ModMAG M1000 User manual

ModMAG® M1000
Electromagnetic Flow Meter
MAG-UM-00379-EN-07 (March 2020) User Manual

CONTENTS
Safety Precautions and Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Basic Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Protection Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Setup and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remove Device from the Pipeline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RoHs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Measuring Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Rigging, Lifting and Moving Large Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Meter Location, Orientation and Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Temperature Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Meter Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Remote Amplier Outdoor Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Inlet and Outlet Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Meter Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Straight Pipe Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pipe Reducer Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Chemical Injection Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Partially Filled Pipe Situations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Amplier Mounting Conguration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Meter Mount Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Remote Mount Conguration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Submersible Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Protection Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Meter Gaskets and Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Meter/Pipeline Connection Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Meter Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Conductive Pipe Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Pipelines with Cathodic Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Non-Conductive Pipe Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ModMAG® M1000 Electromagnetic Flow Meter
Page ii March 2020MAG-UM-00379-EN-07

Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Opening the M1000 Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Auxiliary Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Remote Version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Signal Cable Specication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Maximum Cable Length at Dierent Fluid Temperatures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Conguring Input/Output (I/O). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
M1000 Main Menu Programming Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Screen Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Function Buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Meter Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Measurement Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Input/Outputs Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Totalizer Reset Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Communication Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Miscellaneous Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Information Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
PIN Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Login Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cleaning the Flow Tube and Electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
General Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Errors and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Repair of Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Replacing Meter Electronics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Connecting an AquaCUE/BEACON Encoder Interface to the M1000 Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Detector Type II Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Detector Type Food Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Detector Type III Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Amplier Type ModMAG M1000 Specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
User Manual
Page iiiMarch 2020 MAG-UM-00379-EN-07

Error Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Size Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ModMAG® M1000 Electromagnetic Flow Meter
Page iv March 2020MAG-UM-00379-EN-07

SAFETY PRECAUTIONS AND INSTRUCTIONS
Some procedures in this manual require special safety considerations. In such cases, the text is emphasized with the
following symbols:
Symbol Explanation
Indicates a hazardous situation, which, if not avoided, will result in death or serious personal injury.
WARNING Indicates a hazardous situation, which, if not avoided, could result in death or serious personal injury.
Indicates a hazardous situation, which , if not avoided, could result in minor or moderate personal
injury or damage to property.
IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED BY
THE EQUIPMENT MAY BE IMPAIRED.
ATTENTION
UTILISER L'ÉQUIPEMENT DE MANIÈRE NON SPÉCIFIÉE PAR LE FABRICANT POURRAIT DIMINUER LA PROTECTION
ASSURÉE PAR L'ÉQUIPEMENT.
Basic Precautions
Before installing or using this product, please read this instruction manual thoroughly. Only qualified personnel should install
and/or repair this product. If a fault appears, contact your distributor.
Installation
Do not place any unit on an unstable surface that may allow it to fall.
Never place the units above a radiator or heating unit.
Route all cabling away from potential hazards.
Isolate from the mains before removing any covers.
Power Connection
Use only the type of power source suitable for electronic equipment. If in doubt, contact your distributor. Make sure that any
power cables are of a sufficiently high current rating. All units must be earthed to eliminate the risk of electric shock. Failure to
properly earth a unit may cause damage to that unit or data stored within it.
Protection Class
The device has protection class IP 67 and needs to be protected against dripping water, oils and other liquids.
Setup and Operation
Adjust only those controls that are covered by the operating instructions. Improper adjustment of other controls may result in
damage, incorrect operation or loss of data.
Safety Precautions and Instructions
Page 5March 2020 MAG-UM-00379-EN-07

