Mitsubishi Heavy Industries SRK20HC-S User manual

-
1
-
CONTENTS
1. GENERAL INFORMATION .............................................................................. 1
1.1 Specific features ....................................................................................... 1
1.2 How to read the model name ................................................................... 1
2. SELECTION DATA........................................................................................... 2
2.1 Specifications ........................................................................................... 2
2.2 Range of usage & limitations .................................................................. 5
2.3 Exterior dimensions ................................................................................. 5
2.4 Piping system ........................................................................................... 7
2.5 Selection chart .......................................................................................... 8
3. ELECTRICAL DATA ........................................................................................ 9
3.1 Electrical wiring ........................................................................................ 9
4. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ................... 10
4.1 Operation control function by remote control switch ........................... 10
4.2 Back-up switch.......................................................................................... 11
4.3 Power-cut compensation ......................................................................... 11
4.4 Flap control ............................................................................................... 12
4.5 Comfort timer setting ............................................................................... 12
4.6 Outline of heating operation .................................................................... 13
4.7 Outline of cooling operation .................................................................... 16
4.8 Outline of dehumidifying operation ........................................................ 17
4.9 Automatic operation ................................................................................. 18
4.10 Protective control function ...................................................................... 18
5. APPLICATION DATA ....................................................................................... 20
5.1 Selection of location for installation ....................................................... 21
5.2 Installation of indoor unit......................................................................... 22
5.3 Installation of outdoor unit ...................................................................... 24
5.4 Refrigerant piping ..................................................................................... 24
5.5 Test run ...................................................................................................... 26
5.6 Precautions for wireless remote controller installation and
operation ................................................................................................... 26
6. MAINTENANCE DATA..................................................................................... 27
6.1 Trouble shooting ....................................................................................... 27
6.2 Servicing.................................................................................................... 32

-
1
-
Serial signal transmission error
1 GENERAL INFORMATION
1.1 Specific features
The “Mitsubishi Daiya” room air-conditioner: SRK series are of split and wall mounted type and the unit consists of indoor unit and
outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or heating equipment with opera-
tion control switch and the outdoor unit is composed of condensing unit with compressor.
(1) Remote control flap
The flap can be automatically controlled by operating wireless remote controller.
¡Air scroll: Flap operation is automatically control.
¡Swing: This will swing the flap up and down.
¡Memory flap: Once the flap position is set, the unit memorizes the position and continues to operate at the same position from
the next time.
(2) Automatic Operation
When the remote control switch is set on “auto( ) ”, it will either automatically decide operation mode such as cooling, heating
and thermal dry, or operate in the operation mode before it has been turned to automatic control.
(3) Self diagnosis function
¡We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as
follows.
R410A models
Series No.
Heat pump type
Product capacity
Wall mounted type
Split type room air-conditioner
1.2 How to read the model name
Example : SR K 40 H C - S
Room temperature thermistor error
Indoor fan motor error
Heat exchanger thermistor error
2 time flash
6 time flash
TIMER lamp
ON
1 time flash
Outdoor unit heat exchanger
thermistor error
Discharge pipe thermistor error
Outdoor temperature thermistor
error
2 time flash
4 time flash
RUN lamp
keeps flashing
1 time flash
OFF
OFF
OFF
Outdoor unit error
Compressor overheat
Current cut
2 time flash
5 time flash
RUN lamp
ON
1 time flash
2 time flash
5 time flash
1 time flash
6 time flash 6 time flash
RUN lamp TIMER lamp Outdoor (LED)

