115107D – LV Metering
Normally Off Relay
With default settings, the normally off relay will activate whenever the unit goes into
emergency backup. The options available in this tier of the menu allow for
customization of the normally off relay. Use the left or right arrow keys to navigate
these settings, and press the ENTER key to select one of the normally off relay
settings. Normally off relay functions included are normally off delay, time clock
weekday, time clock weekend, and loadshed.
Normally off delay
The normally off delay function allows the user to delay the turn on time of the
normally off relay, as well as forcing the normally off relay to stay on for a
period of time after the unit returns from emergency backup. Use the left or
right arrow keys to select enable or disable, and then press ENTER. When
enabling, the user will be prompted to set the delay on time and the delay off
time. Both must be set, by using the left or right arrow keys and pressing
ENTER, in order to save any changes.
Time Clock
The time clock weekday and weekend functions allow the user to activate the
normally off relay between a range of time each day. This function is split into
two functions to allow a different time range for weekdays and weekends. The
normally off relay will be activated between the start and stop times once
enabled. Use the left or right arrow keys to select enable or disable, and then
press ENTER. When enabling, the user will be prompted to set the start time
and the stop time. Use the left or right arrow keys to change the times, and
the ENTER key to set the selected time. Both the start time and stop time must
be set in order to save any changes.
Loadshed
The loadshed function deactivates the normally off relay after the unit has been
on emergency backup for a period of time. This feature can extend the
emergency run time of the system by removing unneeded loads. Use the left or
right arrow keys to select enable or disable, and then press ENTER. When
enabling, the user will be prompted to set the amount of time on emergency
backup before the loadshed function deactivates the normally off relay. If
enabled, and the system exceeds the specified time while on emergency
backup, the normally off relay will be deactivated regardless of other normally
off functions.
Audible Alarm
This tier provides the option to disable the audible alarm when the unit is in a fault
condition. This alarm will still function when the display is powered off, and will also
make an audible noise during power up of the display. When the unit is in an alarm
state, the audible alarm will repeat a 1 second on, 1 second off pattern. When the
unit is in emergency backup, the audible alarm will repeat a 1 second on, 4 second
off pattern.
Normally Off Timer
The normally off timer will hold on the normally off relay, providing power to the
normally off load until the specified time has elapsed.