
Activating ERS 20 can be performed via the start guide or
directly in the menu system.
The main product’s software must be the latest version.
Caution
Also see the Installer Manual for the main product.
Start guide
The start guide appears upon first start-up after heat pump
installation, but is also found in menu 7.7.
Menu system
If you do not make all settings via the start guide or need to
change any of the settings, this can be done in the menu
system.
MENU 7.2.1 -ADD/REMOVE ACCESSORIES
Activating/deactivating of accessories.
Select "ERS S10/20/30 1" - "ERS S10/20/30 8".
MENU 7.2.11 - VENT. HEAT EXCHANGER (ERS)
Lowest extract air temp.
Setting range: 0 – 10 °C
Product
Setting range: ERS10, ERS20/ERS30
Action level monitor
Setting range: Level monitor/Blocked/Off
Lowest extract air temp.: Set the lowest extract air temper-
ature to prevent the build-up of ice on the heat exchanger.
Action level monitor: ERS 20 has a built-in level monitor, and
the fans stop when the input is interrupted. When "Level
monitor" is selected, the product issues an alert when the
input is interrupted; when "Blocked" is selected, text is dis-
played instead in operating info.
MENU 1.2.1 - FAN SPEED
Alternatives: normal and speed 1 – speed 4
The ventilation in the accommodation can be temporarily
increased or reduced here.
When you have selected a new speed a clock starts a count
down. When the time has counted down the ventilation
speed returns to the normal setting.
If necessary, the different return times can be changed in
menu 1.2.5.
The fan speed is shown in brackets (in percent) after each
speed alternative.
MENU 1.2.2 - NIGHT COOLING
Night cooling
Setting range: on/off
Start temp exhaust air
Setting range: 20 – 30 °C
Min. diff. ind. temp. - outd. temp.
Setting range: 3 – 10 °C
Night cooling during heating
Setting range: on/off
Here, you can activate night cooling. When the temperature
in the house is high, and the outdoor temperature is lower,
a cooling effect can be obtained by forcing the ventilation.
When night cooling is activated, the fans run at the speed
4. For activated night cooling, the bypass damper (QN37) is
open.
Start temp exhaust air: Here, you set the exhaust air tem-
perature at which night cooling will start.
Min. diff. ind. temp. - outd. temp.: If the temperature differ-
ence is greater than the set value for "Min. diff. ind. temp. -
outd. temp.", and the exhaust air temperature is higher than
the set value for "Start temp exhaust air", the ventilation
operates at speed 4 until one of these conditions is no longer
valid.
Night cooling during heating: It is possible to have night
cooling during the time heating is permitted.
MENU 1.2.5 - FAN RETURN TIME
speed 1 – speed 4
Setting range: 1 – 24 h
Here, you select the return time for the temporary change
of ventilation speed (speed 1 – speed 4), regardless of
whether the speed has been changed in menu 1.2.1 - "Fan
speed", via the home screen or via myUplink.
Return time is the time it takes before the temporary ventil-
ation speed returns to normal speed.
MENU 1.2.6 - FILTER CLEANING INTERVAL
Months between filter cleaning
Setting range: 1 – 24 months
The filters in ERS 20 are of a type that should not be cleaned;
they have to be replaced instead. These must be replaced
regularly, although how often depends of factors such as
the amount of particles in the ventilation air. Test to find
out what is most appropriate for your installation.
15Chapter 7 | Activating ERS 20NIBE ERS 20-300
S
Activating ERS 20