inlet.
2. Install Water Supply
Line
3. Connect Nozzle
Circuit
• To ¼” bulkhead fitting at back right
corner of unit.
• If zone kit, install according to
instructions provided.
Section 3
Setting Up the Unit
• SET-UP Menu, ALT.
• If sensor installed, set
time (in seconds) that
alarm will sound prior to
each scheduled and
remote mist.
j. Establish
optional
External Alarm
• CYCLES Menu.
• 2 – 3 scheduled mists of 30 – 60
seconds in duration is common.
• See Section 5, Managing Insecticide
for field standard frequency, duration
and mist times.
• Blinking C# identifies each
automatic mist cycle with current
mist duration and mist time. Limit is
24 cycles per day.
•
Set mist duration and time (note
a. Set AUTO
MIST Cycles
9. Set Misting Schedule
Section 3
Setting Up the Unit
• GFCI Outlet.
• 115 volts minimum. Confirm voltage
with multi-meter.
• 15 amp circuit required. Unit draws
9 amps when misting. Ensure total
load of unit plus all other devices on
circuit does not exceed breaker
rating.
5. Connect Electric
Power
instructions provided.
4. Connect Remote
Antenna
• Thread onto coax fitting on top of
unit.
• MAINTENANCE Menu, scroll to INS.
• Depress Green ►button 5 seconds
• Unit will fill and mist for 5 minutes or
until stopped.
• Confirm pump pressure (240 psi)
and insert plastic plug into pump
adjustment port.
• Confirm no leaks in nozzle circuit
• If zone valve installed, repeat for
INS2.
6. Run Inspection
Cycle
•
Set mist duration and time (note
AM/PM) for each desired scheduled
mist.
• MAINTENANCE Menu, scroll to
CHG.
• Depress Green ►button 5 seconds.
• DOSE will flash for extended period
as batch tank of fresh water is
brought to target concentration.
10. Charge Insecticide
• If you don’t want to schedule mists
for every day.
• CUSTOM PGM Menu.
• Set selected days to ON or OFF.
• System Mode must be set to AUTO
Custom.
b. Set AUTO MIST
Days

• Remove factory cap and seal from
pour port.
• Thread bottle cap onto pour port,
ensuring it is not cross-threaded or
too tight.
a. Secure Cap on
Bottle
• Remove seal on vent port so that
bottle does not collapse as
insecticide is pumped out.
• Insert bottle into coupler (Pressing
button on coupler will free bottle for
removal.)
• EMPCAR (empty cartridge)
continues to appear in display.
b. Vent Opposite
Port and Insert
Bottle into
Coupler
7. Install Insecticide and Program Dose Settings
• MAINTENANCE Menu, scroll to
REFILL
• Depress Green ►button 5 seconds
to enter routine.
c. Set Dose
Settings
Section 3
Setting Up the Unit
• DAY/TIME Menu.
• Set to ON if daylight savings in
effect, OFF if not.
• Press Green ►to advance.
a. Set Daylight
Savings Time
switch
• Set Day and Time. (note AM and PM)
• Exit by pressing Menu button.
b. Set Day and
Time
8. Program System Setup
• SET-UP Menu, REM.
• Set duration in seconds.
c. Set REMOTE
MIST Duration
• Set dip switches in remote
transmitter. (see Section 4, Using the
Remote)
• SET-UP Menu, LRN.
• Depress Green ►button 5 secs,
until LRN On and countdown starts.
• Depress Remote Transmitter button
until DONE is displayed.
d. Orient Remote
Transmitter
Section 3
Setting Up the Unit
to enter routine.
• Set MIX ratio (parts water to 1 part
concentrate) to target. Default is
108:1 See Section 5, Managing
Insecticide for guidance
• Push Green ►button to advance
• Set bottle size (BOT) in ounces.
Default is 64 oz. Range is 2 to 256
oz.
• Push Green ►button to advance
• Set LEVEL in the bottle. Eight bars
indicates a full bottle of the size
entered in previous step. Four bars
indicates bottle is ½ full.
• Push Green ►button
• DONE will be displayed.
• VENT will be displayed. Confirm
VENT by pushing Green ►button.
• SET-UP Menu, MAN.
• Set duration in seconds.
e. Set MANUAL
MIST Duration
• SET-UP Menu, SEN.
• If sensor installed, ON. Otherwise
OFF.
h. Establish
optional Wind
Sensor
• SET-UP Menu, NOZ.
• If zone valve installed, repeat for NZ2.
f. Set # of nozzles
• SET-UP Menu, WND.
• Set max wind speed.
i. Set Max Wind
Speed (wind
sensor required)
• SET-UP Menu, AGT.
• Set duration of agitation that occurs
prior to each AUTO mist. Default is
15 seconds.
• Set time of once-daily agitation.
Default is 3:00 pm.
• SET-UP Menu, RAG.
• Set duration of agitation that occurs
prior to each REMOTE mist.
g. Set Agitation
Parameters
Table of contents
Other MistAway Lawn And Garden Equipment manuals
Popular Lawn And Garden Equipment manuals by other brands

Sunforce
Sunforce SOLAR user manual

GARDEN OF EDEN
GARDEN OF EDEN 55627 user manual

Goizper Group
Goizper Group MATABI POLMINOR instruction manual

Rain Bird
Rain Bird 11000 Series Operation & maintenance manual

Cub Cadet
Cub Cadet BB 230 brochure

EXTOL PREMIUM
EXTOL PREMIUM 8891590 Translation of the original user manual

Vertex
Vertex 1/3 HP Maintenance instructions

GHE
GHE AeroFlo 80 manual

Land Pride
Land Pride Post Hole Diggers HD25 Operator's manual

Yazoo/Kees
Yazoo/Kees Z9 Commercial Collection System Z9A Operator's & parts manual

Premier designs
Premier designs WindGarden 26829 Assembly instructions

Snapper
Snapper 1691351 installation instructions