MTE RL Series Product manual

RL Line/Load Reactors
208V –690V
TECHNICAL REFERENCE MANUAL
WARNING
High Voltage! Only a qualified electrician can carry out the electrical installation
of this filter.
Quick Reference
❶
Performance Data
Pages 5 - 7
❷
Selection Guide
Pages 8 - 35
❸
Installation Guide
Pages 36 - 42
❹
Start-up/Troubleshooting
Pages 43 - 45

This page intentionally left blank

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 III
TABLE OF CONTENTS
RL LINE/LOAD REACTORS ......................................................................................................................III
1. SAFETY....................................................................................................................................................1
WARNINGS AND CAUTIONS........................................................................................................1
GENERAL SAFETY INSTRUCTIONS ..............................................................................................2
2. GENERAL INFORMATION......................................................................................................................3
RECEIPT &REPAIR STATEMENT.................................................................................................3
ENCLOSURES ...........................................................................................................................4
AGENCY APPROVALS ................................................................................................................4
WARRANTY ..............................................................................................................................4
3. RL LINE/LOAD REACTORS PERFORMANCE DATA ........................................................................... 5
PERFORMANCE SPECIFICATIONS ...............................................................................................5
AUDIBLE NOISE.........................................................................................................................6
SERVICE FACTOR .....................................................................................................................6
PWM /IGBT PROTECTION........................................................................................................6
HARMONIC ATTENUATION..........................................................................................................6
ALTITUDE DERATING.................................................................................................................7
TEMPERATURE DERATING .........................................................................................................7
4. HOW TO SELECT ....................................................................................................................................8
SELECTION GUIDE ....................................................................................................................8
UNDERSTANDING THE RL LINE/LOAD REACTOR PART NUMBER:..................................................9
RL LINE/LOAD REACTOR OPTIONS:.......................................................................................10
Lug Option Details:.............................................................................................................................10
RL LINE/LOAD REACTORS 120V –600V SINGLE PHASE ...........................................................11
Part Number Selection Tables ...........................................................................................................11
RL LINE/LOAD REACTORS 208 VOLTS,60HZ............................................................................12
Part Number Selection Tables ...........................................................................................................12
RL LINE/LOAD REACTORS 208 VOLTS,60HZ............................................................................13
Part Number Selection Tables ...........................................................................................................13
RL LINE/LOAD REACTORS 240 VOLTS,60HZ............................................................................14
Part Number Selection Tables ...........................................................................................................14
RL LINE/LOAD REACTORS 240 VOLTS,60HZ............................................................................15
Part Number Selection Tables ...........................................................................................................15
RL LINE/LOAD REACTORS 400 VOLTS,50HZ............................................................................16
Part Number Selection Tables ...........................................................................................................16
RL LINE/LOAD REACTORS 400 VOLTS,50HZ............................................................................17
Part Number Selection Tables ...........................................................................................................17
RL LINE/LOAD REACTORS 480 VOLTS,60HZ............................................................................18
Part Number Selection Tables ...........................................................................................................18
RL LINE/LOAD REACTORS 480 VOLTS,60HZ............................................................................19
Part Number Selection Tables ...........................................................................................................19
RL LINE/LOAD REACTORS 600 VOLTS,60HZ............................................................................20
Part Number Selection Tables ...........................................................................................................20
RL LINE/LOAD REACTORS 600 VOLTS,60HZ............................................................................21
Part Number Selection Tables ...........................................................................................................21
RL LINE/LOAD REACTORS 690 VOLTS,50HZ............................................................................22
Part Number Selection Tables ...........................................................................................................22
RL LINE/LOAD REACTORS 690 VOLTS,50HZ............................................................................23
Part Number Selection Tables ...........................................................................................................23
RL LINE/LOAD REACTORS.......................................................................................................24

