15
6-5. EHSD-TM9D.UK, EHSC-TM9D.UK
Table 1 Signal Inputs
Name
Terminal block
Connector
Item OFF (Open) ON (Short)
IN1 TBI.1 7-8 — Room thermostat
1 input *1
Refer to SW2-1 in
<Table 6.6.1 DIP Switch Functions>.
IN2 TBI.1 5-6 — Flow switch 1
input
Refer to SW2-2 in
<Table 6.6.1 DIP Switch Functions>.
IN3 TBI.1 3-4 — Flow switch 2
input (Zone1)
Refer to SW3-2 in
<Table 6.6.1 DIP Switch Functions>.
IN4 TBI.1 1-2 — Demand control
input Normal Heat source OFF/
Boiler operation *3
IN5 TBI.2 7-8 — Outdoor thermo-
stat input *2
Standard opera-
tion
Heater operation/
Boiler operation *3
IN6 TBI.2 5-6 — Room thermostat
2 input *1
Refer to SW3-1 in
<Table 6.6.1 DIP Switch Functions>.
IN7 TBI.2 3-4 — Flow switch 3
input (Zone2)
Refer to SW3-2 in
<Table 6.6.1 DIP Switch Functions>.
IN8 TBI.3 7-8 — Electric energy
meter 1
Refer to installation manual.
IN9 TBI.3 5-6 — Electric energy
meter 2
IN10
TBI.2 1-2 — Heat meter
IN11
TBI.3 3-4 — Smart grid ready
input
IN12
TBI.3 1-2 —
INA1
TBI.4 1-3 CN1A Flow sensor
*1. Set the ON/OFF cycle time of the room thermostat for 10 minutes or more;
otherwise the compressor may be damaged.
*2. If using outdoor thermostat for controlling operation of heaters, the lifetime of the
heaters and related parts may be reduced.
*3. To turn on the boiler operation, use the main remote controller to select “Boiler” in
“External input setting” screen in the service menu.
Symbol Name
TB1 Terminal block <Power supply, Outdoor unit>
ECB1 Earth leakage circuit breaker for booster heater
MP1 Water circulation pump 1(Space heating & DHW)
MP2 Water circulation pump 2
(Space heating for Zone1)(Local supply)
MP3 Water circulation pump 3
(Space heating for Zone2)(Local supply)
MP4 Water circulation pump 4 (DHW)(Local supply)
3WV(2WV1)
3-way valve (2-way valve 1)(Local supply)
2WV2a 2-way valve (For Zone 1)(Local supply)
2WV2b 2-way valve (For Zone 2)(Local supply)
MXV Mixing valve (Local supply)
BHT Thermostat for booster heater
BHF Thermal fuse for booster heater
BH1 Booster heater 1
BH2 Booster heater 2
BHC1 Contactor for booster heater 1
BHC2 Contactor for booster heater 2
BHCP Contactor for booster heater protection
TH1 Thermistor (Room temp.)(Option)
TH2 Thermistor (Ref. liquid temp.)
THW1 Thermistor (Flow water temp.)
THW2 Thermistor (Return water temp.)
THW5B Thermistor (DHW tank water temp.)(Option)
THW6
THW7 Thermistor (Zone1 return temp.)(Option)
THW8
THW9 Thermistor (Zone2 return temp.)(Option)
THW10 Thermistor (Mixing tank temp.)(Option)
THWB1
IN1 Room thermostat 1 (Local supply)
IN2 Flow switch 1 (Local supply)
IN3 Flow switch 2 (Local supply)
IN4 Demand control (Local supply)
IN5 Outdoor thermostat (Local supply)
IN6 Room thermostat 2 (Local supply)
IN7 Flow switch 3 (Local supply)
IN8 Electric energy meter 1 (Local supply)
IN9 Electric energy meter 2 (Local supply)
IN10 Heat meter (Local supply)
IN11 Smart grid ready input (Local supply)
IN12
INA1 Flow sensor
FLOW TEMP. CONTROLLER (FTC)
TBO.1−4
Terminal block <Outputs>
TBI.1
−
6 Terminal block <Signal Inputs, Thermistor>
F1 Fuse (IEC T10AL250V)
F2 Fuse (IEC T6.3AL250V)
SW1
−
6 DIP switch *See Table 6.6.1
X1
−
16 Relay
LED1 Power supply (FTC)
LED2 Power supply (Main remote controller)
LED3 Communication (FTC-Outdoor unit)
LED4 Reading or writing data to SD card
CNPWM
Pump speed control signal for MP1
CN108 SD card connector
1
2
CN22
(BU)
CN108
1
3
CN3C
(BU)
1
3
CNPWM
(WH)
1
8
CN851
(BK)
1
5
CNRF
(WH)
Wireless receiver
(Option)
1
5
CN105
(RD)
WiFi adapter
(Option)
1
5
CNIT
(BU)
1
2
CN20
(RD)
1
3
CN21
(YE)
1
4
CNW12
(RD)
CNW5
(BU)
1
4
CN1A
(WH)
TBI.1
TAB1
1
