Warranty
Multipipe warrants that this product (22-23002) will be free from any
defect in materials or workmanship, and shall perform in accordance with its
specification, for a period of five years from the date of installation. Multipipe
sole liability for breach of this warranty will be (at its option) to repair or replace
the defective product.
Customer Name: ....................................................................................................................................................
Customer Address: ...............................................................................................................................................
............................................................................................................................................................................................
....................................................................................... Post Code: ..........................................................................
Tel No: .................................................................... Email: .......................................................................................
Engineers Company: ...........................................................................................................................................
Tel No: ...................................................................... Email: ....................................................................................
Instalation Date: .....................................................................................................................................................
Engineers Name: ...................................................................................................................................................
Engineers Signature: ...........................................................................................................................................
14. Technical Specification
Model: 22-23002
Voltage 230 VAC, +-10 %, 50/60 Hz
Operating performance 230 V: 1,8 W
Temperature setback Adjustable
Temperature range 5°C – 35°C
Span +/-0,5C OR +/-0,25C
Storage temperature -20°C to +60°C
Ambient temperature 0 °C up to 45 °C
Degree of protection IP 30
CE conformity according to Class II ( EN60730 )
Housing material PC, V2
Color RAL 9010 pure white
Connection Screw terminal
Weight 125 g net / 170 g gross
Puls-wide-modulation (PWM) Yes
Profile Modes 3 ( Sun, Moon, Automatic)
Heating and Cooling Yes, automatically Change Over
on the Wiring Centre
Parameter adjustment Yes, in Installer Mode
Dimensions 85mm*85mm*25mm
8. Setting the Thermostat
9. Setting the Thermostat
Note: The d20 will help you to reduce the power outlet
on the thermostat.
Setting the hysteresis
You can set the hysteresis by entering the Installer Mode, accessing d01 and after that
selecting the desired value ( PWM / 0.5°C / 1.0°C ). If your device controls the UFH we
recommend to use the PWM algorithm.
Heating and Cooling Selection
Manually
This mode will be indicated by the flashing icons
Press or to change between modes.
Auto
The CO terminal needs to be connected
using the same phase as the power supply.
After that the heating and cooling functions will be done automatically In Installer
Mode, d18 has to be set on 1 (default is 0), when CO wire is connected.
10. Setting the Thermostat
Cooling blocked
When the thermostat is set on Cooling Disabled (d19-->1) it will block the cooling
function for single rooms until the device receives the heating command. During the
periods of Cooling Blocked no special indicator will be displayed on the LCD screen.
Cooling mode indicator will also be turned off.
Protection
When room temperature is over the limit of 36°C, all heating outputs will be turned off
regardless of the control pattern and delay timers. When room temperature is under
the limit of 4°C, all cooling outputs will be turned off regardless of the control pattern
and delay timers.
Device
No
d01
d02
d05
d07
d08
d12
d13
d18
d19
d20
0
0
0
0
1
1
1
2
1
0
5.0-17.0ºC
5.0-35.0ºC
5.0-40.0ºC
2
1
-3,0 ºC to
+3,0 ºC
0
0
0
0
0.0ºC
5.0ºC
35.0ºC
5.0ºC
2
1
PWM
No Connection
Cooling Allowed
1 to 5 actuators loading
Connection
Cooling Disabled
Offset room temp
measuring error (in 0,5 ºC)
Room temp offset
Heating Control
Heating/Cooling Mode
Cooling Blocked
Selecting the number
of actuators
Cooling Control
Valve Protection
Frost Setpoint
Max. Heating Setpoint
Min. Cooling Setpoint
Default
Value
Function Valves Denition
On-Off: 0,5 ºC (±0,25 ºC)
On-Off: 0,5 ºC (±0,25 ºC)
Disable
Enable
On-Off: 0,5 ºC (±0,5 ºC)
On-Off: 0,5 ºC (±0,5 ºC)
11. Factory Reset
12. Heating/Cooling Mode
13. Temperature Offset (Temperature Calibration)
Press the indicated keys
together for 3 seconds.
Select P47 if you want to
reset to factory settings.
Press to confirm.
Press to confirm.
Note: In order to
quickly reach 47
you can hold down
key. The display will
fast forward in steps
of 5.
Heating Mode Cooling Mode
Temperature Mode Heating Cooling
Sunny 20.0ºC 20.0ºC
Moon 17.0ºC 26.0ºC
Frost (heat system) 5ºC --.-
The Temperature Offset can be set at any value between
-3°C and +3°C. Press OK to confirm.
Long press in order to
enter the Settings Mode.
Press or in order to
set the Temperature Offset.
Multipipe Ltd
Unit 12 Great Hayes Business Park
Lower Burnham Road
Stow Maries
Chelmsford, Essex, CM3 6SQ
Sales
T: 01245 227630
E: sales@multipipe.co.uk
Technical
T: 01245 850799
E: technical@multipipe.co.uk
www.multipipe.co.uk
DIGITAL 230 V
THERMOSTAT
Model: 22-23002
INSTALLER MANUAL