-
2
-
Item
Model SRK20HC-S SRC20HC-S
Cooling capacity(1) W 2050
Heating capacity(1) W 2200
Power source 1 Phase, 220/230/240V, 50Hz
Cooling input kW 0.635
Running current (Cooling) A 3.1/3.0/2.9
Heating input kW 0.605
Running current (Heating) A 3.0/2.9/2.8
Inrush current A 18.9
COP Cooling: 3.21 Heating: 3.61
Cooling sound level 38 48
Noise level Power level dB 52 60
Heating sound level 38 48
Power level 52 60
Exterior dimensions
Height ×Width ×Depth mm 250 ×815 ×247 540 ×720 ×290
Color Cool white Stucco white
Net weight kg 9.0 32
Refrigerant equipment
Compressor type & Q’ty –RM-B5077MNE4 (Rotary type) ×1
Motor kW –0.65
Starting method – Line starting
Heat exchanger Louver fins & inner grooved tubing
Refrigerant control Capillary tubes + Electric expansion valve
Refrigerant(3) kg R410A 0.9 (Pre-Charged up to the piping length of 15m)
Refrigerant oil R0.35 (MA68)
Deice control MC control
Air handling equipment
Fan type & Q’ty Tangential fan ×1 Propeller fan ×1
Motor W 14 12
(Cooling) 7.5 26
Air flow (at High) (Heating) CMM 7.5 26
Air filter, Q’ty Polypropylene net (washable) ×2–
Shock & vibration absorber – Cushion rubber (for compressor)
Electric heater ––
Operation control
Operation switch Wireless-Remote controller –
Room temperature control MC. Thermostat –
Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4″) Gas line: φ9.52 (3/8″)
Connecting method Flare connecting
Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m –
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size ×Core number 1.5 mm2×4 cores (Including earth cable)
Connection wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
2 SELECTION DATA
2.1 Specifications
Model SRK20HC-S (Indoor unit)
SRC20HC-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC – 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even in the short piping.)
Operation data
(1)
Refrigerant
piping
Compressor: Overheat protection, overcurrent protection, Serial signal error protection, Indoor fan mo-
tor error protection
The piping length is 7.5m.

-
3
-
Item
Model SRK28HC-S SRC28HC-S
Cooling capacity(1) W 2550
Heating capacity(1) W 2800
Power source 1 Phase, 220/230/240V, 50Hz
Cooling input kW 0.79
Running current (Cooling) A 3.9/3.7/3.5
Heating input kW 0.775
Running current (Heating) A 3.7/3.5/3.3
Inrush current A 17.2
COP Cooling: 3.21 Heating: 3.61
Cooling sound level 41 48
Noise level Power level dB 55 60
Heating sound level 42 48
Power level 56 60
Exterior dimensions
Height ×Width ×Depth mm 250 ×815 ×247 540 ×720 ×290
Color Cool white Stucco white
Net weight kg 9.0 32
Refrigerant equipment
Compressor type & Q’ty –5PS102DAB [Rotary type] ×1
Motor kW –0.7
Starting method – Line starting
Heat exchanger Louver fins & inner grooved tubing
Refrigerant control Capillary tubes + Electric expansion valve
Refrigerant(3) kg R410A 0.9 (Pre-Charged up to the piping length of 15m)
Refrigerant oil R0.35 (RB68A)
Deice control MC control
Air handling equipment
Fan type & Q’ty Tangential fan ×1 Propeller fan ×1
Motor W 14 15
(Cooling) 8.5 30
Air flow (at High) (Heating) CMM 8.0 30
Air filter, Q’ty
Polypropylene net (washable)
×
2
–
Shock & vibration absorber – Cushion rubber (for compressor)
Electric heater ––
Operation control
Operation switch Wireless-Remote controller –
Room temperature control MC. Thermostat –
Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4″) Gas line: φ9.52 (3/8″)
Connecting method Flare connecting
Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m –
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size ×Core number 1.5 mm2×4 cores (Including earth cable)
Connection wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Model SRK28HC-S (Indoor unit)
SRC28HC-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC – 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even in the short piping.)
Operation data
(1)
Refrigerant
piping
Compressor: Overheat protection, overcurrent protection, Serial signal error protection, Indoor fan
motor error protection
The piping length is 7.5m.

