
Page 7 mrcool.com
Control Panel Operation 2
Control Panel Keypad
The control panel keypad will look similar to
the illustration in Fig 2.1. This will be used to
control most, if not all, of the functions of the
unit. NOTE: some models may be equipped
with a REMOTE SIGNAL RECEPTOR. If this
is the case, the unit can be controlled with
the control panel keypad or by the remote
control.
Power
Press the POWER button to turn the unit on or
off.
Mode
Push this button to cycle through and select
the desired mode: COOL, HEAT, or FAN. The
indicator light beside the mode selected will
illuminate.
COOL: In this mode, cooling will begin
automatically when the room temperature
is 4°F (2°C) below the set temperature. The
compressor will run for at least 5 minutes in
this mode before stopping.
HEAT: In this mode, the temperature can be
set to a maximum of 84°F (29°C). For heat
pump models, the unit will alternate between
reverse cycle heat mode and electric heater
mode depending upon the difference
between the temperature the unit is set to
and the room temperature. The fan motor
will cycles with the compressor.
FAN: The fan operates without heating or
cooling activated (Fan-Only mode). NOTE: If
the unit features DIP SWITCHES, these can
be used to set the temperature range.
Please see the DIP Switch Configurations
section for further information.
NOTE
The reverse cycle and electric heater cannot
be run at the same time. In the scenarios
listed below, it is normal that the unit does
not operate in reverse cycle mode:
1. When the outdoor temperature is lower
than 40°F (4°C) or the room temperature
falls to 8°F (4.5°C) below the set
temperature of the unit, reverse cycle
mode will not occur.
2. There is a 3 minute minimum compressor
run time at any setting to prevent it from
short-cycling. The indoor fan motor will
start before the compressor and stop after
the compressor has cycled off.
3. Pushing the “S1” on the DIP SWITCHES to
the UP (ON) position will prevent the unit
from operating in reverse cycle mode .
4. When frost builds up on the evaporator
coils, the unit will automatically defrost
and the compressor will cycle off.
Up/Down Buttons (+/-)
Push the UP or DOWN buttons to increase or
decrease the temperature setting of the unit
in cooling or heating mode. The temperature
can be adjusted in increments of 1°F (1°C) with
each press of the button. The set temperature
will show on the unit display. NOTE: Pressing
and holding the + and - buttons together will
alternate the temperature display between
°F and °C.
SPEED (Fan Speed)
Every push of this button will change the fan
speed setting to either HIGH, MEDIUM, and
LOW.
Constant Fan Mode
In cooling mode, press the button to turn
the constant fan setting on or off. When this
function is turned on, the constant fan light will
illuminate. This indicates the fan is continuously
running for cooling. When this function is
turned off, the constant fan light will no longer
be illuminated, and the fan will go back to
cycling with the compressor.
.
.
.
Fig. 2.1