Nailor UNI2-VAV User manual

IOM-TBN
Date: 12-2021 Supersedes: NEW Page 1 of 6
IOM – BACnet®UNI2-VAV Diffuser Assembly
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TNB Interface:
TBN
IOM-TBN
Date: 12-2021 Supersedes: NEW Page 2 of 6
TBN BACnet Thermostat •Network Configuration
From the TBN General Configuration submenu, the controller’s
network parameters can be set.
How to enter the General Configuration submenu
To enter the General Conguraon submenu:
1. Hold the Menu buon for ve seconds.
The password eld appears.
2. Use the arrow keys to increase or decrease the displayed
number unl it matches the congured password.
By default, the password is 9995.
3. Press the Menu buon to submit the password.
Upon subming the correct password, the Advanced Menu is
entered and the Setpoints submenu is displayed.
4. Press the Menu buon several mes unl GEN CFG appears
on the display.
5. Press either of the arrow keys to enter the Conguraon
submenu.
Upon entering the General Conguraon submenu, the MAC
Address parameter appears.
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Advanced
Menu
and
- Enters Advanced Menu, when held for 5 sec
- Navigates between parameters
- Submits a modied parameter
- Goes up one level, when held for 5 sec
- Cancels a modied parameter, when held for 5 sec
- Modies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
Buon Navigaon Guide:
Seng up the Network Parameters How to set up the BACnet® MS/TP
communicaon network parameters
The TBN can be used to set the controller’s BACnet® MAC address
and baud rate. In doing so, the TBN must have a subnet ID of 1.
To set up the network parameters:
1. Use the arrow keys to enter the controller’s MAC address.
2. Press the Menu buon to submit the MAC address.
The TBN subnet ID of 1 appears on the display.
3. Press the Menu buon once to move onto the next parameter.
The Baud Rate parameter appears on the display.
4. Use the arrow keys to set the baud rate.
Keep in mind that all the devices on the data bus must be set to
the same baud rate. Typically, the baud rate is set at the router
level. Therefore, it is recommended to set the baud rate to AUTO
so that the baud rate being used on the data bus is automacally
detected and applied to the controller accordingly.
5. Press the Menu buon to submit the baud rate.
5 sec
Screen meout: none
Screen meout: 30 sec.
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 15 sec
Screen meout: 15 sec
Screen meout: 15 sec Screen meout: 30 sec
IOM-TBN
Date: 12-2021 Supersedes: NEW Page 3 of 6
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN BACnet Thermostat •Network Configuration
The TBN hardware informaon appears on the display.
The TBN’s hardware informaon may be required by Nailor
Technical Support for troubleshoong purposes.
How to adjust the screen contrast
1. Navigate to the contrast parameter.
2. Use the arrow keys to adjust the screen contrast.
The Contrast parameter ranges from 0 to 100, where smaller
values give a dimmer contrast than larger ones.
3. Press the Menu buon to submit the new contrast level.
The screen contrast changes according to the new value
submied.
Advanced
Menu
and
- Enters Advanced Menu, when held for 5 sec
- Navigates between parameters
- Submits a modied parameter
- Goes up one level, when held for 5 sec
- Cancels a modied parameter, when held for 5 sec
- Modies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
Buon Navigaon Guide:
OR
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
How to exit the General Configuration submenu
To exit the General Conguraon submenu and go up one level,
do one of the following:
1. Press the Menu buon several mes unl the Exit screen
appears. Then press either of the arrow keys.
2. Press and hold the Menu buon for 5 seconds.
Screen meout: 30 sec
OR
Screen meout: 30 sec
IOM-TBN
Date: 12-2021 Supersedes: NEW Page 4 of 6
TBN BACnet Thermostat •General Configuration
To enter the Configuration submenu:
1. Hold the Menu buon for ve seconds.
The password eld appears.
2. Use the down arrow key to decrease the display number unl
it matches the congured password.
By default, the password is 9995.
3. Press the Menu buon to submit the password.
4. Once the password is accepted, press the Menu buon again
and SETPOINT will appear on the screen.
5. Press the up or down arrow key and the Bypass Time will
appear. The default seng is 60 minutes. To change the default
seng, use the arrow keys.
6. Press the Menu buon again and the Setpoint Low Limit will
appear. The default seng is 64°F. To change the default seng,
use the arrow keys.
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Advanced
Menu
and
- Enters Advanced Menu, when held for 5 sec
- Navigates between parameters
- Submits a modied parameter
- Goes up one level, when held for 5 sec
- Cancels a modied parameter, when held for 5 sec
- Modies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
Buon Navigaon Guide:
