
GB
GB-17
WT07828X01
Pipes A, A1, A2[mm (in)]
Unit model Combination unit Pipe A Pipe A1*1Pipe A2*1
Unit 1 Unit 2 High-pressure Low-pressure High-pressure Low-pressure High-pressure Low-pressure
P72ZKMU - - ø15.88 (5/8) ø19.05 (3/4) - - - -
P96ZKMU - - ø19.05 (3/4) ø22.2 (7/8) - - - -
P120ZKMU - - ø19.05 (3/4) ø28.58 (1-1/8) - - - -
P144ZKMU - - ø22.2 (7/8) ø28.58 (1-1/8) ----
P168ZSKMU P96 P72 ø22.2 (7/8) ø28.58 (1-1/8) ø19.05 (3/4) ø22.2 (7/8) ø15.88 (5/8) ø19.05 (3/4)
P192ZSKMU P96 P96 ø22.2 (7/8) ø28.58 (1-1/8) ø19.05 (3/4) ø22.2 (7/8) ø19.05 (3/4) ø22.2 (7/8)
P216ZSKMU P120 P96 ø28.58 (1-1/8) ø28.58 (1-1/8) ø19.05 (3/4) ø28.58 (1-1/8) ø19.05 (3/4) ø22.2 (7/8)
P240ZSKMU P120 P120 ø28.58 (1-1/8) ø34.93 (1-3/8) ø19.05 (3/4) ø28.58 (1-1/8) ø19.05 (3/4) ø28.58 (1-1/8)
P264ZSKMU P144 P120 ø28.58 (1-1/8) ø34.93 (1-3/8) ø22.2 (7/8) ø28.58 (1-1/8) ø19.05 (3/4) ø28.58 (1-1/8)
P288ZSKMU P144 P144 ø28.58 (1-1/8) ø34.93 (1-3/8) ø22.2 (7/8) ø28.58 (1-1/8) ø22.2 (7/8) ø28.58 (1-1/8)
*1 If the combination units 1 and 2 are in a different order as listed in the table, make sure to use the pipes of appropriate size for the situation.
Pipe B [mm (in)]
Total capacity of indoor units Pipe
Liquid Gas
30 or below ø9.52 (ø3/8) ø15.88 (ø5/8)
Pipes C, D, E [mm (in)]
Total model number of downstream
indoor units Pipe
High-pressure Low-pressure Liquid
72 or below ø15.88 (ø5/8) ø19.05 (ø3/4) ø9.52 (ø3/8)
73 to 108 ø19.05 (ø3/4) ø22.2 (ø7/8) ø9.52 (ø3/8)
109 to 126 ø19.05 (ø3/4) ø28.58 (ø1-1/8) ø12.7 (ø1/2)
127 to 144 ø22.2 (ø7/8) ø28.58 (ø1-1/8) ø12.7 (ø1/2)
145 to 168 ø22.2 (ø7/8) ø28.58 (ø1-1/8) ø15.88 (ø5/8)
Pipes a,b,c,d,e,f [mm (in)]
Capacity index of indoor unit Pipe
Liquid Gas
06, 08, 12, 15, 18 ø6.35 (ø1/4) ø12.7 (ø1/2)
24, 27, 30, 36, 48, 54 ø9.52 (ø3/8) ø15.88 (ø5/8)
72 ø9.52 (ø3/8) ø19.05 (ø3/4)
96 ø9.52 (ø3/8) ø22.2 (ø7/8)
Pipes g, h, i, j [mm (in)]
Capacity index of indoor unit Liquid pipe Gas pipe
ghi j
36 ø9.52 (ø3/8) ø9.52 (ø3/8) ø15.88 (ø5/8) ø15.88 (ø5/8)
48 ø9.52 (ø3/8) ø9.52 (ø3/8) ø15.88 (ø5/8) ø15.88 (ø5/8)
54 ø9.52 (ø3/8) ø9.52 (ø3/8) ø15.88 (ø5/8) ø15.88 (ø5/8)
72 ø9.52 (ø3/8) ø9.52 (ø3/8) ø19.05 (ø3/4) ø15.88 (ø5/8)
96 ø9.52 (ø3/8) ø9.52 (ø3/8) ø22.2 (ø7/8) ø15.88 (ø5/8)
9-5. Piping connections and valve operations
Before heating the brazed sections, remove the gas and oil that are trapped in the pipes.
- Failure to do so may generate fire, resulting in serious injury.
Ventilate the room while servicing the unit.
- If the refrigerant leaks, oxygen deficiency may result. If the leaked refrigerant comes in contact with a heat source,
toxic gas will be generated.
Store pipes indoors, and keep both ends of the pipes sealed until just before making a flare connection or
brazing. (Store elbows and other joints in plastic bags.)
- If dust, dirt, or water enters the refrigerant lines, the refrigerant oil will deteriorate and the compressor will
malfunction.
Keep the service valves closed until refrigerant charging is completed.
- Failure to do so will damage the unit.
Place a wet towel on the service valves before brazing the pipes to keep the temperature of the valves from
rising above 120ºC (248ºF).
- Failure to do so may result in equipment damage.