-
4
-
Item
Model SRK40HC-S SRC40HC-S
Cooling capacity(1) W 3600
Heating capacity(1) W 4000
Power source 1 Phase, 220/230/240V, 50Hz
Cooling input kW 1.12
Running current (Cooling) A 5.3/5.1/4.9
Heating input kW 1.165
Running current (Heating) A 5.5/5.3/5.1
Inrush current A 25.2
COP (Cooling) Cooling: 3.21 Heating: 3.42
Cooling sound level 42 51
Noise level Power level dB 56 63
Heating sound level 43 52
Power level 57 64
Exterior dimensions
Height ×Width ×Depth mm 250 ×815 ×247 640 ×850 ×290
Color Cool white Stucco white
Net weight kg 9.0 41
Refrigerant equipment
Compressor type & Q’ty –5KS150DBB [Rotary type] ×1
Motor kW –1.1
Starting method – Line starting
Heat exchanger Louver fins & inner grooved tubing
Refrigerant control Capillary tubes + Electric expansion valve
Refrigerant(3) kg R410A 1.17 (Pre-Charged up to the piping length of 15m)
Refrigerant oil R0.43 (RB68A)
Deice control MC control
Air handling equipment
Fan type & Q’ty Tangential fan ×1 Propeller fan ×1
Motor W 14 35
(Cooling) 9.5 38
Air flow (at High) (Heating) CMM 9.0 38
Air filter, Q’ty
Polypropylene net (washable)
×
2
–
Shock & vibration absorber – Cushion rubber (for compressor)
Electric heater ––
Operation control
Operation switch Wireless-Remote controller –
Room temperature control MC. Thermostat –
Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4″) Gas line: φ12.7 (1/2″)
Connecting method Flare connecting
Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m –
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size ×Core number 1.5 mm2×4 cores (Including earth cable)
Connection wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Model SRK40HC-S (Indoor unit)
SRC40HC-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
Heating 20ºC – 7ºC 6ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even in the short piping.)
Operation data
(1)
Refrigerant
piping
Compressor: Overheat protection, overcurrent protection, Serial signal error protection, Indoor fan
motor error protection
The piping length is 7.5m.

-
5
-
2.2 Range of usage & limitations
2.3 Exterior dimensions
(1) Indoor unit
Models SRK20HC-S, 28HC-S, 40HC-S
Indoor return air temperature
(Upper, lower limits)
Refrigerant line (one way) length Max. 15m
All models
Refer to the selection chart
Power source voltage Rating ±10%
Voltage at starting Min. 85% of rating
Frequency of ON-OFF cycle Max. 10 times/h
ON and OFF interval Max. 3 minutes
Outdoor air temperature
(Upper, lower limits)
Vertical height difference between
outdoor unit and indoor unit
Max. 5m (Outdoor unit is higher)
Max. 5m (Outdoor unit is lower)
Item
Models
Unit: mm
A
VIEW A
815
117.5 580 117.5
247
4.5
4.5
4.5
3
560
788
60 14.5
60
9
148.5
216.5
216.5
216.5
8.2
44.5
236.1
5.7
450
450
67.5
42.7
47.2
175
44.5
216.5
216.5
216.5
148.5
53.5
250
Piping for Gas
Therminal block
Piping hole right (left)
Drain hose 540 (ø16)
Piping for Liquid 465.1 (ø6.35)
Piping hole (ø65) Piping hole (ø65)
( )
20.28: ø9.52
40: ø12.7 397.1

-
6
-
(2) Outdoor unit
Models SRC20HC-S, 28HC-S
Drain hole
286.4
12
50
290
49.6 43.5
850
203.1 510 136.9
476
Elogated hole
(2-12 x16)
314 12
328
Terminal block
Service valve (Liquide)
ø6.35 (1/4'')
Service valve (Gas)
ø12.7 (1/2'')
Ground
terminal
124 34.6
20˚
20˚
42.7
100.3
15
640
14
Model SRC40HC-S
Unit: mm
290
540
14.4 47.4 42.6
264.5
71
404.5
510
720
17.8
Drain holes
50 12
39.7
99.9
340
312.5 13.5
14
139 2-16x12
61.9
139.3 33.3 Flare connecting ø6.35 (1/4")
Service valve (Liquid)
40°
40°
Flare connecting ø9.52 (3/8")
Service valve (Gas)
Terminal block

-
7
-
2.4 Piping system
Models SRK20HC-S, 28HC-S, 40HC-S
Outdoor unitIndoor unit
Room temp.
thermistor
Heat
exchanger
Flare connecting
Heat
exchanger
thermistor
Piping
(Liquid)
ø6.35
Check joint
4 way valve
Service valve (Liquid)
Flare connecting
Discharge temp.
thermistor
Cooling cycle
Heating cycle Outdoor air
temp. thermistor
Heat
exchanger
Heat exchanger
thermistor
Compressor
Capillary tube
Strainer
Accumulator
Service valve
(Gas)
Capillary tube
Electronic
expansion valve
( )
Piping
(Gas)
20, 28 : ø9.52
40 : ø12.7

