Napoleon GPV GAS POWER VENT User manual

1
W415-0682 / B / 06.10.10
$10.00
INSTALLATION
INSTRUCTIONS
INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE THIS TERMINAL IS SERVING.
CONSUMER: RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
THESE INSTRUCTIONS ARE TO BE USED IN CONJUNCTION WITH THE APPLIANCE AND PVA INSTRUCTIONS.
CERTIFIED
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 4Y8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
ID[ZZZQDSROHRQILUHSODFHVFRPDVN#QDSROHRQRQFD
ZZZFRQWLQHQWDOILUHSODFHVFRPDVN#FRQWLQHQWDOILUHRQFD
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.88 CSA 2.33 FOR VENTED GAS FIREPLACE HEATERS
AND ANSI Z21.50 CSA 2.22 FOR GAS FIREPLACES.
GENERAL INFORMATION
These Installation Instructions must be used in conjunction
with the appliance and appropriate PVA adapter kit Installation
Instructions. Clearances listed in these Instructions supersede
those in the appliance's Installation Instructions.
Power venting of direct vent appliances may result in the
reduction of efficiencies by as much as ten percent. Consider
this in making any venting and heating decisions in any
installation application.
SELECTING AND INSTALLING THE FIREPLACE
When selecting a gas appliance for use with the GPV, take into
consideration the various requirements and limitations in the
venting installation section for the following models:
Models Equipped with an Intermittent Pilot Ignition (I.P.I.)
It is recommended that the GPV be used with a gas appliance
equipped with an Intermittent Pilot Ignition (I.P.I.). Downward
vertical vent runs are permitted with an I.P.I. system. See
venting section in appropriate PVA Installation Instructions.
Models Equipped with Millivolt/ Standing Pilot
Downward vertical vent runs are not permitted with a standing
pilot system. See venting section in appropriate PVA Installation
Instructions.
INSTALLATION TO BE DONE BY A QUALIFIED INSTALLER
to conform with local codes. In absence of local codes install
to the current National Building Code in Canada or to regional
building codes in the United States. It must be electrically
connected and grounded in accordance with local codes. In
the absence of local codes, use the current CSA C22.1
CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA
70 NATIONAL ELECTRIC CODE in the United States.
The GPV operates on 120 VAC 60 HZ electrical service which is
supplied at the firebox junction box.
GAS POWER VENT
(GPV) The GPV is a Direct Vent Terminal
designed to allow installation of
gas appliances where typical vent
configurations cannot be achieved.

2
W415-0682 / B / 06.10.10
TABLE OF CONTENTS
1.0 VENTING 2
1.1 INSTALLATION OVERVIEW 3
1.2 VENT TERMINAL CLEARANCES 4
1.3 VENT LENGTHS 5
1.4 POWER VENT TERMINAL 5
1.4.1 TERMINAL INSTALLATION 5
1.4.2 POWER VENT INSTALLATION 6
1.4.3 INITIAL FIRING PROCEDURES 6
1.4.4 ELECTRICAL BOX INSTALLATION 7
1.5 RESTRICTOR PLATE INSTALLATION 8
1.6 WIRING DIAGRAM AND INSTALLATION 8
1.6.1 SIT IPI 885 PROFLAME COMPLETE WITH GPV POWER VENT TERMINAL 8
1.6.2 SIT MILLIVOLT 820 NOVA COMPLETE WITH GPV POWER VENT TERMINAL 10
1.6.3 SIT IPI 880/886 PROFLAME COMPLETE WITH GPV POWER VENT TERMINAL 11
1.6.4 DEXEN IPI 6003-3V COMPLETE WITH GPV POWER VENT TERMINAL 12
2.0 ADJUSTMENTS 13
2.1 VENTURI ADJUSTMENTS 13
3.0 REPLACEMENTS 13
4.0 TROUBLE SHOOTING 14
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
1.0 VENTING
There are specific adaptors and venting requirements for each appliance, refer to your power vent adaptor
leaflet for more information.
For complete installation instructions refer to the following web sites:
Manufacturer Website
Napoleon - English http://www.napoleonfireplaces.com/Tech/installation_manuals/installations.html
Napoleon - French http://www.napoleonfoyers.com/Fireplaces/powervent.html
Continental http://www.continentalfireplaces.com/fireplaces/gas/powervent.html