Remove Device from the Pipeline
If the device has been operated with toxic, caustic, flammable or water-endangering products, check and make sure, by
rinsing or neutralizing if necessary, that all cavities are free from such dangerous substances before you remove the device.
RoHs
The M1000 meter is RoHs compliant.
SYSTEM DESCRIPTION
The Badger Meter M-Series® Model M1000 electromagnetic flow meter is intended for fluid metering in most industries
including water, wastewater, food and beverage, pharmaceutical and chemical.
The basic components of an electromagnetic flow meter are:
• The detector, which includes the flow tube, isolating liner and measuring electrodes.
• The amplifier, which is the electronic device responsible for the signal processing, flow calculation, display and output
signals.
Amplier
Detector
®
Figure 1: Amplifier and Detector
The construction materials of the wetted parts (liner and electrodes) should be appropriate for the specifications on the
intended type of service. We recommend that you review all of the compatibilities consistent with the specifications.
Each meter is factory tested and calibrated. A calibration certificate is included with each meter.
WARNING
CONSULT THE INSTALLATION INSTRUCTIONS BEFORE DETERMINING THE TEMPERATURE RATING OF THE CABLE.
AVERTISSEMENT
CONSULTEZ LES INSTRUCTIONS D'INSTALLATION AVANT DE DÉTERMINER LES CARACTÉRISTIQUES THERMIQUES
DUCÂBLE.
IMPORTANT
Wire connections must meet or exceed a temperature rating of 176° F (80° C).
Measuring Principle
In accordance with Faraday's induction principle, electric voltage is induced in a conductor moving through a magnetic
field. In electromagnetic flow measurement, the moving conductor is replaced by the flowing fluid. Two opposite measuring
electrodes conduct the induced voltage, which is proportional to flow velocity to the amplifier. Flow volume is calculated
based on pipe diameter.
ModMAG® M1000 Electromagnetic Flow Meter
Page 6 March 2020MAG-UM-00379-EN-07

Nameplate
Look at the device nameplate to be sure that the device is delivered according to your order. Check for the correct supply
voltage printed on the nameplate.
Mod MAG
MAG Detector Head
Serial No.
Size
Max. Temp.
Nom. Pressure
Electrodes
Liner
Detector Factor
Protection Rate
Mod MAG
MAG Detector Head
Model
Power Supply
Protection Rate
Figure 2: Nameplate examples
UNPACKING AND INSPECTION
Follow these guidelines when unpacking the M-Series equipment.
• If a shipping container shows any sign of damage, have the shipper present when you unpack the meter.
• Follow all unpacking, lifting and moving instructions associated with the shipping container.
• Open the container and remove all packing materials. Store the shipping container and packing
materials in the event the unit needs to be shipped for service.
• Verify that the shipment matches the packing list and your order form.
• Inspect the meter for any signs of shipping damage, scratches, or loose or broken parts.
OTE:NIf the unit was damaged in transit, it is your responsibility to request an inspection report from the carrier within 48
hours. You must then file a claim with the carrier and contact Badger Meter for appropriate repairs or replacement.
• All detectors with polytetrafluoroethylene (PTFE) liners are shipped with a liner protector on each end to maintain proper
form of the PTFE material during shipping and storage.
OTE:NDo not remove the liner protectors until you are ready to install.
• Storage: If the meter is to be stored, place it in its original container in a dry, sheltered location. Storage temperature
ranges are: –4…140° F (–20…60° C).
Unpacking and Inspection
Page 7March 2020 MAG-UM-00379-EN-07

Rigging, Lifting and Moving Large Units
WHEN RIGGING, LIFTING OR MOVING LARGE UNITS, FOLLOW THESE GUIDELINES:
ATTENTION
POUR LE GRÉEMENT, DU LEVAGE OU DU DÉPLACEMENT D'UNITÉS DE GRANDE TAILLE, VEUILLEZ SUIVRE CES
INSTRUCTIONS :
• DO NOT lift or move a meter by its amplifier, junction box, detector neck,
orcables.
• Use a crane rigged with soft straps to lift and move meters with flow tubes
that are 2…8 in. (50…200 mm). Place the straps around the detector body,
between the flanges, on each side of the detector.
• Use lifting lugs when lifting meter flow tubes that are 5.91 inches (150 mm) in
diameter or larger.
®
Place straps between flanges.
Figure 3: Rigging Large Units
• Use the sling-rigged method to lift large detectors into a vertical position
while they are still crated. Use this method to position large detectors
vertically into pipelines.
Figure 4: Sling-Rigged Lifting Methods
• Do not lift a detector with a forklift by positioning the detector body on the forks, with the flanges extending beyond the
lift. This could dent the housing or damage the internal coil assemblies.
• Never place forklift forks, rigging chains, straps, slings, hooks or other lifting devices inside or through the detector's flow
tube to hoist the unit. This could damage the isolating liner.
• Do not lift meter with a fork lift on the jacket sheet. This could damage the body.
Do not lift detector with forklift Do not lift or rig lifting devices through detector
Figure 5: Lifting and rigging cautions
ModMAG® M1000 Electromagnetic Flow Meter
Page 8 March 2020MAG-UM-00379-EN-07