8
1
8
1
8
1
8
1
6
SW1
SW2
SW3
SW4
SW5
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
3
1
7
1
3
1
3
CNBC
(GY)
CNBH
(WH)
CNBHT
(BK)
CNIH
(OG)
CNV1
(WH)
CNP4
(RD)
CNP1
(WH)
TBO.1
TBO.2
TBO.3
TBO.4
1
3
5
1
3
CNP4
(RD)
F1
F2
CN01
(BK)
TBO.1
X1
X2
X3
X14
1
3
3
CNPWM
(WH)
CNP1
(WH)1
3
M
1~
2WV2b
MP3
MP4
1
2
3
4
5
6
TBO.2
1
3
5
3WV
1
2
3
4
5
6
7
8
TBO.3
X4
X10
X16
X11
X12
TBO.4
1
2
3
4
5
6
7
8
X15
X13
X9
X8
Signal output
(Boiler)
Signal output
(thermo on)
Signal output
(Error)
Signal output
(Defrost)
Signal output
(Comp. on)
Signal output
(Cooling)
2WV2a
1
3
1
3
1
7
X6
X7
CNBHT
(BK)
CNBC
(GY)
CNBH
(WH)
1
5
3
1
5
3
1
3
1
3
3
5
FTC board
X5B
X5A
MXV
Close
N
Open
MP2
MP1
M
1~
M
1~
TBI.2TBI.3TBI.4TBI.5TBI.6
12345678 12345678 12345678 12345678 12345678 12345678
1
2
3
4
5
6
3
5
1
4
NL
S3S2S1
NL
S3S2S1
To outdoor
unit
TB1
OG OG
YE
YE
GNYE
To outdoor
unit
Power supply
~/N 230V 50Hz
TB1
OG
BU
RD
BU
RD
YE
GNYE
1
3
1
3
OG
BN
OG
BN
Indoor unit powered
by independent source
Indoor unit powered
via outdoor unit
CIRCUIT
BREAKER
1
3
5
CN3C
(BU)
CN3C
(BU)
CN01
(BK)
1
5
SW6
M
1~
M
1~
M
1~
M
1~
M
1~
OG
YE
1
3
5
CN01
(BK)
2WV1
M
1~
1
4
CN401
(WH)
456
TBO.2
L1
(1) L2
(3) L3
(5)
42
WH
RD
31 5
BK
6
42 6
WH
RD
BK
A1
A2
31 5
WH
RD
BK
ECB1
BHCP
A1
42 6 A2 42 6 A2
31 5 A1
WH/No.1
WH/No.2
VT
VT
BHC2BHC1
PK
PK
GY
GY
BH1 BH2
BHTBHF
θ
1
3
1
3
1
7
CNBH
(WH)
CNBC
(GY)
CNBHT
(BK)
2
2
2
2
2
2
WH
WH
Power supply
to Booster heater
3~ 230V 50Hz
3
5
2 2
WH/No.3
BU/No.4
BU/No.5
BU/No.6
CN01
(BK)
F1F2
t° t° t°
12345678
IN4IN3IN2IN1
12345678
IN10IN7IN6IN5
12345678
IN12IN9IN8 IN11
12345678
OUTA1
1 4
Flow
Sensor
CN1A
(WH)
12345678
t°
THW6 THW7 THW8 THW9
t° t°
12345678
THWB1 THW10
2 1
Main remote
controller
TBI.1 TBI.2 TBI.3 TBI.4 TBI.5TBI.6
CN20
(RD)
t°
CN21
(YE)
1 3 1 2
CNW12
(RD)
14
CNW5
(BU)
t°
TAB1
CN22
(BU)
THTH1TH2THW5B
- + + -
V
- + - +
14
t° t°t°
THW2THW1
1 4
Pressure
Sensor
CN401
(WH)
CNV1
(WH)
Table 2 Outputs
Name
Terminal block
Connector
Item OFF ON
OUT1
TBO.1 1-2 CNP1 Water circulation pump 1 output
(Space heating/cooling & DHW) OFF ON
OUT2
TBO.1 3-4 — Water circulation pump 2 output
(Space heating/cooling for Zone1) OFF ON
OUT3
TBO.1 5-6 —
Water circulation pump 3 output
(Space heating/cooling for Zone2) *1 OFF ON
2-way valve 2b output *2
OUT4
TBO.2 4-6 CNV1 3-way valve (2-way valve) output Heating DHW
—
CN851
3-way valve output
OUT5
TBO.2 1-2 — Mixing valve output *1 Stop Close
TBO.2 2-3 Open
OUT6
—
CNBH 1-3
Booster heater 1 output OFF ON
OUT7
—
CNBH 5-7
Booster heater 2 output OFF ON
OUT8
TBO.4 7-8 — Cooling signal output OFF ON
OUT9
TBO.4 5-6 CNIH Immersion heater output OFF ON
OUT10
TBO.3 1-2 — Boiler output OFF ON
OUT11
TBO.3 5-6 — Error output Normal Error
OUT12
TBO.3 7-8 — Defrost output Normal Defrost
OUT13
TBO.4 3-4 — 2-way valve 2a output *2 OFF ON
OUT14
— CNP4 Water circulation pump 4 output
(DHW) OFF ON
OUT15
TBO.4 1-2 — Comp. ON signal OFF ON
OUT16
TBO.3 3-4 — Thermo ON signal OFF ON
OUTA1
TBI.4 7-8 — Analog output 0V-10V
Do not connect to the terminals that are indicated as “—” in the “T
*1. For 2-zone temperature control.
*2. For 2-zone valve ON/OFF control.
Tool
Tool
Conductor Conductor
Outline view Top view
<How to use TBO.1 to 4>
Connect them using either way as shown below.
1. Symbols used in wiring diagram are,
: connector, : terminal block.
2. Indoor unit and outdoor unit connecting
wires have polarities, make sure to match
terminal numbers (S1, S2, S3) for correct
wirings.
3. Since the outdoor unit side electric wiring
may change, be sure to check the outdoor
unit electric wiring diagram for service.
LED1
LED2
LED3
LED4
OCH712C