RL Reactors Technical Reference Manual 208V –690V
IV Form: RL-TRM-E April 2019 REV. 001
Open Dimension Reference...............................................................................................................24
RL LINE/LOAD REACTORS.......................................................................................................25
Technical and Mechanical Specifications...........................................................................................25
RL LINE/LOAD REACTORS.......................................................................................................26
Technical and Mechanical Specifications...........................................................................................26
RL LINE/LOAD REACTORS.......................................................................................................27
Technical and Mechanical Specifications...........................................................................................27
RL LINE/LOAD REACTORS.......................................................................................................28
Technical and Mechanical Specifications...........................................................................................28
RL LINE/LOAD REACTORS.......................................................................................................29
Technical and Mechanical Specifications...........................................................................................29
RL LINE/LOAD REACTORS.......................................................................................................30
Technical and Mechanical Specifications...........................................................................................30
RL LINE/LOAD REACTORS.......................................................................................................31
Technical and Mechanical Specifications...........................................................................................31
RL LINE/LOAD REACTORS.......................................................................................................32
Technical and Mechanical Specifications...........................................................................................32
RL LINE/LOAD REACTORS.......................................................................................................33
Technical and Mechanical Specifications...........................................................................................33
RL LINE/LOAD REACTORS.......................................................................................................34
Technical and Mechanical Specifications...........................................................................................34
RL LINE/LOAD REACTORS.......................................................................................................35
Technical and Mechanical Specifications...........................................................................................35
5. HOW TO INSTALL .................................................................................................................................36
INSTALLATION CHECKLIST .......................................................................................................36
G
ROUNDING
..........................................................................................................................37
POWER WIRING CONNECTION .................................................................................................38
TYPICAL CONNECTION DIAGRAMS............................................................................................39
TORQUE RATINGS...................................................................................................................40
TORQUE RATINGS...................................................................................................................41
TORQUE RATINGS...................................................................................................................42
6. START-UP..............................................................................................................................................43
S
AFETY
P
RECAUTIONS
..........................................................................................................43
7. TROUBLESHOOTING............................................................................................................................44

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 V
List of Figures
Figure 3-1: Altitude Derating Curve............................................................................................ 7
Figure 3-2: Temperature Derating.............................................................................................. 7
Figure 5-1: Line Reactor ...........................................................................................................39
Figure 5-2: Load Reactor..........................................................................................................39
Figure 5-3: Multiple Line Reactors.............................................................................................39
Figure 5-4: Single Phase Line Reactors....................................................................................39
List of Tables
Table 3-1: Performance Specifications....................................................................................... 5
Table 4-1: RL Reactors 120V –600V –Single Phase...............................................................11
Table 4-2: RL Reactors 208V –3-Phase...................................................................................12
Table 4-3: RL Reactors 208V –3-Phase...................................................................................13
Table 4-4: RL Reactors 240V –3-Phase...................................................................................14
Table 4-5: RL Reactors 240V –3-Phase...................................................................................15
Table 4-6: RL Reactors 400V –3-Phase...................................................................................16
Table 4-7: RL Reactors 400V –3-Phase...................................................................................17
Table 4-8: RL Reactors 480V –3-Phase...................................................................................18
Table 4-9: RL Reactors 480V –3-Phase...................................................................................19
Table 4-10: RL Reactors 600V –3-Phase.................................................................................20
Table 4-11: RL Reactors 600V –3-Phase.................................................................................21
Table 4-12: RL Reactors 690V –3-Phase.................................................................................22
Table 4-13: RL Reactors 690V –3-Phase.................................................................................23
Table 4-14: RL Reactors Open Panel Technical Specifications.................................................25
Table 4-15: RL Reactors NEMA 1/2 Technical Specifications...................................................30
Table 4-16: RL Reactors NEMA 3R Technical Specifications....................................................33
Table 5-1: RL Reactors Torque Ratings....................................................................................40
Table 7-1: Troubleshooting Guide.............................................................................................45

RL Reactors Technical Reference Manual 208V –690V
1 Form: RL-TRM-E April 2019 REV. 001
1. SAFETY
Warnings and Cautions
The following symbols are used in this manual:
WARNING
High VoltageWarning: warns of situations that dangerously high
voltage is involved. Failure to use proper precautions may lead
to serious injury or death.
WARNING
General Warning: warns of situations that can result in serious
injury or death if proper precautions are not used.
Caution
General Caution: identifies situations that could lead to
malfunction or possible equipment damage.

