20
Check Code Abnormal points and detection method
Judgment and action
U1
(1302)
High pressure (High-pressure switch
63H operated)
Abnormalifhigh-pressureswitch63H
(4.15MPa)operatedduringcompressor
operation.
1Decreasedwaterflow
2Cloggedfilterofwaterpipe
3Lockedwaterpump
4Malfunctionofwaterpump
5Dirtofindoorheatexchanger
6Defectiveoperationofstop
valve(Notfullopen)
7Cloggedorbrokenpipe
8Lockedoutdoorfanmotor
9
Malfunctionofoutdoorfanmotor
0Shortcycleofoutdoorunit
1Dirtofoutdoorheatexchanger
2Decreasedairflowcausedby
defectiveinspectionofoutside
temperaturethermistor
(Itdetectslowertemperature
thanactualtemperature.)
3Disconnectionorcontactfailure
ofconnector(63H)onoutdoor
controllerboard
4Disconnectionorcontactfailure
of63Hconnection
5
Defectiveoutdoorcontrollerboard
6Defectiveactionoflinear
expansionvalve
7Malfunctionoffandrivingcircuit
1−5Checkwatercircuitandrepairdefect.
6Checkifstopvalveisfullyopen.
7Checkpipingandrepairdefect.
8−1Checkoutdoorunitandrepairdefect.
2Checkthedetectedtemperatureofoutside
temperaturethermistoronLEDdisplay.
(SW2onA-ControlServiceTool:Refer
to "10-7.FUNCTIONOFSWITCHES,
CONNECTORSANDJUMPERS".)
3−5TurnthepoweroffandcheckifF5is
displayedwhenthepoweristurnedon
again.
WhenF5isdisplayed,referto“Judgment
andaction”forF5.
6Checklinearexpansionvalve.
Referto"10-4.HOWTOCHECKTHEPARTS"
.
7Replaceoutdoorcontrollerboard.
Case
U2
(TH32:1132)
High comp. surface temperature
(1)
Abnormalifcomp.surfacethermistor(TH32)
exceeds125°C or115°Ccontinuouslyfor
5minutes.
Abnormalifcomp.surfacethermistor(TH32)
exceeds110°Cormorecontinuouslyfor
30secondsafter90secondshavepassed
sincethedefrostingoperationstarted.
(2)Abnormalifdischargesuperheat
(Cooling:TH32−T63HS
Heating:TH32−T63HS )increases.
AlltheconditionsinAorBaredetected
simultaneouslyfor10minutescontinu-
ouslyafter6minutespastfromcompres-
sorstart-up(includingthethermostat
indicationorrecoveryfromdefrosting).
<ConditionA>
•Heatingmode
•Whendischargesuperheatislessthan
70
°C
.
•WhentheTH6tempismorethanthe
valueobtainedbyTH7−5:.
•WhenthecondensingtempofTH5is
lessthan35:.
<ConditionB>
•Duringcompressoroperation(Cooling
andHeating)
•Whendischargesuperheatislessthan
80
°C
inCooling.
•Whendischargesuperheatislessthan
90
°C
inHeating.
•WhencondensingtempofTH6is
morethan−40:.(InCoolingonly.)
1Overheatedcompressor
operationcausedbyshortage
ofrefrigerant
2Defectiveoperationofstop
valve
3Defectivethermistor
4Defectiveoutdoorcontroller
board
5Defectiveactionoflinear
expansionvalve
1Checkintakesuperheat.
Checkleakageofrefrigerant.
Chargeadditionalrefrigerant.
2Checkifstopvalveisfullyopen.
34TurnthepoweroffandcheckifU3is
displayedwhenthepowerisonagain.
WhenU3isdisplayed,referto“Judgement
andaction”forU3.
5Checklinearexpansionvalve.
Referto"10-4.HOWTOCHECKTHE
PARTS".
<Abnormalities detected while unit is operating>
U3
(TH32:5132)
Open/short circuit of comp. surface
thermistor (TH32)
Abnormalifopen(−20°Corless)or
short(217°Cormore)isdetectedduring
compressoroperation.
(Detectionisinoperativefor10minutes
ofcompressorstartingprocessandfor10
minutesafterandduringdefrosting.)
1Disconnectionorcontactfailure
ofconnector(TH32)onthe
outdoorcontrollercircuitboard
2Defectivethermistor
3Defectiveoutdoorcontroller
circuitboard
1
Checkconnectionofconnector(TH32)onthe
outdoorcontrollercircuitboard.Checkbreaking
oftheleadwireforthermistor
TH32).Referto
"10-6.TESTPOINTDIAGRAM".
2
Checkresistancevalueofthermistor(TH32)
ortemperaturebymicroprocessor.(Thermistor/
TH32:Referto"10-4.HOWTOCHECKTHE
PARTS".)(SW2onA-ControlServiceTool:
Referto"10-7.FUNCTIONOFSWITCHES,
CONNECTORSANDJUMPERS".)
3Replaceoutdoorcontrollerboard.