SKG Steam Humidifier
BACnet® Communication Module User Guide
8
SKG Humidifier Object Table
The SKG Humidifier use the following BACnet object table. The type is the BACnet Object type, the instance is
the BACnet Object instance. W? indicates whether the Present_Value property is writable. Together the type
and instance form the BACnet Object_Identifier for an object according to the following C-language algorithm:
•object_identifier=(unsigned long)((unsigned long)type<<22)+instance
Object instances are assigned according to the following scheme:
•The Object instance for the Device Object is 153000 by default. This value can be reprogrammed from
between 0 and 4194302 as needed to insure uniqueness system-wide
•For the Properties that are Common for all SKG Models, the Object instances range from 1 to 99 as
needed.
•For the Tank Properties, the Object instances range from 101 to 199 for Tank 1, 201 to 299 for Tank 2,
301 to 399 for Tank 3 and 401 to 499 for Tank 4 as needed.
Common for all SKG Models:
type inst Object_Name Description range of Present_Value W?
AI 1 Humidity_Out Humidity Output 0-100 %RH
type inst Object_Name Description range of Present_Value W?
AV 1 Humidity_Demand Humidity Demand 0-100 %RH W
AV 2 Room_Humidity Room Humidity 0-100 %RH W
AV 3 Room_Humidity_Off Room Humidity offset ±0-10.0 %RH W
AV 4 Duct_Humidity Duct Humidity 0-100 %RH W
AV 5 Duct_Humidity_Off Duct Humidity offset ±0-10.0 %RH W
AV 6 Outside_Temp Outside Temperature -40 - 40 °C or -40 - 104
°F W
AV 7 Lock_On_Capacity Lock On capacity 10-100% W
AV 8 Max_Output_Limit Maximum output limit 10-100% W
AV 9 Drain_Delay Drain Delay 1-100Hrs W
AV 10 Service_Delay Service Delay 1-5000Hrs W
AV 11 End_Season_Delay End of season delay 1-250Hrs W
AV 12 PID_Loop_KP PID Loop gain KP 0-255 W
AV 13 PID_Loop_KI PID Loop gain KI 0-255 W
AV 14 PID_Loop_KD PID Loop gain KD 0-255 W
AV 15 Ctl_Band Control band
0-20.0% (0..200) W
AV 16 Ctl_SP Control set point 0-100%RH W
AV 17 Extern_SP_Min External setpoint minimum 0-100%RH W
AV 18 Extern_SP_Max External setpoint
maximum 0-100%RH W
AV 19 Duct_Hum_HiLim_SP Duct hum. high limit set
point 50-100%RH W
AV 20 Min_ON_Time_Fan Minimum ON time for fan 2-20 minutes W
AV 21 Min_H2O_Temp Min. water temp. in ON
mode 50-90 °C or 122-194 °F
(0 -> Mode is Off) W
AV 22 Antifreeze_Temp Anti-freeze mode
temperature 7-12 °C or 44-54 °F (0 ->
Mode is Off) W
AV 23 Analog_Ctl_In_Lo Analog Control input Lo
Limit 0-10.00VDC W
AV 24 Analog_Ctl_In_Hi Analog Control input Hi
Limit 0-10.00VDC W
AV 25 Analog_Hum_In_Lo Analog Humidity input Lo
Limit 0-10.00VDC W
AV 26 Analog_Hum_In_Hi Analog Humidity input Hi
Limit 0-10.00VDC W
AV 27 Analog_Duct_In_Lo Analog Duct input Lo Limit 0-10.00VDC W
AV 28 Analog_Duct_In_Hi Analog Duct input Hi Limit 0-10.00VDC W