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 2
General Safety Instructions
WARNING
High Voltage! Only a qualified electrician can carry out the electrical
installation of this filter.
High voltage is used in the operation of line/load reactors. Use extreme
caution to avoid contact with high voltage when operating, installing or
repairing line/load reactors.
Injury or death may result if safety
precautions are not observed.
Line/load reactors are used in conjunction with inverters, or other electrical
equipment that may feedback lethal voltages. Follow the safety instructions
in the equipment used with the reactor in addition to the safety instructions
in this manual.
WARNING
The opening of the branch circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or
electrical shock, line/load reactors should be examined and replaced if
damaged.
An upstream disconnect/protection device must be used as required by the
National Electrical Code (NEC) or governing authority.
Even if the upstream disconnect/protection device is open, the drive
downstream of the line/load reactor may feedback high voltage to the
reactor. The drive safety instructions must be followed. Injury or death
may result if safety precautions are not observed.
Line/load reactors must be grounded with a grounding conductor
connected to all grounding terminals. Open panel reactors must have a
2”x2” area cleaned of paint and varnish on the lower mounting bracket.
Only spare parts obtained from MTE Corporation or an authorized MTE
distributor can be used.
Caution
Loose or improperly secured connections may damage or degrade reactor
performance. Visually inspect and secure all electrical connections before
power is applied to the filter.
The user of this reactor must assure that the input voltage and frequency
is correct for the reactor rating and that the voltage applied falls within the
rated operating tolerance envelop specified for the reactor. For severe
power line applications where the power feed is likely to experience surges
and transients that exceed the input voltage rating, it is recommended that
a TVSS (Transient Voltage Surge Suppression) or SPD (Surge Protection
Device) be deployed ahead of the reactor to reduce the possibility of
exceeding the reactor’s rated voltage. Consult with TVSS or SPD
manufacturer to determine the correct protection requirements for your
power line conditions.

RL Reactors Technical Reference Manual 208V –690V
3 Form: RL-TRM-E April 2019 REV. 001
2. GENERAL INFORMATION
The purpose of this manual is to properly specify, size, and install the RL Series Line/Load
Reactors.
For most current information, please refer to website
https://www.mtecorp.com/products/reactors/rl-reactors/
Receipt & Repair Statement
Upon Receipt of this Filter:
RL Line/Load Reactors have been subjected to demanding factory tests before shipment.
Carefully inspect the shipping container for damage that may have occurred in transit. Then
unpack the reactor and carefully inspect for any signs of damage. Save the shipping container for
future transport of the reactor.
In the event of damage, please contact and file a claim with the freight carrier involved
immediately.
If the equipment is not going to be put into service upon receipt, cover and store the reactor in a
clean, dry location. After storage, ensure that the equipment is dry and that no condensation or
dirt has accumulated on the reactor before applying power.
Repair/Exchange Procedure
MTE Corporationrequires a Return Material Authorization Number and formbefore we canaccept
any reactors that qualify for return or repair. If problems or questions arise during installation,
setup, or operation of the reactor, please contact MTE for assistance at:
Toll Free: 1-800-455-4MTE (1-800-455-4683)
International Tel: (+1)262-253-8200
Fax: (+1)262-253-8222

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 4
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and
prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure
selected, these enclosures meet the requirements of NEMA 1/2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows.
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment and provide a degree of protection against limited amounts of falling water and
dirt.
Type 3R NEMA / IEC IP23 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the
enclosed equipment and provide a degree of protection against falling rain sleet and
external ice formation.
Agency Approvals
UL-508, File E180243 Component Listed (1 amp –2400 amps)
UL-508, File E180243 UL Listed NEMA 1 units (1 amp –2400 amps)
CSA C22.2, File LR29753-13 CSA Certified (1 amp –2400 amps)
Class N, 200° C, File E66214, Type 200-18, UL Recognized Insulation System
CE Marked Warranty
Five (5) years from the date of shipment. See https://www.mtecorp.com/industry-leading-
warranty/ for details.