METER LOCATION, ORIENTATION AND APPLICATIONS
The M1000 provides two amplifier mounting options: an integral or meter mount option and a junction box/remote option.
Figure 6: Meter mount amplifier Figure 7: Junction box with remote amplifier
Temperature Ranges
TO PREVENT DAMAGE TO THE METER, STRICTLY OBSERVE THE MAXIMUM TEMPERATURE RANGES OF THE AMPLIFIER
AND DETECTOR.
ATTENTION
AFIN D'ÉVITER TOUT DOMMAGE AU COMPTEUR, RESPECTEZ RIGOUREUSEMENT LES PLAGES DE TEMPÉRATURES
MAXIMALES DE L'AMPLIFICATEUR ET DU DÉTECTEUR.
• In regions with extremely high ambient temperatures, it is recommended to protect the amplifier from direct sunlight.
• In cases where fluid temperature exceeds 212° F (100° C), use the remote version.
Amplifier Ambient temperature –4…140° F (–20…60° C)
Detector Fluid temperature
PTFE / PFA –40…302° F (–40…150° C)
Hard rubber 32…176° F (0…80° C)
Soft Rubber 32…176° F (0…80° C)
Meter Location, Orientation and Applications
Page 9March 2020 MAG-UM-00379-EN-07

Meter Location
• Do not install the detector on the suction side of pumps. This could damage the liner (in particular PTFE liners).
• Verify that the pipeline is always filled on the measuring point. If not a correct or accurate measurement is not possible.
• Do not install the detector on the highest point of a pipeline system. Gas accumulation may follow.
• Do not install the detector in downcomer pipes with free outlet.
• Do not install the meter on pipes with extreme pipe vibrations. If pipes are vibrating, secure the piping with
appropriate pipe supports in front of and behind the meter. If vibrations cannot be restrained, mount the amplifier in a
remotelocation.
• Do not install the detector close to pipeline valves, fittings or impediments that can cause flow disturbances.
• Do not install the detector on outlet sides of piston or diaphragm pumps. Pulsating flow can affect meter performance.
• Avoid installing the detector near equipment that produces electrical interference such as electric motors, transformers,
variable frequency and power cables.
• Verify that both ends of the signal cables are securely fastened.
• Place power cables and signal cables in separate conduits.
• Place the meter where there is enough access for installation and maintenance tasks.
Figure 8: Meter location
Remote Amplier Outdoor Location
The amplifier can be installed and operated outdoors. However, it must be protected from the elements as follows:
• The ambient environment/temperature rating for the unit is –4…140° F (–20…60° C).
• If an indoor location is within 150 feet (50 meters) of the detector, consider increasing the cable length and mounting the
amplifier indoors.
• At minimum, create a roof or shield over and/or around the amplifier to protect the LCD display screen from
directsunlight.
• See “Remote Mount Configuration” on page14.
ModMAG® M1000 Electromagnetic Flow Meter
Page 10 March 2020MAG-UM-00379-EN-07

Inlet and Outlet Pipe
Always install the detectors in front of fittings producing turbulences. If this is not possible, plan for distances greater than 3 ×
DN. Distance should be greater than 2 × DN.
Figure 9: Inlet and outlet pipe
Meter Orientation
Mag meters can operate accurately in any pipeline orientation and can measure volumetric flow in forward and
reversedirections.
OTE:NA "Forward Flow" direction arrow is printed on the detector label.
Vertical Placement
Mag meters perform best when placed vertically, with liquid flowing upward
and meter electrodes in a closed, full pipe.
Vertical placement allows the pipe to remain completely full, even in low flow,
low pressure applications, and it prevents solids build-up, sediment deposit and
accumulation on the liner and electrodes.
Figure 10: Vertical placement
Horizontal Placement
M1000 meters are equipped with an Empty Pipe Detection feature.
If an electrode mounted in the pipe is not covered by fluid for five
seconds, the meter will display an Empty Pipe Detection condition.
The meter will send out an error message and stop measuring
flow. When the electrode is again covered with fluid, the error
message disappears and the meter will beginmeasuring.
Electrode
Plane
RIGHT
Electrode
Plane
WRONG
Figure 11: Horizontal placement
When installing the meter on a horizontal pipe, mount the detector to the pipe with the flow-measuring electrode axis in a
horizontal plane (three and nine o’clock). This placement helps prevent solids build-up, sediment deposit and accumulation
on the electrodes.
Meter Location, Orientation and Applications
Page 11March 2020 MAG-UM-00379-EN-07

