675-511.13
7. Reinstall the burner assembly making certain that the
retaining pins (and clips) are replaced and the burner is
correctly positioned.
8. For codes 11 or 12 or if digit 11 of model number is S and
digit 12 is 1, reconnect the pilot gas tube and thermocouple
at the combination gas control. For codes 30 or 31 or if
digit 11 of model number is N and digit 12 is 1, reconnect
the pilot gas tube at the combination gas control and the
ignition cable(s) at the ignition control.
9. Modify the combination gas control regulator to use
propane gas. Follow the instructions in the regulator kit
to convert the combination gas control. Some conversion
kits will have more than one regulator kit and they are
specific to the manufacturer of the combination gas control
(i.e. Honeywell, Robertshaw, etc.). Check the conversion
kit Parts List, Table 5.1, 5.2, or 5.3, for application of the
correct regulator kit. A second check can be made by
finding the model number on the combination gas control
and matching it with the correct kit. Do not attempt to
substitute one regulator kit for another.
10. Affix the propane conversion label to the combination gas
control. This label is supplied with the regulator conversion
kit (see Figure 6.2).
11. Affix the conversion Rating Plate adjacent to the unit's
original rating plate (see Figure 6.3). Be sure that all blanks
on the label are completely filled in (date of conversion,
kit number, and organization/individual performing the
conversion).
12. Remove the natural gas designation disc(s) and replace
with the propane gas designation disc(s) included with the
conversion kit (see Figure 7.1). Note that some units may
use several discs.
13. Turn on the gas supply to the unit.
14. Check the line pressure of the gas supply upstream of
the combination gas control either with a water column
manometer or with a gauge with water column scale. The
supply pressure should be no less than 12 in. w.c. and no
more than 14 in. w.c.
15. Connect the manometer or (gauge) to the outlet pressure
tap designated on the combination gas control.
16. Restore electric supply to unit.
17. Light unit following instructions on unit rating plate. Turn
up thermostat setting to call for heat. After the main
burners light, measure the outlet (manifold) pressure of
the combination gas control. The outlet pressure should
be 10 in. w.c. The outlet pressure can be adjusted at the
combination gas control's regulator. Turning the adjustment
clockwise will increase the outlet pressure while turning it
counterclockwise will decrease the pressure.
18. Verify normal operating sequence of ignition system
according to the Installation & Service Manual.
19. Check for leaks at all joints and connections in the gas
lines. This is most easily done with a soap/water solution.
Simply brush or spray some of the solution on a joint or
connection and look for bubble formation.
20. Observe the main burner flame. The flame should have a
well-defined conical shape with the base anchored to the
burner port. If the flame appears to be lifting or rising above
the burner port (see Figure 6.1), loosen the thumb screw
on the air shutter and slide the shutter forward toward the
mixer tube (see Figure 4.4).
21. If a majority of the flame is yellow, move the air shutter
back away from the mixer tube. Slight yellow tips on a
propane flame are common and are not objectionable.
Adjust pilot flame. Follow instructions in Installation and
Service Manual.
Figure 6.1
Lifting Flame
Figure 6.2
Typical Combination Gas Control Conversion Label
Figure 6.3
Conversion Rating Plate
WARNING
MISE EN GARDE
VALVE CONVERTED FOR USE AT
4.2" - 11.0" W.C. IMPROPER OPERATION
COULD RESULT IN DEATH OR
SERIOUS INJURY.
SOUPAPE CONVERTIE POUR USAGE
A COLONNE D'EAU DE 10.6 A 28CM.
UN FONCTIONNEMENT INAPPROPRIE
PEUT PROVOQUER LA MORT OU DES
BLESSURES GRAVES
MODINE MANUFACTURING COMPANY
CONVERSION KIT RATING PLATE
This appliance was converted on
to propane gas with kit no. __________________
by: _______________________________________
__________________________________________
which accepts the responsibility that this
conversion has been properly made. Use
parts supplied by Heating Division of Modine
Manufacturing Company. Conversion to be
performed by a qualified service technician.
Appliance model number and input rating: See
existing rating plate.
Inlet gas pressure: Minimum 12" W.C.
Maximum 14" W.C.
Manifold gas pressure: 10" W.C.
Burner orifice size: # __________ drill
Ce générateur d’air chaud a été converti le
___________ pour fonctionner au gaz propane à
l’aide de l’ensemble n°______________________
par _______________________________________
__________________________________________
(nom et adresse de l’organisme qui a effectué la
conversion), qui accepte l’entière responsabilité
de la conversion.
5H73734A
INSTALLATION