RL Reactors Technical Reference Manual 208V –690V
5 Form: RL-TRM-E April 2019 REV. 001
3. RL LINE/LOAD REACTORS PERFORMANCE DATA
Performance Specifications
Table 3-1: Performance Specifications
Impedance Levels
1.5%, 2%, 3%, 4%, 5% available
Continuous Service Factor*
Reactors rated 1 to 750 Amps –150% of rating
Reactors rated above 750 Amps –125% rating
Overload Rating
200% of fundamental for 30 minutes
300% of fundamental for 1 minute
Input Voltage(s)
120V –600V 1 phase
208V –690V 3 phase
Current Range
1A –1,500A
Maximum System Voltage
600 Volts (units with terminal blocks)
690 Volts (units with box lugs or tab terminals)
Maximum Switching Frequency
20 kHz
Ambient Temperature (Operating)
-40 to +50 degrees C Open Panel Reactor
-40 to +40 degrees C Enclosed Reactor
-40 to +90 degrees C Storage
Insulation System
Class N (200° C)
Altitude without derating
3,300 feet above sea level
Fundamental Frequency
50/60 Hz
Inductance Curve
100% at 100% current
100% at 150% current
50% at 350% current (minimum)
Inductance Tolerance
+/- 10%
Notes:
*Select reactor based on fundamental current rating.
The Short Circuit Current Rating (SCCR) is not required under Exception No.1 of
UL508A SB4.2.1 effective 4/25/06.

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 6
Audible Noise
RL Line/Load Reactors offer low noise operation. Core and coil construction, flux density control,
harmonic compensation as well as our epoxy impregnation process assure minimal audible noise
radiation. Although our reactors are typically “quiet”, waveforms vary by drive type and application
and therefore reactor audible noise may vary by application. Noise levels may be affected by
type of motor and motor conductor as well as motor conductor length.
Typical audible noise levels for units selected from our catalog by HP rating are:
•2 thru 12 amps 55 dBA
•18 thru 100 amps 65 dBA
•130 thru 400 amps 70 dBA
•500 thru 1200 amps 75 dBA
Service Factor
RL Line/Load Reactors are compensated for the additional currents and high frequencies caused
by the presence of harmonics. The reactor fundamental current rating indicates the typical full
load motor current and is also the basis of impedance rating. Standard reactors rated 1 amps
thru 750 amps offer a full 1.5 service factor rating which allows them to carry overload current up
to 150% of their fundamental rating when applied as an input line reactor. Since the nameplate
ratings of motor drives (ASD) varies widely by manufacturer, this helps to assure that the reactor
maximum current rating is compatible with the nameplate current rating on the ASD. The service
factor rating compensates for ASD manufacturer variances in motor drive current ratings and for
harmonic currents. Nominal inductance is assured all the way up to the service factor current
rating.
PWM / IGBT Protection
RL Line/Load Reactors are protected against the high peak voltage and fast rise time voltage
pulses associated with PWM waveforms. The dielectric strength is 4000 volts rms and RL
reactors meet theratings of an inverter duty motor (NEMA MG-1, part 31). For convenience, they
can be located either at the motor or at the drive.
Harmonic Attenuation
Our unique harmonic compensation assures maximum circuit inductance in the presence of
complex waveforms and can be relied upon to minimize input total harmonic current distortion
(THID). Additionally, it offers superior absorption of transient voltage spikes. Our standard
reactors will typically reduce 6-pulse rectifier input current harmonics to the following levels at full
load operating conditions:
•3% reactor alone 45% or less THID
•5% reactor alone 35% or less THID
•3% AC reactor + 3% DC link choke 33% or less THID
•5% AC reactor + 3% DC link choke 28% or less THID
(DC link choke inductance is equivalent ac impedance).