Straight Pipe Requirements
Sufficient straight-pipe runs are required at the
detector inlet and outlet for optimum meter accuracy
and performance. An equivalent of three diameters of
straight pipe is required on the inlet (upstream) side. Two
diameters are required on the outlet (downstream) side.
FORWARD FLOW
MINIMUM STRAIGHT PIPE MINIMUM STRAIGHT PIPE
ELBOW
TEE
GATE VALVE
(FULLY OPEN)
MINIMUM STRAIGHT PIPE
CHECK VALVE
GLOBE VALVE
BUTTERFL
Y VALVE
PUMP
ELBOW
TEE
ANY VAL
VE
FLOWMETER
3 x D
7 x D
2 x D
D (Pipe Size)D (Pipe Size)
MINIMUM PIPING REQUIREMENT
STANDARD CONCENTRIC
REDUCERS
(NO DISTANCE REQUIRED)
Figure 12: Straight pipe requirements
Pipe Reducer Requirements
With pipe reducers, a smaller meter can be mounted in larger pipelines. This
arrangement may increase low-flow accuracy.
There are no special requirements for standard, concentric pipe reducers.
Custom fabricated pipe reducers must have an approximate slope angle of
8degrees to minimize flow disturbances and excessive loss of head. If this is not
possible, install the custom pipe reducers as if they were fittings and install the
required amount of straight pipe.
Figure 13: Pipe reducer requirements
You can determine the occurring pressure drop by using the shown nomogram
(only applicable to liquids with similar viscosity like water).
OTE:NIn cases where flow velocities are very low, you can increment them by
reducing the size on the measuring point and hence obtain a better
measuring accuracy.
Define pressure loss:
1. Calculate diameter ratio d/D.
2. Read pressure loss depending on d/D ratio and ow velocity.
Diameter Ratio d/D
Pressure Drop in mbar
Figure 14: Pressure drop nomogram
ModMAG® M1000 Electromagnetic Flow Meter
Page 12 March 2020MAG-UM-00379-EN-07

Chemical Injection Applications
For water line applications with a chemical injection point, install the meter
upstream of the injection point. This eliminates any meter performance issues.
Figure 15: Chemical injection point downstream of meter
If a meter must be installed downstream of a chemical injection connection,
the distance between the flange and the injection point should be between
50…100 feet (15…30 meters). The distance must be long enough to
allow the water or chemical solution to reach the meter in a complete,
homogeneousmixture.
Figure 16: Chemical injection point upstream of meter
If the injection point is too close, the meter senses the two different conductivities for each liquid. This will likely result in
inaccurate measurements. The injection method—spaced bursts, continuous stream of drips or liquid or gas—can also affect
downstream readings by the meter.
Partially Filled Pipe Situations
In some locations, the process pipe may be momentarily only partially filled. Examples include: lack of back pressure,
insufficient line pressure and gravity flow applications.
To eliminate these situations:
• Do not install the meter at the highest point of the pipeline.
• Do not install the meter in a vertical, downward flow section of pipe.
• Always position the ON/OFF valves on the downstream side of the meter.
WRONG RIGHT
FLOW
FLOW
FLOW
FLOW
FLOW
FLOW
WRONG
FLOW
FLOW
RIGHT
Figure 17: Meter placement Do not install in a vertical, downward position. Position "On/Off" valves on downstream side.
Figure 18: Position valves on downstream side
To minimize the possibility of partially full pipe flows in horizontal, gravity or low pressure applications, create a pipe
arrangement that allows the detector to remain full of liquid at all times.
Figure 19: Pipe positioned to keep water in detector
Meter Location, Orientation and Applications
Page 13March 2020 MAG-UM-00379-EN-07