3
W415-0682 / B / 06.10.10
1.1 INSTALLATION OVERVIEW
A typical vent
configuration
Reducer, refer to
power vent
adapter kit (PVA)
for specific vent-
ing instructions
where applicable.
Gas Power
Vent Terminal
Electrical Box
(velcro to base)
LHD50 Illustrated
Firestop
Spacer
Frame Assembly Terminal
Access
Cover

4
W415-0682 / B / 06.10.10
INSTALLATIONS
CANADA U.S.A.
A12” 12” Clearance above grade, veranda porch, deck or balcony.
B12” Δ9” ΔClearance to windows or doors that open.
C12” * 12” * Clearance to permanently closed windows.
D18” ** 18” ** Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’ from
the center line of the terminal.
E12” ** 12” ** Clearance to unventilated soffit.
F0” 0” Clearance to an outside corner wall.
G0” 0” Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” 2” Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H3’ 3’ *** Clearance to each side of the center line extended above the meter / regulator assembly to a maximum
vertical distance of 15’.
I3’ 3’ *** Clearance to a service regulator vent outlet.
J12” 9” Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K6’ 3’ Clearance to a mechanical air supply inlet.
L7’ ‡ 7’ *** Clearance above a paved sidewalk or paved driveway located on public property.
M12” †† 12” *** Clearance under a veranda, porch or deck.
N12” 12” Clearance above the roof.
O2’ †* 2’ †* Clearance from an adjacent wall including neighbouring buildings.
P8’ 8’ Roof must be non-combustible without openings.
Q3’ 3’ See chart for wider wall dimensions.
R6’ 6’ See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open-
ing between the terminal and the open side of the structure.
S12” 12” Clearance under a covered balcony
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to maximize the distance to vinyl clad soffits.
*** This is a recommended distance. For additional requirements check local codes.
‡ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
12.2B
R
QS
GP
COVERED BALCONY APPLICATIONS ††*
QMIN
RMAX
MAX
R
= 3 feet
= 2 x
feet
QACTUAL
1.2 VENT TERMINAL CLEARANCES

5
W415-0682 / B / 06.10.10
1.3 VENT LENGTHS
REFER TO POWER VENT ADAPTER KIT (PVA) FOR SPECIFIC VENTING INSTRUCTIONS
1.4 POWER VENT TERMINAL
1.4.1 TERMINAL INSTALLATION
20.4
A. Remove the electrical access plate from the frame assembly, then remove the
knock out from this plate.
B. Insert the wiring through the electrical access plate and engage the conduit bush-
ing. Re-secure this plate. NOTE: The GPV includes a 20 foot wire
harness cable. If this cable does not reach the appliance, then it
may be cut and a splice added. These connections must conform
with local codes or, in the absence of local codes, use the current CSA
C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA 70
National Electrical Code in the United States.
C. Remove terminal access cover, see “INSTALLATION OVERVIEW” for
location and route cable through terminal.
D. Assemble gas power vent terminal to frame assembly.
E. Connect the male and female connectors.
F. Replace terminal access cover.
NOTE: Where possible, it is strongly recommended to have an access panel inside the building for
servicing the unit.
This application occurs when venting through an exterior wall. Having determined the correct
height for the terminal location, cut and frame a hole in the exterior wall as illustrated to ac-
commodate the GPV.
DETERMINE
THE
CORRECT
HEIGHT
11 1/4”
10 1/4”
ELECTRICAL
ACCESS PLATE TERMINAL
FEMALE
MOLEX
CONNECTOR
MALE MOLEX
CONNECTOR