RL Reactors Technical Reference Manual 208V –690V
7 Form: RL-TRM-E April 2019 REV. 001
Altitude Derating
Figure 3-1: Altitude Derating Curve
Temperature Derating
Figure 3-2: Temperature Derating
Altitude Derating Curve
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
03300 6600 9900 13200 16500
Altitude (Feet)
Current De-Rating Factor
Reactor Temperature De-Rating
0.60
0.65
0.70
0.75
0.80
0.85
0.90
0.95
1.00
1.05
40 45 50 55 60 65 70 75 80 85 90
Ambient Temperature Deg. C
Current De-Rating Factor

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 8
4. HOW TO SELECT
Selection Guide
MTE RL Line/Load Reactors are optimized to support global IEC and NEC Drive /motor
applications. RL’s are RMS current rated impedance devices. Selection is based on the choice
of inductance correlated to the application motor full load amps, voltage and frequency and the
number of phases. Use the product selection brochure based on input voltage and NEC FLA
motor selection table for common voltages. For critical impedance selection based on specific
HP or load currents, consult MTE applications engineering.
Choose the impedance level:
3% Reactors rated at 3% are typically sufficient to absorb line spikes and motor current
surges, and help prevent nuisance tripping to the drive and circuit breakers in most
applications. 3% is typically specified by most drive manufacturers.
5% Reactors rated at 5% are best for reducing harmonic current and frequencies. Use
them when you must reduce VFD drive generated harmonics, and to reduce motor
operating temperature.
Single Phase Applications:
RL reactors may also be sized to protect single phase drives. Please see MTE Application
Note: How to Use a 3-Phase Line Reactor for a Single-Phase Application for details.
NOTE: For inverters feeding isolation transformers select a reactor with a current rating
equal to or greater than that of the transformer primary current.
Please verify information below for proper selection:
Line Voltage and Frequency: Input voltage 208V-690V 50/60 Hz (3-phase); 120V-
600V 50/60 Hz (1-phase). See Table 3-1: Performance Specifications (p5) for
specification.
Current Rating: Support for 1 Amp –1500 Amps.
Performance:See Table 3-1: Performance Specifications (p5) for specification.
Altitude: 3,300 feet above sea level without derating. See Figure 3-1: Altitude Derating
Curve (p7) for derating information.
Enclosure Type: Open Panel, NEMA 1/2 & NEMA 3R, see Enclosures (p4) for
enclosure descriptions.
Temperature: See Table 3-1: Performance Specifications (p5) for operating
temperature information and Figure 3-2: Temperature Derating (p7) for derating
information.
Refer to Article 430 Table 430.91 of the National Electrical code for the selection of the
appropriate enclosure Type Number for your application.

RL Reactors Technical Reference Manual 208V –690V
9 Form: RL-TRM-E April 2019 REV. 001
Understanding the RL Line/Load Reactor Part Number:
RL _ - _ _ _ _ X X X
MOV Options*
A = 208 Volts
C = 240 Volts
E = 400 Volts
G = 480 Volts
J = 600 Volts
Current Rating (i.e. 001 is 1 Amp)
Mechanical Configurations
0 = Base Mount
1 = NEMA 1
3 = NEMA 3R
Reactor Relative Impedance Number
1 - 4 (1) is lowest value
Lug/Terminal Block Options**
B1 = Side Facing
B8 = Top Mounted
B14 = Front Facing

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 10
RL Line/Load Reactor OPTIONS:
* MOV Option –Adding Metal Oxide Varistors (MOV) can help prevent damage to reactors and
variable frequency drives (VFD’s) when large spikes in transient voltage occur.
** B1 & B14 Lug Orientation Option –If the current RL part lug orientation does not work for
installation; a modification can be made to adjust the lug to be either Side Facing or Front Facing.
To signify the change, add either B1 or B14 to the end of the RL part number.
** B8 Terminal Block Option –If the current RL front mounted terminal block does not work for
installation, a modification can be made to adjust a terminal block to be Top Mounted. To signify
the change, add B8 to the end of the RL part number. (Note: Terminal blocks are only available
on reactors 45 Amps and below. Contact MTE for additional information.)
Lug Option Details:
“B1” Lug Orientation Option “B14” Lug Orientation Option
“B8” Terminal Block Modification