-
8
-
2.5 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specification ✕ Correction factors as follows.
(1) Coefficient of cooling and heating capacity in relation to temperatures
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor
units.
(3) Correction relative to frosting on outdoor heat exchanger during heating
In additions to the foregoing corrections (1), (2) the heating capacity needs to be adjusted also with respect to the frosting on the
outdoor heat exchanger.
How to obtain the cooling and heating capacity
Example : The net cooling capacity of the model SRK40HC-S with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C
and outdoor dry-bulb temperature 35˚C is Net cooling capacity = 3600 ✕0.975 ✕1.0 =3510 w
SRK40HC-S Length 15m Factor by air
temperatures
15
ISO-T1 Standard ConditionOutdoor air W.B. temperature °C W.B.
010-10 -5 5
14 16 18 20 22
15
10
27
25
20
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
20
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Heating
Cooling
Applicable range
Coefficient of cooling &
Heating capacity in
relation to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Heating operation
Indoor air D.B.
temperature
°C D.B.
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
Air inlet temperature of
outdoor unit in ˚CWB
Adjustment coefficient
-10
0.95
-9
0.94
-7
0.93
-5
0.91
-3
0.88
-1
0.86
1
0.87
3
0.92
5
1.00

-
9
-
3 ELECTRICAL DATA
3.1 Electrical wiring
Models SRK20HC-S, 28HC-S, 40HC-S
Power source
1 Phase
220/230/240V 50Hz
Outdoor unit
Indoor unit
LB
CNW
CF
I
WH
HEAT
EXCHANGER
CNM
CNU
CNC
Tr
F
(i250V 3.15A)
52C-3
52C
52C
Printed circuit
board
Printed circuit
board
1
1
1
5
3
3
52X1
CFO
52X2
52X3
52X3
52X2
52X1
52C-4
N
ZNR
IC8
3
5
1
WH
2/N
3
Y/GN
FM
FM
I
FMo
CM
20S
EEV
LB
BR
BK
RD
Y/GN
RD
WH
BR
TB TB
RD
J
Y/GN
G
LNJ
F
(250V 3.15A)
ZNR
BK
BK
25
1C
3
1
CM1
CM2
WH
WH
WH
CC
RD
RD
Y/GN
G1
D.S
BR
BL
CNB
CNE CNG
Th1 Th2
CNG
Th4
Th5
Th6
CNE
CNB
CNU
Display
Wireless
R-Amp
1
2
3
Black
Brown
Red
Light blue
White
Yellow/Green
BK
BR
RD
LB
WH
Y/GN
Color symbol
Meaning of marks
Symbol Parts name
CF
I
Capacitor for FM
I
CM Compressor motor
FFuse
FM
I
Fan motor (Indoor)
FMo Fan motor (Outdoor)
FM Flap motor
Symbol Parts name
Th
1
Room temp. thermistor
Th
2
Heat exchanger thermistor (Indoor unit)
Th
4
Heat exchanger thermistor (Outdoor unit)
Th
5
Outdoor air temp. thermistor
Th
6
Discharge temp. thermistor
Tr Transformer
Symbol Parts name
ZNR Varistor
20S 4 way valve (coil)
52C Magnetic contactor
DS Diode stack
52X
1-3
Auxiliary relay
EEV Electronic expansion valve
51C Motor Protector for CM