AMPLIFIER MOUNTING CONFIGURATION OPTIONS
There are two configurations for mounting the amplifier and many options to accommodate a variety of meter placement
and environmental conditions.
Meter Mount Conguration
The meter mount configuration has the amplifier mounted directly on the detector. This compact, self-contained
configuration minimizes installation wiring.
Remote Mount Conguration
The remote mount configuration places the amplifier at a location away from the fluid flow and detector. This is necessary in
situations where process fluid temperature or the environment exceeds amplifier ratings.
The detector and amplifier are connected by wires, run through conduit, between junction boxes on the detector and the
amplifier. The distance between the detector junction box and amplifier junction box can be up to 150 feet (50 meters). A
remote mounting bracket is supplied.
Use a remote mount configuration in the following cases:
• Detector protection class IP 68
• Medium temperature > 212° F (100° C)
• Strong vibrations
DO NOT INSTALL THE SIGNAL CABLE CLOSE TO POWER CABLES, ELECTRIC MACHINES, ETC.
MAKE SURE THAT SIGNAL CABLES ARE SECURELY FASTENED. DUE TO CAPACITY CHANGES, CABLE MOVEMENTS MAY
RESULT IN INCORRECT MEASUREMENTS.
FOR MEDIUM TEMPERATURE HIGHER THAN 158° F 70° C MAKE SURE THAT ANY CABLE IS NOT IN CONTACT WITH THE
HOT SURFACE OF THE DETECTOR.
Submersible Option
If you are installing the meter in a vault, you should order the remote mount, submersible amplifier option. You must not
install the amplifier inside a vault. This will eliminate any potential problems resulting from humidity or temporary flooding in
the vault.
OTE:NNational Electronics Manufacturer's Association (NEMA) 6P enclosures are constructed for indoor or outdoor use
to provide protection against access to hazardous parts; to provide a degree of protection against ingress of solid
foreign objects and water (hose directed water and the entry of water during prolonged submersion at a limited
depth); to provide an additional level of protection against corrosion and will be undamaged by the external
formation of ice on the enclosure.
Protection Class
To fulfill requirements of the protection class, follow these guidelines:
• BODY SEALS NEED TO BE UNDAMAGED AND IN PROPER CONDITION.
• ALL OF THE BODY SCREWS NEED TO BE FIRMLY TIGHTENED.
• OUTER DIAMETERS OF THE USED WIRING CABLES MUST CORRESPOND TO CABLE INLETS (FOR M20 DIAMETER 5…13
MM). IN CASES WHERE CABLE INLET IS NOT USED, PUT ON A DUMMY PLUG.
• TIGHTEN CABLE INLETS.
• IF POSSIBLE, LEAD CABLE AWAY DOWNWARDS. HUMIDITY MUST NOT GET INTO CABLE INLET.
ModMAG® M1000 Electromagnetic Flow Meter
Page 14 March 2020MAG-UM-00379-EN-07

• WE NORMALLY DELIVER THE METER IN ACCORDANCE WITH PROTECTION CLASS IP 67. IF YOU HOWEVER REQUIRE A
HIGHER PROTECTION CLASS, THE AMPLIFIER IS TO BE INSTALLED SEPARATELY FROM THE DETECTOR. IF REQUESTED,
WE CAN ALSO DELIVER THE DETECTOR IN IP 68.
ATTENTION
• LES JOINTS DE CORPS NE DOIVENT PAS ÊTRE ENDOMMAGÉS ET ÊTRE EN BON ÉTAT.
• TOUTES LES VIS DE CORPS DOIVENT ÊTRE FERMEMENT SERRÉES.
• LE DIAMÈTRE EXTÉRIEUR DES FILS DE CÂBLAGE UTILISÉS DOIVENT CORRESPONDRE AUX ENTRÉES DE CÂBLE (POUR
M20 DIAMÈTRE 5…13 MM). DANS LES CAS OÙ L'ENTRÉE DE CÂBLE N'EST PAS UTILISÉE, METTEZ UNE FICHE ISOLANTE.
• SERREZ LES ENTRÉES DE CÂBLE.
• SI CELA EST POSSIBLE, DIRIGEZ LE CÂBLE VERS LE BAS. ÉVITEZ QUE DE L'HUMIDITÉ NE PÉNÉTRE DANS L'ENTRÉE DE
CÂBLE.
• LE COMPTEUR OFFERT EST NORMALEMENT CONFORME À LA CLASSE DE PROTECTION IP 67. CEPENDANT, SI
VOUS EXIGEZ UNE CLASSE DE PROTECTION SUPÉRIEURE, L'AMPLIFICATEUR DOIT ÊTRE INSTALLÉ SÉPAREMENT DU
DÉTECTEUR. SUR DEMANDE, LE DÉTECTEUR PEUT ËTRE OFFERT EN IP 68.
METER GASKETS AND GROUNDING
Gasket and grounding requirements must be considered when determining the meter location, orientation and application.
Meter/Pipeline Connection Gaskets
You must install gaskets (not provided) between the detector's isolating liner
and the pipeline flange to ensure a proper and secure hydraulic seal. Use gaskets
that are compatible with the fluid. Center each gasket on the flange to avoid flow
restrictions or turbulence in the line.
During installation, do not use graphite or any electrically conductive sealing
compound to hold the gaskets. This could compromise the accuracy of the
measuring signal.
If you are using a grounding ring in the detector/pipeline connection, place the
ring between two gaskets. (See “Pipelines with Cathodic Protection” on page16.)
GASKETS RECOMMENDED
Figure 20: Meter/pipeline connection gaskets
Meter Grounding
Process pipeline material can be either electrically conductive (metal) or not electrically conductive (made of or lined with
PVC, fiberglass or concrete).
IMPORTANT
It is essential that the meter amplifier’s input ground (zero voltage reference) be electrically connected to the liquid media and to a
good, solid earth ground reference.
Conductive Pipe Grounding
To achieve an adequate ground, the meter body MUST be electrically connected to the liquid media. The meter flanges are
provided with grounding bolts for this purpose.
If the pipe material is electrically conductive, simply install grounding straps between these grounding bolts and the
mating flanges.
To provide a good electrical connection at the mating flanges, we recommend that you drill and tap the flanges and install a
grounding screw (not provided).
Grounding straps must be copper wire, at least 12 AWG size. They must be connected on both sides (inlet and outlet) of the
detector and to a local, earth ground.
Meter Gaskets and Grounding
Page 15March 2020 MAG-UM-00379-EN-07