6
W415-0682 / B / 06.10.10
1.4.2 POWER VENT INSTALLATION
23.6
A. Stretch the inner flex pipe to the required length taking
into account the additional length needed for the fin-
ished wall surface. Slip the vent pipe a minimum of 3”
over the inner sleeve of the terminal and secure with 3
#8 screws. Apply a heavy bead of the high temperature
sealant W573-0007 Mill Pac (not supplied).
B. Using the outer flex pipe, slide over the outer combus-
tion air sleeve of the terminal and secure with 3 #8
screws. Seal using high temperature sealant W573-
0002 (not supplied).
C. Apply a bead of caulking (not supplied) to the framed
opening and secure the terminal. Ensure the arrows
stamped into the frame assembly are pointing upwards.
NOTE: For firestop spacer installation instructions,
see PVA kit or the appliance Installation Manual.
D. Route venting through framed opening and firestop spacer to the
appliance.
E. The terminal mounting plate may be recessed into the exterior
wall or siding no greater than the depth of its return flange.
F. If more vent pipe needs to be used to reach the appliance, couple
them together as illustrated. The vent system must be supported
approximately every 3 feet for both vertical and horizontal runs.
Use noncombustible strapping to maintain the minimum clearance
to combustibles.
G. Install the reducer (if required) or vent and properly secure and
seal to the unit using high temperature sealant
W573-0007 Mill Pac (not supplied). HI-TEMP
SEALANT
#8 X 1/2” SELF DRILLING
SCREWS & WASHERS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE INNER
FLEX PIPE
OUTER
FLEX PIPE
TERMINAL
CAULKING
FIRESTOP
SPACER
#10 X 2”
SCREWS
HIGH
TEMPERATURE
SEALANT
RETURN
FLANGE
1.4.3 INITIAL FIRING PROCEDURES
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGE SHOULD BE PERFORMED BY A QUALI-
FIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT THE BURNER BE-
FORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION.
In some instances the system may not light pilot/burner with the door open/removed. Partially blocking the
exhaust flue collar will allow the safety pressure switch to activate and allow gas flow to the pilot during the
initial test firing.

7
W415-0682 / B / 06.10.10
1.4.4 ELECTRICAL BOX INSTALLATION
NOTE: Before finishing in the appliance, the power vent must be installed.
A. Start by removing the pre-finishing access panel or opening lower louvre.
B. Position the Power Vent Control Module in a convenient location (not on top of the heat shield in the
LHD50) and Velcro it to the base of the appliance.
C. Slide the 20’ power vent cable through the right side of the appliance and connect the box connector to
the side panel, see “INSTALLATION OVERVIEW” section for illustration.
D. Feed the wires through the inside panel, slide the split bushing over the coated wires and snap into
the 7/8” hole to protect the wires as illustrated. Attach the connections as per the appropriate wiring
diagram. See “WIRING DIAGRAM AND INSTALLATION” section.
POWER VENT
CONTROL
MODULE
BX SNAP
BUSHING
LHD50 Illustrated
20’ POWER
VENT CABLE
SPLIT BUSHING
REQUIRED

8
W415-0682 / B / 06.10.10
1.5 RESTRICTOR PLATE INSTALLATION
1.6 WIRING DIAGRAM AND INSTALLATION
Connect the wiring to the power vent termination as outlined in the previous section, and connect the wiring
to the appliance as outlined in the schematic below. Ensure that the proper clearances are maintained for the
wiring and conduit. When installing the wiring it must never run above the vent run and it must be a minimum 1”
from all venting.
NOTE: The GPV includes a 20 foot wire harness. If this harness does not reach the appliance, then it
may be cut and a splice added. These connections must conform with local codes or, in the absence
of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA 70
National Electrical Code in the United States.
REFER TO PVA KIT FOR APPLIANCE SPECIFIC INSTRUCTIONS.
1.6.1 SIT IPI 885 PROFLAME COMPLETE WITH GPV POWER VENT TERMINAL
1. Disconnect the wires labeled ON/OFF (White/Green) and TH (Green). Reconnect them to the
corresponding male/female connectors on the Power vent control module.
2. Disconnect the two D/C (Red/Black) wires from each other and reconnect them to the corresponding D/C
connectors on the Power vent control module.
3. Disconnect the Orange wire from the gas valve and reconnect it to the Yellow wire (female connector) from
the Power vent control module.
4. Connect the remaining Yellow wire (male connector) from the Power vent control module to the tab on the
gas valve where the Orange wire was removed.