-
10
-
LO
MID
HI
AUTO
HI POWER
ECONO
ON OFF
AM PM
HI POWER
TEMP
ECONO
AIR FLOW
CANCEL
ON OFF
RESERVE
TIMER
TIME
ACL
FAN SPEED
ON
MODE
LO
MID
HI
AUTO
TIME
OFF
HI POWER
ECONO
ON OFF
AM PM
FAN SPEED button
Each time the button is pushed, the indi-
cator is switched over in turn.
•The above illustration shows all controls, but in practice
only the relevant parts are shown.
OPERATION MODE select button
Each time the button is pushed, the indi-
cator is switched over in turn.
AIR FLOW button
This button changes the flap mode. When
pressed, this button changes the mode in the
following order:
ON/OFF button
Press for starting operation, press again for
stopping.
HI POWER button
This button changes the HI POWER mode.
ECONOMY button
This button changes the ECONOMY mode.
RESET switch
Switch for resetting microcomputer.
ON TIMER button
This button selects ON TIMER operation.
Clock switch
This switch for setting the clock.
OFF TIMER button
This button selects OFF TIMER operation.
TEMPERATURE button
This button sets the room temperature.
(This button changes the present time and
TIMER time.)
CANCEL button
This button cancels the ON timer and OFF
timer.
RESERVE button
This button sets the present time and
TIMER time.
SIndication section
OPERATION MODE Indicator
Indicates selected operation with lamp.
[ (Auto) •(Cool) •(Heat) •(Dry)]
TEMPERATURE Indicator
Indicates set temperature.
(Does not indicate temperature when operation
mode is on AUTO)
FAN SPEED Indicator
Indicates set air flow rate with lamp.
AIR FLOW Indicator
Shows selected flap mode.
HI POWER MODE indicator
Indicates during Hi power mode operation.
ECONOMY MODE indicator
Indicates during economy mode operation.
ON TIMER Indicator
Indicates during ON TIMER operation.
Clock Indicator
Indicates present time or timer setting time.
OFF TIMER Indicator
Indicates during OFF TIMER operation.
Models All models
Remote controller
SOperation section
(Air scroll) (SWING)
4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
4.1 Operation control function by remote control switch

-
11
-
Unit indication section
Models All models
4.2 Back-up switch
When the remote controller batteries become weak, or if the remote controller is lost or malfunctioning, this switch may be used to turn
the unit on and off.
(a) Operation
Push the switch once to place the unit in the automatic mode. Push it once more to turn the unit off.
(b) Details of operation
The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by sensor),
whether to go into the cooling, thermal dry or heating modes.
Function Room temperature
Operation mode
setting Fan speed Flap Timer switch
Cooling About 26ºC
Thermal dry About 25ºC Auto Auto Continuous
Heating About 25ºC
4.3 Power-cut compensation
(1) Power-cut compensation is a function that records the operational status of the air-conditioner immediately prior to it being
switched off by a power cut, and then automatically resumes operations at that point after the power has been restored.
(2) The following settings will be cancelled:
(a) Timer settings
(b) High-power operations
Notes (1) The power-cut compensation function is set at on when the air-conditioner is shipped from the factory.
Consult with your dealer if this function needs to be switched off.
(2) If the power-cut compensation function is set at on, ensure that the power switch is turned off after operations
have been halted.
(If the power switched is turned off while the air-conditioner is still operating, the fan in the indoor unit will
start operating in the same way as when the switch is turned on. The indoor unit will commence operations
approximately three minutes after the power has been switched on.)
(3) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reser the timer.
(4)
If the jumper wire (J7) “REMOTE/AUTORESTART”is cut, auto restart is disabled. (See the diagram at right)
ON/OFF button
ECONOMY light (orange)
Illuminates during ECONOMY operation.
TIMER light (yellow)
Illuminates during TIMER operation.
HI POWER light (green)
Illuminates during HI POWER operation.
RUN (HOT KEEP) light (green)
•Illuminates during operation.
•Flashes at air flow stop due to the ‘HOT KEEP’.
RUN
TIMER
HIPOWER
ECONO

-
12
-
4.4 Flap control
Control the flap by AIRFLOW button on the wireless remote controller.
(1) Air scroll
The flap will be automatically set to the angle of air flow best to operation.
(a) Starting time of operation
(b) When not operating
The flap returns to the position of air flow directly below, when operation has stopped.
(2) Memory flap
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is started.
¡Recommendable stopping angle of the flap
(3) Swing flap
Flap moves in upward and downward directions continuously.
sDuring cooling andt
dry operation
Thick line : Rapid movement
Thin line : Slow movement
Stops for approximately
5 seconds in the
horizontal position.
sDuring heating t
operation
Stops for approximately
5 seconds in this
position. Thick line : Rapid movement
Thin line : Slow movement
Horizontal
blowing
COOL•DRY
Slant forward
blowing
HEAT
Corrects the starting time of next operation by
calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time Setting time
15 min. 10 min. 5 min.
earlier earlier earlier
¡If the difference (= Setting temperature – Room tempera-
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. earlier + 5 min. = 20 min. earlier
↑↑
Current operation Correction value
start time
4.5 Comfort timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation
is selected, the comfort timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the
relationship between the room temperature at the setting time (temperature of room temperature thermistor) and the setting temperature.
(Max. 60 minutes)
Operation mode Operation start time correction value (Min.)
3 < Room temp. – Setting temp. 1 < Room temp. – Setting temp. ≤3 Room temp. – Setting temp. ≤1
At cooling +5 No change –5
3 < Setting temp. – Room temp. 2 < Setting temp. – Room temp. ≤3 Setting temp. – Room temp. ≤2
At heating +5 No change –5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature thermistor (Th1).
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
=
=
=
=