How to enter the Conguraon submenu
7. Press the Menu buon again and the Setpoint High Limit will
appear. The default seng is 74°F. To change the default seng,
use the arrow keys.
8. Press the Menu buon again an Reheat Cong will appear. The
default seng is No Heat. To change the default seng, use the
arrow keys.
9. Press the Menu buon again and Min Posion Heat will appear
only if 1 or 2 stage heang or 0-10/2-10 volts was selected on
the previous screen. The default seng is 10%. Use the arrow
keys to change the default seng. This screen will be skipped if
no reheat is selected and the next screen to appear will be Min
Damper Posion.
10. Press the Menu buon again and the Minimum Damper
Posion will appear. The default seng is 100%. To change the
default seng, use the arrow keys.
11. Press the Menu buon again and the Maximum Damper
Posion will appear. The default seng is 100%. To change the
default seng, use the arrow keys.
12. Press the Menu buon again and the Unoccupied Damper
Posion will appear. The default seng is 10%. To change the
default seng, use the arrow keys.
Screen meout: none
Screen meout: 15 sec
Screen meout: 15 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
IOM-TBN
Date: 12-2021 Supersedes: NEW Page 5 of 6
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN BACnet Thermostat •General Configuration
13. Press the Menu buon again the Unocc Heat Setpoint will
appear. The default seng is 62°F. To change the default, use the
arrow keys.
14. Press the Menu buon again the Unocc Cool Setpoint will
appear. The default seng is 78°F. To change the default, use the
arrow keys.
15. Press the Menu buon again and the Max Duct
Temp will appear if either 1 or 2 stage reheat or 0-10/2-10 volts
was enabled. The default seng is 80°F. To change the default
seng, use the arrow keys. This screen will be skipped if no
reheat is selected.
16. Press the Menu buon again and the Max Duct Discharge
will appear if either 1 or 2 stage reheat or 0-10/2-10 volts was
enabled. The default seng is 120°F. To change the default
seng, use the arrow keys. This screen will be skipped if no
reheat is selected.
17. Press the Menu buon again and the Slave Damper Enable
will appear. The default seng is Disable. To change the default,
use the arrow keys.
18. Press the Menu buon again and Moon Bypass will appear
if the TBN has a moon detector on board. The default seng is
Enable. To change the default seng, use the arrow keys.
19. Press the Menu buon again and Moon Bypass Time will
appear if the TBN has a moon detector on board. The default
seng is 60 Minutes. To change the default seng, use the
arrow keys.
20. Press the Menu buon again and CO2 Setpoint will appear if
the TBN has CO2 detecon on board. The default seng is 800
ppm. To change the default seng, use the arrow keys.
Advanced
Menu
and
- Enters Advanced Menu, when held for 5 sec
- Navigates between parameters
- Submits a modied parameter
- Goes up one level, when held for 5 sec
- Cancels a modied parameter, when held for 5 sec
- Modies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
Buon Navigaon Guide:
21. Press the Menu buon again and Operaon - Auto will
appear. This is the default for automac damper operaon.
22. To use Hand Posions, press the UP arrow buon unl the
display reads Operaon - Hand. This allows Hand Posion to be
acve.
If the UP arrow buon is pressed again, the display will toggle
back to Auto. Press Menu to advance to next screen.
23. When in Hand Posion, use the arrow buons to increase or
decrease the damper posion value. The default percentage is
25% which is the xed posion the damper will open.
24. Exit the submenu via the arrow keys or let stat meout.
OR
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
Screen meout: 30 sec
IOM-TBN
Date: 12-2021 Supersedes: NEW Page 6 of 6
IOM •BACnet®UNI2-VAV Diffuser Assembly
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
TBN Wiring Diagram:
NOTE:
1. Dashed lines indicate new eld wiring. Sold lines indicate
exisng wiring to remain or new eld wiring by others.
2. All eld wiring must meet or exceed the requirements of the
Naonal Electrical Code (NEC) and the Sate Local requirements.
3. For inputs and outputs, the shield wire is grounded at the
controller end only.
4. Wiring for inputs and outputs is 18 AWG, shielded, twisted pair
with stranded nned copper conductors.
5. The BACnet® MS/TP network wire is 24 AWG (0.65 mm)
stranded, twisted shield pair (Jackson system part#: 24/2
BACnet®). The BACnet® MS/TP communicaon wire is polarity
sensive and the only acceptable topology is to Daisy-chain the
cable from one controller to the next.
6. Mount space temperature sensor per ADA requirements. Field
verify locaon and coordinate with other trades.
SMART VUE
COMMUNICATING
SPACE SENSOR
WIRELESS
PORT
SHIELD
NET--
NET+
RX/TX
24VAC
24V COM
PRESSURE
HIGH
LOW
24V COM
POWER
STATUS
SUBNET
UI3
UI2
COM
UI1
COM
UO4
DO3
DO2
DO1
24VAC OUT