9
W415-0682 / B / 06.10.10
IPI Board
SPARK
ELECTRODE
FLAME
SENSOR
SIT Valve
Electronic Ignition
BLACK 3/16
CONNECTION
BLACK 1/8
CONNECTION
TUBE
GREEN
ORANGE
YELLOW / GREEN
YELLOW / GREEN
IPI / CPI (ACS)
SWITCH
(OPTIONAL)
RED / FCM-COM
BLUE
PINK
BLACK
WHITE / TPTH
BLACK / DC SUPPLY
RED / DC SUPPLY
GREY / FCM-COM
PURPLE / FCM-COM
COM
120 VOLT FAN AUX OUT
ORANGE / MOTOR
YELLOW / MOTOR
BLACK / MOTOR
BROWN / MOTOR
WHITE
Receiver
Control
Module
POWER
Pilot Assembly
WHITE / GREEN /
ON/OFF
BLACK
RED
IMPORTANT: IF USED,
IT MUST BE
CONNECTED TOA 6
VOLT BATTERY PACK,
HOWEVER MUST NOT
BE USED WHEN USING
THE REMOTE
CONTROL RECEIVER
PLUG
INTO
120 VOLT
Power
Vent
Control
Module
BLACK
WHITE
YELLOW
YELLOW
BLOWER
VAC SWITCH
GREEN
GPV Terminal
SPLIT FLOW
(IF INCLUDED
WITH APPLIANCE)
GREEN / TH
BLACK / DC SUPPLY
RED / DC SUPPLY
Pull connectors apart to
connect to power vent
YELLOW
YELLOW
1
2
3
4

10
W415-0682 / B / 06.10.10
1.6.2 SIT MILLIVOLT 820 NOVA COMPLETE WITH GPV POWER VENT TERMINAL
PILOT
BURNER
THERMOCOUPLE
THERMOPILE
RED
WHITE
BLACK
WHITE
ORANGE
RED
YELLOW
YELLOW
GREEN
Pilot Assembly
SIT Millivolt Gas Valve
Double Pole
Switch
BLACK
WHITE
YELLOW
YELLOW
BLOWER
VAC SWITCH
GREEN
GPV Terminal
Power Vent
Control
Module
Appliance
Junction Box
JUMPER
2
1
NOTE: Must use double pole switch (supplied) or double pole thermostat (not supplied) with specific
power vent adaptor kit.
1. Connect the jumper wire to tabs 1 and 3 on the gas valve.
2. Connect the jumper wire to the two Yellow wires from the Power vent control module.

11
W415-0682 / B / 06.10.10
1.6.3 SIT IPI 880/886 PROFLAME COMPLETE WITH GPV POWER VENT TERMINAL
ACS/IPI
SWITCH
(OPTIONAL)
DC BACK-UP
(NOT ALLOWED
WITH GPV
INSTALLATION)
GROUND
DFC
VALVE
ORANGE GREEN
GROUND
EYELET
IPI / CPI
+
+
-
-
IPI BOARD
DC SUPPLY
TRANSFORMER
VALVE
ELECTRONIC
BLACK
WHITE
ORANGE
RED
GREEN
Power
Vent
Control
Module
Appliance
Junction Box
BLACK
WHITE
YELLOW
YELLOW
BLOWER
VAC SWITCH
GREEN
GPV Terminal
Double Pole
Switch
YELLOW
YELLOW
JUMPER
2
1
NOTE: Must use double pole switch (supplied) or double pole thermostat (not supplied) with specific
power vent adaptor kit.
1. Connect the jumper wires to the wire labeled ON/OFF (Green/White) and the wire labelled TH (Green).
2. Connect the other end of the jumper wires to the Yellow wires from the Power vent control module.

12
W415-0682 / B / 06.10.10
1.6.4 DEXEN IPI 6003-3V COMPLETE WITH GPV POWER VENT TERMINAL
NOTE: Must use double pole switch (supplied) or double pole thermostat (not supplied) with specific
power vent adaptor kit.
1. Connect the Brown wires from the Ignition module to the yellow wires from the Power vent control
module.
Dexen Gas Valve
Ignition Module
Battery
Holder
Battery
Relay
ORANGE
YELLOW
GREEN
BLACK
ORANGE
BLUE
RED
BROWN
BROWN
BLUE
BLACK
YELLOW
YELLOW
BLACK
WHITE
ORANGE
RED
GREEN
Ignitor
Power
Vent
Control
Module
Appliance
Junction Box
BLACK
YELLOW
BLACK
WHITE
YELLOW
YELLOW
BLOWER
VAC SWITCH
GREEN
GPV Terminal
Double Pole
Switch
1