RL Reactors Technical Reference Manual 208V –690V
11 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 120V –600V Single Phase
Part Number Selection Tables
Table 4-1: RL Reactors 120V –600V –Single Phase
Motor
%
Impedance
Input Voltage & Hz
KW
HP
120V 60Hz
208V 60Hz
240V 60Hz
240V 50Hz
400V 50Hz
480V 60Hz
600V 60Hz
0.18
0.25
5%
RL-01801
RL-00204
RL-00402
RL-00403
RL-00103
RL-00203
RL-00102
0.25
0.33
5%
RL-01801
RL-00803
RL-00402
RL-00402
RL-00203
RL-00202
RL-00103
0.37
0.5
5%
RL-01201
RL-00802
RL-00803
RL-00803
RL-00201
RL-00202
RL-00202
0.55
0.75
5%
RL-01801
RL-01202
RL-00802
RL-00802
RL-00404
RL-00404
RL-00202
0.75
1
5%
RL-01801
RL-00801
RL-01202
RL-00802
RL-00403
RL-00403
RL-00404
1.1
1.5
5%
RL-02501
RL-01201
RL-01201
RL-01802
RL-00803
RL-00803
RL-00403
1.5
2
5%
RL-03501
RL-01201
RL-01201
RL-01802
RL-00803
RL-00803
RL-00804
2.2
3
5%
RL-05501
RL-01801
RL-01801
RL-02502
RL-01203
RL-01203
RL-00803
3.7
5
5%
RL-10001
RL-03501
RL-02501
RL-03502
RL-01803
RL-01803
RL-01203
5
7.5
5%
RL-16001
RL-04501
RL-04501
RL-03501
RL-02503
RL-02503
RL-01803
7.5
10
5%
RL-
20001B14
RL-05501
RL-04501
RL-05502
RL-03502
RL-02502
RL-02503
11
15
5%
-
RL-08001
RL-08001
RL-10002
RL-04502
RL-04502
RL-03503
15
20
5%
-
RL-10001
RL-10001
RL-13002
RL-05502
RL-05503
RL-04503
18.5
25
5%
-
RL-13001
RL-13001
RL-13002
RL-08002
RL-08003
RL-05503
22
30
5%
-
RL-16001
RL-16002
RL-16002
RL-08002
RL-08002
RL-05503
30
40
5%
-
RL-
20001B14
RL-
20002B14
RL-
20002B14
RL-10002
RL-10002
RL-08003
37.5
50
5%
-
RL-
25001B14
RL-
25002B14
RL-
25002B14
RL-13003
RL-13003
RL-10003
45
60
5%
-
RL-
32001B14
RL-
32002B14
RL-
32002B14
RL-16003
RL-16003
RL-13003
55
75
5%
-
RL-
40001B14
RL-
32001B14
RL-
40002B14
RL-
20003B14
RL-
20003B14
RL-13003
75
100
5%
-
RL-
50001B14
RL-
40001B14
RL-50002
RL-
25003B14
RL-
25003B14
RL-
20003B14
93
125
5%
-
-
-
-
-
RL-
32003B14
RL-
25003B14
112
150
5%
-
-
-
-
-
RL-
40003B14
RL-
25003B14
150
200
5%
-
-
-
-
-
RL-
40003B14
RL-
32003B14
See Technical and Mechanical Tables for detailed data.

