Check Code Abnormal point and detection method Case Judgment and action
E0
or
E4
Remote controller transmission error
(E0)/signal receiving error (E4)
1Abnormal if main or sub remote
controller cannot receive any
transmission normally from Interface
unit/Flowtemp.controllerofrefrigerant
address“0”for3minutes.
(Checkcode:E0)
2Abnormal if sub-remote controller could
notreceiveanysignalfor2minutes.
(Checkcode:E0)
1
AbnormalifInterface/Flowtemp.
controller board cannot receive any
data normally from remote controller
boardorfromotherInterface/Flowtemp.
controllerboardfor3minutes.(Check
code:E4)
2
Interface/Flowtemp.controllerboard
cannotreceiveanysignalfromremote
controllerfor2minutes.(Checkcode:
E4)
1Contactfailureattransmission
wireofremotecontroller
2All remote controllers are set
as“sub”remotecontroller.
Inthiscase,E0isdisplayed
on remote controller, and E4
isdisplayedatLED(LED1,
LED2)ontheoutdoorcontrol-
ler circuit board.
3Miswiringofremotecontroller
4Defectivetransmittingreceiv-
ingcircuitofremotecontroller
5Noise has entered into the
transmissionwireofremote
controller.
1Checkdisconnectionorloosenessof
Interfaceunit/Flowtemp.controllerunitor
transmissionwireofremotecontroller.
2Setoneoftheremotecontrollers“main”,If
thereisnoproblemwiththeactionabove.
3Checkwiringofremotecontroller.
•Totalwiringlength:max.500m
(Donotusecable×3ormore.)
•Thenumberofconnectingremotecontroller
(Refertotheindoorunit'sInstallationManual.)
If the cause of trouble is not in 1–3 above,
4Diagnoseremotecontrollers.
a)When“RCOK”isdisplayed,remote
controllers have no problem.
Turnthepoweroff,andonagaintocheck.
Ifabnormalitygeneratesagain,replace
Interface/Flowtemp.controllerboard.
b)When“RCNG”isdisplayed,replaceremote
controller.
c)When“RCE3”or“ERC00–66”isdisplayed,
noisemaybecausingabnormality.
E1
or
E2
Remote controller control board
1Abnormal if data cannot be read nor-
mally from the nonvolatile memory of
the remote controller control board.
(Checkcode:E1)
2Abnormal if the clock function of remote
controller cannot be operated normally.
(Checkcode:E2)
1Defectiveremotecontroller 1Replace remote controller.
E3
or
E5
Remote controller transmission error
(E3)/signal receiving error (E5)
1
Abnormal if remote controller could not
findblankoftransmissionpathfor6sec-
onds and could not transmit.
(
Check
code:E3)
2
When remote controller receives the
transmitted data same time and com-
pares these data. Abnormal if the data is
judgedtobedifferentfor30continuous
times.(
Check
code:E3)
1
AbnormalifInterface/Flowtemp.control-
ler board could not find blank of transmis-
sion path.(
Check
code:E5)
2
WhenInterface/Flowtemp.controller
receives the transmitted data same time
and compares these data. Abnormal if
thedataisjudgedtobedifferentfor30
continuoustimes.(
Check
code:E5)
1Refertotheindoorunit's
Installation Manual for remote
controller connection.
2Defectivetransmittingreceiv-
ingcircuitofremotecontroller
3Defectivetransmittingreceiv-
ingcircuitofInterface/Flow
temp. controller board
4Noise has entered into trans-
missionwireofremotecon-
troller.
1Refertotheindoorunit'sInstallationManual
for remote controller connection.
2–4Diagnoseremotecontroller.
a)When“RCOK”isdisplayed,remote
controllers have no problem.
Turnthepoweroff,andonagainto
check.
Whenbecomingabnormalagain,
replace indoor controller board.
b)When“RCNG”isdisplayed,replace
remote controller.
c)When“RCE3”or“ERC00–66”isdis-
played,noisemaybecausingabnor-
mality.
E6
Interface unit/Flow temp. controller-out-
door unit communication error (Signal
receiving error)
1AbnormalifInterface/Flowtemp.
controller board cannot receive any
signalnormallyfor6minutesafter
turningthepoweron.
2AbnormalifInterface/Flowtemp.
controller board cannot receive any
signalnormallyfor3minutes.
1
Contactfailure,shortcircuitor,
miswiring(conversewiring)of
Interfaceunit/Flowtemp.con-
troller-outdoorunitconnecting
wire
2Defectivetransmittingreceiving
circuitofInterface/Flowtemp.
controller board
3Defectivetransmittingreceiv-
ingcircuitofInterface/Flow
temp. controller board
4
Noise has entered into Interface
unit/Flowtemp.controller-
outdoorunitconnectingwire.
Note:CheckLEDdisplayontheoutdoor
controllercircuitboard.(Connect
A-controlservicetool,PAC-SK52ST.)
1Checkdisconnectionorloosenessof
Interfaceunit/Flowtemp.controller-outdoor
unitconnectingwireofInterfaceunit/Flow
temp. controller or outdoor unit.
2–4Turnthepoweroff,andonagainto
check.Ifabnormalitygeneratesagain,
replaceInterface/Flowtemp.controller
board or outdoor controller circuit board.