Other manuals for UNI2-VAV

1

Popular Accessories manuals by other brands

INNOBIZ Kemila manual

INNOBIZ

INNOBIZ Kemila manual

Symbol CRD 7200 Quick reference guide

Symbol

Symbol CRD 7200 Quick reference guide

Opticon EBS-30 Specification manual

Opticon

Opticon EBS-30 Specification manual

Emerson Rosemount TupHFET TF396 instruction manual

Emerson

Emerson Rosemount TupHFET TF396 instruction manual

DARQ Matter Pocket 2.5k user guide

DARQ Matter

DARQ Matter Pocket 2.5k user guide

Pilz PSEN sl-1.0p 2.1 operating manual

Pilz

Pilz PSEN sl-1.0p 2.1 operating manual

Acer SP100 user guide

Acer

Acer SP100 user guide

Telex RADIOCOM BTR-1 Owner & user manual

Telex

Telex RADIOCOM BTR-1 Owner & user manual

S+S Regeltechnik Thermasgard ALTF 1 Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik Thermasgard ALTF 1 Operating Instructions, Mounting & Installation

Covidien Nellcor MAXN Instructions for use

Covidien

Covidien Nellcor MAXN Instructions for use

Novalynx 200-WS-02 Series user manual

Novalynx

Novalynx 200-WS-02 Series user manual

Baumer SmartReflect FNDK 14G6902/S14/IO quick start guide

Baumer

Baumer SmartReflect FNDK 14G6902/S14/IO quick start guide

Chauvet COLORstrip Footswitch user manual

Chauvet

Chauvet COLORstrip Footswitch user manual

Ankom Daisy II D200 Service Procedure

Ankom

Ankom Daisy II D200 Service Procedure

ABB ABB-free@home WBI-S-1-xx-WL Series product manual

ABB

ABB ABB-free@home WBI-S-1-xx-WL Series product manual

Hans Turck DR15S-IOL8X2 Series manual

Hans Turck

Hans Turck DR15S-IOL8X2 Series manual

Lifetime 1529 owner's manual

Lifetime

Lifetime 1529 owner's manual

Malmbergs TP001-ZA instruction manual

Malmbergs

Malmbergs TP001-ZA instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.