Strain relief & cover
Make sure all cables are properly secured
and the protection cover is placed back
over the terminals.
Power ON
Make sure to close the enclosure before
connecting the AC mains.
If powered devices are not working properly
please check if the DC output is 13.2 V.
The DC output can be adjusted with the
Voltage adjuster.
AC mains input
-V +V
Live
(brown)
AC mains
Neutral
(blue)
L N
3 x 0.75 mm², earth connection, max. 2 m
Make sure that the AC mains (230-240 VAC)
is NOT connected!
Shield & earth
-V +V
Shield
AC mains DC output
Earth wire
(green-yellow)
The protective earth wire should be the
last to disconnect in the event of an
inadvertent pull on the power cord.
DC output
1
2
3
-V +V
GND Vin
DC output
2 x 0.5 mm2 shielded, max. 5 m
Remove the protection cover from the
terminals before wiring.
A
B
DC outputAC mains input
Power LED
Voltage adjusterL N -V +V
Protection cover
13 2
5
4
5
Wiring specications
Purpose
A. AC mains input wiring
B. DC output wiring
Specification
3 x 0.75 mm², earth connection, max. 2 m
2 x 0.5 mm2 shielded, max. 5 m
Failure to comply with the wiring specifications may result in
malfunction and/or dangerous situations.
Instructions
Step
1.
2.
3.
4.
5.
DC output
Shield & earth
AC mains input
Strain relief & cover
Power ON
Remarks
Default output is 13.2 V.
Connect shield and earth wire at the same time to the same terminal.
Make sure the AC mains input is still disconnected at this point.
Use the available provisions to secure all cables.
Make sure the protection cover is put back over the terminals.
Before installing or servicing this device
please read and take the ‘Safety precautions’
into account. These can be found on the
backside of this installation guide.
Conductors connected to the screw
terminals must be fitted with a ring,
crimped lugs, etc. so that reliance is not
placed upon the screw alone.

Document information
Date
Version
Part number
March 19, 2020
5
5283507
This information is furnished for guidance, and with no guarantee as to its
accuracy or completeness; its publication conveys no licence under any patent
or other right, nor does the publisher assume liability for any consequence of
its use; specifications and availability of goods mentioned in it are subject to
change without notice; it is not to be reproduced in any way, in whole or in
part, without the written consent of the publisher.
info@nedapsecurity.com
www.nedapsecurity.com
+31 (0) 544 471 111
Nedap Security Management
Parallelweg 2
NL-7141DC Groenlo
The Netherlands
© 2020 Nedap N.V. All rights reserved.
Install movie
Opening enclosure
2
3
4
Tool ø< 5 mm
1
Mounting
60
ø5(3x)
12.5
113.5
19
120
DIN rail 35 x 7.5mm Drill pattern
All dimensions are in millimeters (mm).
Preferred screws: 4.8 x 32 mm (DIN7981)
Certications
This equipment is tested and conforms with the essential requirements of
Electromagnetic Compatibility Directive 2004/108/EC: EN50130-4 (2011), EN55022
(2010) + AC(2011); and Low Voltage Directive 2006/95/EG: EN60950-1 (2006) +
A11(2009) + A1(2010) + A12(2011) + AC(2011) + A2(2013).
LED indication
Colour
Green
Description
DC output active
Power LED (internal)
General
Safety precautions
This equipment should be accessible, installed, operated, serviced, and repaired by qualified personnel
only. The installation and interconnection of this equipment to facility wiring and other equipment must
be done by a competent, qualified craftsperson who is familiar with applicable standards and codes
governing the installation.
Installation methods, practices, or procedures that are unauthorised or done improperly are dangerous
and could result in serious personal injury or damage to property and equipment
Warning
Power Supply: Ensure the source voltage matches the voltage of power supply before turning ON the
power.
Power Cord and Plug: To prevent an electric shock or fire, be sure to use the power cord as described
below:
Maximum 4.5 m long, rated minimum 250 V, 10 A, Type SJT flexible cord. One end terminates with
tandem blade (240V units) grounding, molded-on, attachment plug with a 10 A, 240 V 3-pole
configuration. Cord and plug should have CE approval.
The socket-outlet shall be installed near the equipment and shall be easy accessible.
Fixed Power Connection: In the case of a fixed connection to the mains, a disconnect from mains must
be available near the equipment.
Protective Grounding: The protective grounding terminal must be connected to ground to prevent an
electric shock before turning ON the power.
Fuse: For continued protection against risk of fire replace fuses only with the same type and rating of
fuse.
Before replacing the fuses, turn off the power and disconnect the power source. Do not use a different
fuse or short-circuit the fuse holder.
Do Not Operate Near Flammable Materials: Do not operate the equipment in the presence of flammable
liquids or vapors. Operation of any electrical equipment in such environment constitutes a safety
hazard.
Opening the covers: Do not open the top cover when active since lethal voltages do exist inside. Always
first disconnect from mains supply and make sure maintenance is safe.
Do Not Modify: To be sure of safety, do not modify or add anything to the equipment other than
mentioned in this installation guide or indicated by NEDAP NV.
Technical specications
Dimensions230 x 165 x 65 mm (H x W x D)
WeightApprox. 820 g
Enclosure PC ABS
Temperature range Operation: 0°C to 40°C
Storage: -30°C to 65°C
Relative humidity20% to 90% (non-condensing)
AC mains input230-240 VAC, 50/60 Hz, 1.2 A
DC output13.2 VDC SELV, 4.5 A
AC mains input wiring3 x 0.75 mm², earth connection, max. 2 m
DC output wiring2 x 0.5 mm² shielded, max. 5 m
Safety Class I