-
13
-
4.6 Outline of heating operation
(1) Operation of major functinal components
(2) Fan speed switching
(a) Auto fan control
The indoor fan is automatically controlled in accordance with the difference between the room temperature (detected by the
room temperature thermistor) and the thermostat setting as shown below.
(3) Thermostat operation
The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
(4) Hot keep
This function controls the indoor unit fan speed as shown below in accordance with the temperature sensed by the indoor heat
exchanger thermistor.
(a) When the compressor and outdoor unit fan are operating
Indoor fan motor
Flaps
Display
52C
Outdoor fan motor
ON
ON or OFF
Lights up
ON
OFF
ON
ON or OFF
Lights up
ON
ON
OFF
Stop position control
Lights up or flashes
OFF after stop mode
OFF
4-way valve Depending on the stop mode ON Depending on the stop mode
When the compressor
command is OFF
When the compressor
command is ON
When the compressor goes
OFF due to an abnormal stop.
Functional
components
Item
Air scroll
Swing flap
Swing stop
Auto fan control
Speed 6
Speed 6
Speed 6
Speed 4
Speed 4
Speed 4
AUTO HIGH MED
Speed 2
Speed 2
Speed 2
LOW
Flow control
Fan speed switching
Speed 6
Speed 4
Speed 2
Thermostat setting point
䊱
-5 -4 -3 -2 -1 0
OFF
ON
Set temp.
Compressor
outdoor fan
+1
Room temp.
Speed 6
Speed 4
Speed 2
Speed 1
OFF
34
40
43
30
34
37
25
30
30
20
25
25
15
15
20
Model : 20
Model : 28
Model : 40
Auto fan control,
or the set fan speed
Indoor heat exchanger temp. (˚C)

-
14
-
(c) To accomplish rapid recovery from the thermostat off state, after the compressor and outdoor unit’s fan go OFF, the set
temperature is raised by 1ºC until 1 minute passes after the hot keep end temperature has been reached following restarting.
(5) Hot Spurt
(a) For 40 minutes after a heating operation begins, the system runs with set temperature raised by 2ºC.
(b) In the following cases, this function is canceled and does not activate afterwards.
1) When the compressor and outdoor unit fan have been turned OFF by the thermostat going off.
2) During high pressure control operation.
(6) High Power Operation (“HI POWER” button on the remote controller : ON)
The system runs under the following conditions for 15 minutes without relation to the set temperature or the fan speed setting.
(7) Defrost Operation
(a) Starting conditions (Defrost operation begins when all the following conditions are satisfied.)
140 minutes have passed since the heating operation began. (Accumulated operation time)
240 minutes have passed since the previous defrosting operation ended. (Accumulated operation time)
3The outdoor unit heat exchanger thermistor temperature is –5ºC or lower continuously for 3 minutes.
4The difference between the outdoor temperature thermistor temperature and the outdoor heat exchange thermistor tem-
perature is 4.5ºC.
5The compressor is running.
Also, the number of times the compressor goes OFF is counted, and when it reaches 10 or more times, if the conditions
in 1, 2and 3above (except that the outdoor heat exchanger thermistor temperature is –1ºC), the defroster operation
starts.
(b) End conditions (when either of the following conditions is satisfied)
1Outdoor heat exchanger thermistor temperature: 9ºC or higher
2Defrosting operation has continued for 10 minutes.
Notes (1) Room temperature is not adjusted during the HI POWER operation.
(2) Protective function will actuate withe priority even during the HI POWER operation.
Speed 6
Speed 4
Speed 2Speed 2
OFF
34
40
43
30
34
37
25
30
30
Model : 20
Model : 28
Model : 40
Auto fan control,
or the set fan speed
Indoor unit fan
Outdoor unit fan
Compressor
Speed 6 fixed
ON
ON
(b) When the compressor and outdoor fan are stopped
1) While the compressor operation is delayed. 2) Up until 5 minutes have passed
since the end of a compressor
start delay operation, when 52C
goes OFF, the indoor unit’s fan
speed changes forcibly from
OFF to speed 1.
Indoor heat exchanger temp. (˚C)