13
W415-0682 / B / 06.10.10
2.1 VENTURI ADJUSTMENTS
2.0 ADJUSTMENTS
REFER TO PVA KIT FOR SPECIFIC APPLIANCE INSTRUCTIONS.
3.0 REPLACEMENTS
Contact your dealer or the factory for questions concerning prices and policies on replacement parts. Normally
all parts can be ordered through your Authorized dealer / distributor.
FOR WARRANTY REPLACEMENT PARTS, A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE
REQUIRED TO HONOUR THE CLAIM.
When ordering replacement parts always give the following information:
• Model & Serial Number of appliance
• Installation date of appliance
• Part number
• Description of part
• Finish
* IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED. FOR
FURTHER INFORMATION, CONTACT YOURAUTHORIZED DEALER. 41.1
FAILURE TO POSITION THE PARTS
IN ACCORDANCE WITH THIS
MANUAL OR FAILURE TO USE ONLY
PARTS SPECIFICALLY APPROVED
WITH THIS APPLIANCE MAY
RESULT IN PROPERTY DAMAGE OR
PERSONAL INJURY.
!
WARNING
COMPONENTS
REF GPV PART NO. DESCRIPTION
1 W062-0026 BLOWER
2 W660-0056 SWITCH, VACUUM
3* W750-0195 WIRE HARNESS, TERMINAL
4* W750-0209 20’ WIRE HARNESS CABLE FROM UNIT TO TERMINAL
5 W010-1924PW PEWTER MAIN BODY
6 W010-1925PW PEWTER FRAME
7 W290-0138 BLOWER GASKET
8 W500-0400 BLOWER MOUNTING PLATE
9 W200-0256PW PEWTER ACCESS COVER
10 W500-0419 DILUTION AIR PLATE
11* W345-0008 HOSE
2
1
9
87
10
5
6

14
W415-0682 / B / 06.10.10
SYMPTOM PROBLEM TEST SOLUTION
Main burner flame is
a blue lazy transpar-
ent flame.
Leak in exhaust vent. - Check exhaust vent pipe and all connection seals.
Incorrect installation. - Refer to PVA kit for appliance specific restrictor.
Carbon is being
deposited on glass or
combustion chamber
surfaces.
Air shutter has become blocked
or incorrect setting.
- Ensure air shutter opening is free of lint or other
obstructions or has correct setting.
Flame is impinging on the logs
or combustion chamber.
- Check that the media is correctly positioned.
- Open air shutter to increase the primary air.
- Check the input rate: Check the manifold
pressure and orifice size as specified by the rating
plate values.
- Check that the door gasket is not broken or
missing and that the seal is tight.
- Check that both 4" and 7" vent liners are free of
holes and well sealed at all joints.
- Check that the proper restrictor is used
White / Grey film
forms.
Sulphur from fuel is being de-
posited on glass, logs or com-
bustion chamber surfaces.
- Clean the glass with a gas appliance glass
cleaner. DO NOT CLEAN GLASS WHEN HOT.
- If deposits are not cleaned off regularly, the glass
may become permanently marked.
Exhaust fumes
smelled in room,
headaches.
Fireplace is spilling. - Check door seal and relief flap seal.
- Check for proper restrictor.
- Check that the paint curing process is complete.
Main burner will not
light.
Main door is not installed. - Install main door.
Main burner flames
are very aggressive.
No restrictor. - Add restrictor.
Main burner won’t
light.
Vacuum switch not activated. - Remove blockage. In really cold conditions, ice
buildup may occur on the terminal and should be
removed as required.
- Test vacuum switch and replace as required.
4.0 TROUBLE SHOOTING
IMPORTANT: Prove all systems check before completely enclosing unit.
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPEN OR REMOVED.
IN SOME INSTANCES THE SYSTEM MAY NOT LIGHT PILOT/BURNER WITH THE DOOR OPEN/
REMOVED. PARTIALLY BLOCKING THE EXHAUST FLUE COLLAR WILL ALLOW THE SAFETY
PRESSURE SWITCH TO ACTIVATE AND ALLOW GAS FLOW TO THE PILOT DURING THE INITIAL
TEST FIRING.

15
W415-0682 / B / 06.10.10
44.1
5.0 NOTES

16
W415-0682 / B / 06.10.10
44.1
Other manuals for GPV GAS POWER VENT
1
Table of contents
Other Napoleon Ventilation Hood manuals
Popular Ventilation Hood manuals by other brands

Broan
Broan Elite E64000 SERIES installation instructions

Best
Best UP27M series user manual

AEG
AEG DBE5661HG user manual

KOBE
KOBE IS2336SQB-DC16-1 Installation instructions and operation manual

Greentek
Greentek SOLACE Series Installation and operation manual

Thermador
Thermador HGEW 36 FS use and care manual