Pipelines with Cathodic Protection
For pipelines with cathodic protection, install the meter with potential-free contacts. No electric connection from the meter to
the pipeline system may exist and power supply is to be provided via isolating transformer.
USE GROUNDING ELECTRODES GROUNDING RINGS ALSO NEED TO BE INSTALLED ISOLATED FROM THE
PIPELINE SYSTEM.
ATTENTION
UTILISEZ LES ÉLECTRODES DE MISE À LA TERRE LES ANNEAUX DE MISE À LA TERRE DOIVENT ÊTRE INSTALLÉES À
PARTIR DU SYSTÈME DE CONDUITES.
Observe national rules for potential-free installations.
6 mm² Cu
"X"
M4:1
"X"
Electrically isolated Electrically isolated
Figure 21: Cathodic protection
Non-Conductive Pipe Grounding
If the process pipe is not electrically conductive (PVC, fiberglass, cement-lined pipes or any other non-conductive material)
and the meter was not originally ordered with an optional grounding electrode, you must install a pair of grounding rings
between the mating flanges at both ends of the meter. See the following illustration.
In this case, the grounding straps should be connected to both of the
grounding rings and to a good, solid earth ground. Grounding rings
are available in stainless steel. If your fluid is too aggressive for stainless
steel, order a meter with the optional grounding electrode in a material
compatible with the fluid.
GASKETS RECOMMENDED
GROUNDING RING
GROUNDING RING
Figure 22: Non-conductive pipe grounding
ModMAG® M1000 Electromagnetic Flow Meter
Page 16 March 2020MAG-UM-00379-EN-07

POWER CONNECTIONS
Wiring Safety
WARNING
AT INSTALLATION, BE SURE TO COMPLY WITH THE FOLLOWING REQUIREMENTS:
• Disconnect power to the unit before attempting any connection or service to the unit.
• Do not bundle or route signal lines with power lines.
• Keep all lines as short as possible.
• Use twisted pair shielded wire for all output wiring.
• Observe all applicable local electrical codes.
AVERTISSEMENT
LORS DE L'INSTALLATION, ASSUREZVOUS DE RESPECTER LES EXIGENCES SUIVANTES :
• Débranchez l'appareil avant d'essayer toute connexion ou tout service à l'appareil.
• Ne par regrouper ou acheminer les lignes de signaux aux lignes électriques.
• Gardez toutes les lignes aussi courtes que possible.
• Utilisez un câble blindé à paire torsadée pour tout le câblage de sortie.
• Respectez tous les codes locaux applicables en matière d'électricité.
Opening the M1000 Cover
The M1000 amplifier design lets you open the cover
without completely removing it.
Follow these steps:
1. Completely remove the top two screws from the
amplier using a blade/slotted screwdriver.
2. Loosen both of the bottom screws so that the round
head of each screw clears the top face of the cover.
3. Pull down the cover to the open position.
• For the 2 × M20 cable inlets, use only flexible
electriccables.
• Use separate cable inlets for auxiliary power, signal and
input/output cables.
Top screws
Bottom screws
Figure 23: Remove two screws Figure 24: Open the cover
Power Connections
Page 17March 2020 MAG-UM-00379-EN-07