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 12
RL Line/Load Reactors 208 Volts, 60Hz
Part Number Selection Tables
Table 4-2: RL Reactors 208V –3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25
3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.25
0.33
3%
RL-00204
RL-00214
RL-00234
5%
RL-00403
RL-00413
RL-00433
0.37
0.5
3%
RL-00401
RL-00411
RL-00431
5%
RL-00402
RL-00412
RL-00432
0.55
0.75
3%
RL-00401
RL-00411
RL-00431
5%
RL-00803
RL-00813
RL-00833
0.75
1
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.1
1.5
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.5
2
3%
RL-00801
RL-00811
RL-00831
5%
RL-01202
RL-01212
RL-01232
2.2
3
3%
RL-01801
RL-01811
RL-01831
5%
RL-01802
RL-01812
RL-01832
3.7
5
3%
RL-02501
RL-02511
RL-02531
5%
RL-02502
RL-02512
RL-02532
5
7.5
3%
RL-03501
RL-03511
RL-03531
5%
RL-03502
RL-03512
RL-03532
7.5
10
3%
RL-05501
RL-05511
RL-05531
5%
RL-05502
RL-05512
RL-05532
11
15
3%
RL-05501
RL-05511
RL-05531
5%
RL-04501
RL-04511
RL-04531
15
20
3%
RL-08001
RL-08011
RL-08031
5%
RL-05501
RL-05511
RL-05531
18.5
25
3%
RL-10001
RL-10011
RL-10031
5%
RL-08001
RL-08011
RL-08031
See Technical and Mechanical Tables for detailed data.

RL Reactors Technical Reference Manual 208V –690V
13 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 208 Volts, 60Hz
Part Number Selection Tables
Table 4-3: RL Reactors 208V –3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
22
30
3%
RL-10001
RL-10011
RL-10031
5%
RL-13002
RL-13012
RL-13032
30
40
3%
RL-13001
RL-13011
RL-13031
5%
RL-16002
RL-16012
RL-16032
37.5
50
3%
RL-16001
RL-16011
RL-16031
5%
RL-20002B14
RL-20012B14
RL-20032B14
45
60
3%
RL-20001B14
RL-20011B14
RL-20031B14
5%
RL-20002B14
RL-20012B14
RL-20032B14
55
75
3%
RL-25001B14
RL-25011B14
RL-25031B14
5%
RL-25002B14
RL-25012B14
RL-25032B14
75
100
3%
RL-32001B14
RL-32011B14
RL-32031B14
5%
RL-32002B14
RL-32012B14
RL-32032B14
93
125
3%
RL-40001B14
RL-40011B14
RL-40031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
112
150
3%
RL-50001B14
RL-50011B14
RL-50031B14
5%
RL-50002
RL-50012
RL-50032
150
200
3%
RL-60001
RL-60011
RL-60031
5%
RL-75002
RL-75012
RL-75032
187
250
3%
RL-75001
RL-75011
RL-75031
5%
RL-75002
RL-75012
RL-75032
225
300
3%
RL-85001B14
RL-85011B14
RL-85031B14
5%
RL-90002B14
RL-90012B14
RL-90032B14
262
350
3%
RL-100001B14
RL-100011B14
RL-100031B14
5%
RL-100002B14
RL-100012B14
RL-100032B14
300
400
3%
RL-120001B14
RL-120011B14
RL-120031B14
5%
RL-120002B14
RL-120012B14
RL-120032B14
375
500
3%
RL-140001
RL-140011
RL-140031
5%
RL-150002
RL-150012
RL-150032
See Technical and Mechanical Tables for detailed data.

RL Reactors Technical Reference Manual 208V –690V
Form: RL-TRM-E April 2019 REV. 001 14
RL Line/Load Reactors 240 Volts, 60Hz
Part Number Selection Tables
Table 4-4: RL Reactors 240V –3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
0.18
0.25
3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.25
0.33
3%
RL-00204
RL-00214
RL-00234
5%
RL-00201
RL-00211
RL-00231
0.37
0.5
3%
RL-00402
RL-00412
RL-00432
5%
RL-00403
RL-00413
RL-00433
0.55
0.75
3%
RL-00401
RL-00411
RL-00431
5%
RL-00402
RL-00412
RL-00432
0.75
1
3%
RL-00802
RL-00812
RL-00832
5%
RL-00803
RL-00813
RL-00833
1.1
1.5
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
1.5
2
3%
RL-00801
RL-00811
RL-00831
5%
RL-00802
RL-00812
RL-00832
2.2
3
3%
RL-01201
RL-01211
RL-01231
5%
RL-01202
RL-01212
RL-01232
3.7
5
3%
RL-01801
RL-01811
RL-01831
5%
RL-02502
RL-02512
RL-02532
5
7.5
3%
RL-02501
RL-02511
RL-02531
5%
RL-03502
RL-03512
RL-03532
7.5
10
3%
RL-03501
RL-03511
RL-03531
5%
RL-03502
RL-03512
RL-03532
11
15
3%
RL-04501
RL-04511
RL-04531
5%
RL-05502
RL-05512
RL-05532
15
20
3%
RL-05501
RL-05511
RL-05531
5%
RL-08002
RL-08012
RL-08032
18.5
25
3%
RL-08001
RL-08011
RL-08031
5%
RL-10001
RL-10011
RL-10031
See Technical and Mechanical Tables for detailed data.