-
15
-
(c) Operation of functinal components during defrosting operation
(8) Forced Defrost
During trial operation, if defrost operation is performed, defrost operation can be performed only once time, in accordance with the
following operation.
1) Remote control operation
(b) If remote control operation is performed, for 1 minute after 3-minute timer operation, the operation is canceled if one of the
following conditions is satisfied.
1Outdoor heat exchanger liquid pipe thermistor temperature: 14ºC or higher
210 minutes has passed (including the 1 minute of forced operation).
(9) ECONO operation ( “ECONO” button on the remote controller : ON)
The set temperature changes as shown at right and the
indoor unit fan runs at speed 3.
OFF
Compressor command
Indoor unit fan
Operating lamp
Flashes
Outdoor unit fan
4-way valve
Defrost start operation
Hot keep
Defrost operation Operation after defrost is ended.
Normal heating operation
(defrost recovery)
Controlled by the indoor heat
exchanger temperature
The chart at left is for reference.
Hot keep control governs operation
during heating.
Hot keep
Recovery
temperature
(9ºC)
OFF
OFF
OFF
ON
ON
Lit
ON
ON
120 sec. 120 sec.
Operation
Operation mode
Set temperature
Fan speed select
Air flow setting
On timer
Current time
On timer time
Run
Heating
19˚C
Low
Swing
ON
On after 180 min.condition
Compressor
4-way valve
Indoor unit fan
Flap
Outdoor unit fan
Display
ON
OFF
OFF
Fully closed
OFF
Same as defrost
2) Functional components operation
Running time
Running start ~ 1 hour
1~2 hours
2 hours ~
Set temperature compensation
Set temperature -1.0
Set temperature -2.0
Set temperature -2.5

-
16
-
4.7 Outline of cooling operation
(1) Operation of major fanctinal components
(2) Fan speed switching
(a) Auto fan control
The indoor fan is automatically controlled in accordance with the difference between the room temperature (detected by the
room temperature thermistor) and the termostat setting as shown below.
(3) Thermostat operation
The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
(4) High Power operation ( “HI POWER” button on the remote controller : ON)
The following operation is performed for 15 minutes without relation to the set temperature or fan speed setting.
(5) ECONO Operation ( “ECONO” button on the remote controller : ON)
The set temperature changes as shown at right, and the
indoor unit fan speed is set on speed 1.
Notes (1) Room temperature is not adjusted during the HI POWER operation.
(2) Protective functions will actuate with priority even during the HI POWER operation.
Indoor fan motor
Flaps
Display
52C
Outdoor fan motor
ON
ON or OFF
Lights up
ON
OFF
ON
ON or OFF
Lights up
ON
ON
OFF
Stop position control
Lights up or flashes
OFF after stop mode
OFF
4-way valve Depending on the stop mode OFF Depending on the stop mode
When the compressor
command is OFF
When the compressor
command is ON
When the compressor goes
OFF due to an abnormal stop.
Functional
components
Item
Air scroll
Swing flap
Swing stop
Auto fan control
Speed 5
Speed 5
Speed 5
Speed 3
Speed 3
Speed 3
AUTO HIGH MED
Speed 2
Speed 2
Speed 2
LOW
Flow control
Fan speed switching
Speed 4
Speed 3
Speed 2
Thermostat setting point
Speed 5
䊱+1 +2 +3 +4
OFF
ON
Set temp.
-1
Room temp.
Compressor
outdoor fan
䊱
Indoor unit fan
Outdoor unit fan
Compressor
Speed 6 fixed
ON
ON
Running time
Running start ~ 1 hour
1~2 hours
2 hours ~
Set temperature compensation
Set temperature +0.5
Set temperature +1.0
Set temperature +1.5

