20
Check code
Abnormal point and detection method
Judgment and action
Case
E0
or
E4
Remote controller transmission error
(E0)/signal receiving error (E4)
Abnormal if main or sub remote controller
cannot receive any transmission
normally from Interface unit/Flow temp.
controller of refrigerant address “0” for 3
minutes.
(Check code: E0)
Abnormal if sub-remote controller could
not receive any signal for 2 minutes.
(Check code: E0)
Abnormal if Interface/Flow temp.
controller board can not receive any
data normally from remote controller
board or from other Interface/Flow temp.
controller board for 3 minutes.
(Check code: E4)
Interface/Flow temp. controller board
cannot receive any signal from remote
controller for 2 minutes.
(Check code: E4)
Check disconnection or looseness of
Interface unit/Flow temp. controller unit or
transmission wire of remote controller.
Set one of the remote controllers “main”, If
there is no problem with the action above.
Check wiring of remote controller.
• Total wiring length: max. 500 m
(Do not use cable × 3 or more.)
•
The number of connecting remote controller
:
Refer to the indoor units service manual.
When it is not the above-mentioned problem of
~
Diagnose remote controllers.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
Interface/Flow temp. controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
Contact failure at transmission
wire of remote controller
All remote controllers are set
as “sub” remote controller. In
this case, E0 is displayed on
remote controller, and E4 is
displayed at LED (LED1, LED2)
on the outdoor controller circuit
board.
Miswiring of remote controller
Defective transmitting receiving
circuit of remote controller
Noise has entered into the
transmission wire of remote
controller.
E1
or
E2
Remote controller control board
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Check code: E1)
Abnormal if the clock function of remote
controller cannot be operated normally.
(Check code: E2)
Defective remote controller Replace remote controller.
Remote controller transmission error
(E3)/signal receiving error (E5)
1
Abnormal if remote controller could not find
blank of transmission path for 6 seconds
and could not transmit.
(Check code: E3)
2
When remote controller receives the
transmitted data same time and compares
these data. Abnormal if the data is judged
to be different for 30 continuous times.
(Check code: E3)
1
Abnormal if Interface/Flow temp. controller
board could not find blank of transmission
path. (Check code: E5)
2
When Interface/Flow temp. controller
receives the transmitted data same time
and compares these data. Abnormal if the
data is judged to be different for 30 con-
tinuous times. (Check code: E5)
1Set a remote controller to main, and the
other to sub.
2~4Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is dis-
played, noise may be causing abnormal-
ity.
12 remote controllers are set as
“main.”
(In case of 2 remote controllers)
Note that some models can
only connect 1 remote control-
ler. For more detail, refer to the
indoor unit's service manual.
2Defective transmitting receiving
circuit of remote controller
3Defective transmitting receiving
circuit of Interface/Flow temp.
controller board
4Noise has entered into trans-
mission wire of remote control-
ler.
E3
or
E5
E6
Interface unit/Flow temp. controller-out-
door unit communication error (Signal
receiving error)
1Abnormal if Interface/Flow temp.
controller board cannot receive any
signal normally for 6 minutes after turning
the power on.
2Abnormal if Interface/Flow temp.
controller board cannot receive any
signal normally for 3 minutes.
1
Contact failure, short circuit or,
miswiring (converse wiring) of
Interface unit/Flow temp. control-
ler-outdoor unit connecting wire
2Defective transmitting receiving
circuit of Interface/Flow temp.
controller board
3Defective transmitting receiving
circuit of Interface/Flow temp.
controller board
4
Noise has entered into Interface
unit/Flow temp. controller-
outdoor unit connecting wire.
* Check LED display on the outdoor control circuit
board. (Connect A-control service tool, PAC-
SK52ST.)
1Check disconnection or looseness of
Interface unit/Flow temp. controller-outdoor
unit connecting wire of Interface unit/Flow
temp. controller or outdoor unit.
2~4Turn the power off, and on again to check.
If abnormality generates again, replace
Interface/Flow temp. controller board or
outdoor controller circuit board.
E8
Interface unit/Flow temp. controller-
outdoor unit communication error
(Signal receiving error)
(Outdoor unit)
(1) Abnormal if outdoor controller circuit
board could not receive anything
normally for 3 minutes.
1Contact failure of Interface unit/
Flow temp. controller-outdoor
unit connecting wire
2Defective communication circuit
of outdoor controller circuit board
3Defective communication
circuit of Interface/Flow temp.
controller board
4
Noise has entered into Interface
unit/Flow temp. controller-
outdoor unit connecting wire.
1Check disconnection or looseness of
Interface unit/Flow temp. controller-outdoor
unit connecting wire of Interface unit/Flow
temp. controller or outdoor unit.
2~4Turn the power off, and on again to
check. Replace Interface/Flow temp.
controller board or outdoor controller circuit
board if abnormality is displayed again.