RL Reactors Technical Reference Manual 208V –690V
15 Form: RL-TRM-E April 2019 REV. 001
RL Line/Load Reactors 240 Volts, 60Hz
Part Number Selection Tables
Table 4-5: RL Reactors 240V –3-Phase
Motor
%
Impedance
MTE Part Number &
Enclosure Type
KW
HP
Open
NEMA 1/2
NEMA 3R
22
30
3%
RL-10001
RL-10011
RL-10031
5%
RL-08001
RL-08011
RL-08031
30
40
3%
RL-13001
RL-13011
RL-13031
5%
RL-13002
RL-13012
RL-13032
37.5
50
3%
RL-13001
RL-13011
RL-13031
5%
RL-16002
RL-16012
RL-16032
45
60
3%
RL-16001
RL-16011
RL-16031
5%
RL-16002
RL-16012
RL-16032
55
75
3%
RL-20001B14
RL-20011B14
RL-20031B14
5%
RL-20002B14
RL-20012B14
RL-20032B14
75
100
3%
RL-25001B14
RL-25011B14
RL-25031B14
5%
RL-25002B14
RL-25012B14
RL-25032B14
93
125
3%
RL-32001B14
RL-32011B14
RL-32031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
112
150
3%
RL-40001B14
RL-40011B14
RL-40031B14
5%
RL-40002B14
RL-40012B14
RL-40032B14
150
200
3%
RL-50001B14
RL-50011B14
RL-50031B14
5%
RL-60002
RL-60012
RL-60032
187
250
3%
RL-60001
RL-60011
RL-60031
5%
RL-75002
RL-75012
RL-75032
225
300
3%
RL-75001
RL-75011
RL-75031
5%
RL-75002
RL-75012
RL-75032
262
350
3%
RL-85001B14
RL-85011B14
RL-85031B14
5%
RL-85002B14
RL-85012B14
RL-85032B14
300
400
3%
RL-100001B14
RL-100011B14
RL-100031B14
5%
RL-100002B14
RL-100012B14
RL-100032B14
375
500
3%
RL-120001B14
RL-120011B14
RL-120031B14
5%
RL-140002
RL-140102
RL-140302
See Technical and Mechanical Tables for detailed data.
Other manuals for RL Series
1
This manual suits for next models
135
Table of contents
Other MTE Industrial Electrical manuals
Popular Industrial Electrical manuals by other brands

Murata
Murata GRM0225C1E5R4WA03 Series Reference sheet

Murata
Murata GRM219R61H225ME15 Series Reference sheet

Murata
Murata GRM155R71E472KA01 Series Reference sheet

Murata
Murata GQM1555C2D5R4BB01 Series Reference sheet

ABB
ABB Tmax XT XT3 Disassembly instructions

Moeller
Moeller A-NZM 14 installation instructions

Rohde & Schwarz
Rohde & Schwarz TS7124AS Instruction handbook

Murata
Murata GJM0335C1ER75WB01 Series Reference sheet

Murata
Murata GRM155D71A225ME15 Series Reference sheet

Moeller
Moeller NHI-NZM 144 Series installation instructions

Murata
Murata GRM1555C1H751GA01 Series Reference sheet

DITEC
DITEC COM E operating instructions