-
17
-
Note (1) Thermostat operation is performed in A, B Block. When compressor and indoor fan stop by thermostat operation within 12 minutes from start, temperature
check is performed by operating indoor fan at speed 1 for 20 seconds before finishing 12 minutes and allowing decision of next operation block.
(3) DRY operation
After finishing start up operation described in (b) above, thermal dry operation is performed at 8 minutes intervals, according to the
difference between room temperature and thermostat setting temperature as shown below.
Beside, 1 cycle of this operating time consists of 8 minutes, 7 cycle operation is performed then.
D Block C Block B Block A Block
4.8 Outline of dehumidifying operation
(1) Choose the appropriate operation block area by the difference between room temperature and thermostat
setting temperature as shown below.
¡Operation block area
–20 +3
Room temp. –Setting temp.(deg)
(2) Start up operation
ON
OFF
OFF
036912
ON
OFF
OFF
012
Compressor
and
outdoor fan
Set fan speed
Indoor fan
Start Temperature check Start Temperature check
Compressor
and
outdoor fan
Set fan speed
Indoor fan
Operation block decision
C.D Block A.B Block
minutes
minutes
Speed 1Speed 1 20
seconds
ON
OFF
OFF
048
ON
OFF
OFF
08
Compressor
and
outdoor fan
Indoor fan
D Block
Compressor
and
outdoor fan
Indoor fan
C Block
Compressor
and
outdoor fan
Indoor fan
B Block
Compressor
and
outdoor fan
Indoor fan
A Block
20 seconds 20 seconds
minutes
minutes
Start Temperature check Start Temperature check
Operation block decision
20 seconds
minutes
minutes
Start Temperature check Temperature check
Operation block decision
Start
Speed 1
Speed 1
OFF
OFF
08
ON
OFF
OFF
038
Speed 1
Speed 1
Running time
Running start ~ 1 hour
1~2 hours
2 hours ~
Set temperature compensation
Set temperature +0.5
Set temperature +1.0
Set temperature +1.5
(4) ECONO Operation ( “ECONO”button on the remote controlle : ON)
The set temperature changes as shown at right, and the
indoor unit fan speed is set on speed 1.

-
18
-
4.9 Automatic operation
(1) Determination of operation mode
The blow operation of the indoor fan is carried out at the 1st speed for 20 seconds and the room temperature is checked to
determine the operation mode automatically. (When the unit is operated by the turn-on timer, the blow operation is not carried out.)
Room temperature
Operation mode
Room temp.<21˚C21˚C Room temp.<26˚C
<
=
26˚C Room temp.
Heating Dry Cooling
<
=
(2) Within 30 minutes after either auto or manual operation stops, if auto operation is started, or if you switch to auto operation during
manual operation, the system runs in the previous operation mode.
(3) The temperature is checked 1 time in 30 minutes after the start of operation, and if the judgment differs from the previous operation
mode, the operation mode changes.
(4) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote controller and the setting temperature.
Signals of wireless remote controller (Display)
–6–5–4–3–2–1±0+1+2+3+4+5+6
Setting Cooling 19 20 21 22 23 24 25 26 27 28 29 30 31
temperature Dehumidifying 19 20 21 22 23 24 25 26 27 28 29 30 31
Heating 20 21 22 23 24 25 26 27 28 29 30 31 32
4.10 Protective control function
(1) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(a) Operating conditions
(i) Indoor heat exchanger temperature (detected with Th2) is lower than 2.5ºC.
(ii) 3 minutes elapsed after the start of operation.
(b) Detail of anti-frost operation
Compressor OFF
Indoor fan 1st speed
Outdoor fan OFF
4-way valve Stop mode
(c) Reset conditions: Indoor heat exchanger temperature (Th2) is higher than 8ºC.
(2) Indoor fan motor protection
When the air conditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 rpm or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
Timer lamp illuminates simultaneously and the operation lamp flashing 6 times at each 8-second.
(3) Dew condensation prevention control for cooling operation
This prevents dew condensation, in the indoor unit, from occurring.
(a) Operating condition: when compressor is kept ON for 30 min. after the unit starts operation.
(b) Operation content: forces the indoor fan to change from Speed 1 to Speed 2.
(c) Resetting condition: When compressor is off, or when dew condensation prevention control has been operating continu-
ously for 30 minutes.
(4) Three-minute forced operation
When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as is in the
operation mode. (After 3 minutes has passed the thermal operation is effective.)
However, stopping the compressor via a stop signal or protection control has priority.
This manual suits for next models