Auxiliary Power
TO PREVENT ACCIDENTS, CONNECT MAIN POWER ONLY AFTER ALL OTHER WIRING HAS BEEN COMPLETED.
ATTENTION
AFIN D'ÉVITER LES ACCIDENTS, BRANCHEZ L'ALIMENTATION PRINCIPALE SEULEMENT UNE FOIS TOUT LE
CÂBLAGECOMPLÉTÉ.
WARNING
• Do not connect meter under impressed mains voltage.
• Observe type plate (mains voltage and frequency).
• Equipment is provided with an external means for disconnecting the meter from each operating energy supply source.
The disconnecting means can disconnect all current-carrying conductors.
1. Open the cover (see “Opening the M1000 Cover” on page17).
2. Push the auxiliary power cable through the upper cable inlet.
3. Connect as shown in Figure 25.
4. Close the cover and tighten the screws.
Power supply 92…275V AC (50/60 Hz)
Recommended cable size min. 0.75 mm²
Power supply 9…36V DC (13VA)
Recommended cable size min. 0.75 mm²
Figure 25: Auxiliary power connection
ModMAG® M1000 Electromagnetic Flow Meter
Page 18 March 2020MAG-UM-00379-EN-07

Remote Version
CONNECT OR REMOVE THE SIGNAL CONNECTION CABLE ONLY
WHEN THE UNIT HAS BEEN SWITCHED OFF.
ATTENTION
BRANCHEZ OU RETIREZ LE CÂBLE DU SIGNAL DE CONNEXION
UNIQUEMENT LORSQUE L'APPAREIL EST ÉTEINT.
Connection to the Measuring Amplifier
1. Open the cover (see “Opening the M1000 Cover” on page17).
2. Push the signal cable through the lower cable inlet.
3. Connect as shown in Figure 26.
4. Close the cover and tighten the screws and the wire gland.
Connection to the Junction Box
1. Open the junction box.
2. Push the signal cable through the upper cable inlet.
3. Connect as shown in Figure 26.
4. Close the cover and tighten the screws and wire gland.
Figure 26: Remote version connection
Junction Box M1000 Description Wire Color
11 C1 Coil 1 Green
12 C2 Coil 2 Yellow
13 CS Main shield Yellow/Green
45 E1 Electrode 1 White
44* ES Electrode shield Black
46 E2 Electrode 2 Brown
40 EP Empty pipe Pink
44* ES Empty pipe shield Black
* Connections with number 44 are on the same potential.
Power Connections
Page 19March 2020 MAG-UM-00379-EN-07

Signal Cable Specication
OTE:NOnly use signal cables delivered by Badger Meter or corresponding cable in accordance with the
followingspecification. Take maximum signal cable length between detector and amplifier into account (keep
distance as low as possible).
Distance With electrode idle Loop resistance
0…164 ft (0…50 m) 3 × (2 × 0.25 mm²) =< 160 Ω/km
PVC cable with pair and total shield
Capacity: wire/wire < 120 nF/km, wire/shield < 160 nF/km
Temperature range –22…158° F (–30…70° C)
white (45)
brown (46
)
pink (40
)
black (44
)
black (44
)
yellow (12
)
green (11
)
(5 . . . 50 m)
green
(11)
yellow
(12)
p
ink (40)
white (45)
brown
(46)
black
(44)
black
(44)
yellow/
green (13) yellow/green (13
)
16…164 ft
Figure 27: Signal cable specification
Maximum Cable Length at Dierent Fluid Temperatures
ModMAG® M1000 Electromagnetic Flow Meter
Page 20 March 2020MAG-UM-00379-EN-07
Table of contents
Other ModMAG Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Vigor
Vigor 1922 operating instructions

RS PRO
RS PRO IM-195 instruction manual

sauermann
sauermann DP500 Installation and operating instructions

Keysight
Keysight x series Installation note

Agilent Technologies
Agilent Technologies OmniBER 725 Configuration guide

BURWELL
BURWELL Elcometer 270 operating instructions