2. A power source wiring
1. For an electric shock prevention to turn on electricity to the machinery and tools which
after one sees a protective ground connection surely.
2. To the electric wire terminal to use the insulation sleeve compression terminal.
3. The device's power supply voltage to match the voltage of the power is in check.
4. For the protection of life to turn on an electric current to the instrument after
attaching the cover.
1. To all the member front line 600V vinyl insulation front lines (JIS C3307), or to use the
front line of above considerable width.
2. To the protective ground terminal to connect above of 3rd type(to connect below earth
resistance 100Ω and smallest size 1.6㎜).
3. Other protection devices and grounding, the grounding in public may be affected by
noise. Accordingly the public are advised not to other devices.
Pressure range from 0.0~0.1 to 0.0~500.0bar.
Compact size and robust construction.
Range ability in the ratio of 5:1
Built-in multiple function.
Zero trim function.
4 Digit LCD & FND for parameter alteration and
PV output on the spot.
IP-67
1. Input Type
2. Measuring and displaying interval : 100ms
3. CMRR(Common Mode Rejection Ratio) : 140dB or more
4. NMRR(Normal Mode Rejection Ratio) : 60dB or more
5. Moving average filter (1~99)
6. Power : DC 9~35V
7. Accuracy : ±0.25% FS
8. Output : DC 4.00~20.00㎃
9. Load limit : (Vsp9V) 0.022=RΩ
10. Vibration(20..5000㎐) : 20㎐
11. Diaphragm : SUS316L
12. Oil Filling : Silicon Oil
13. Dead Volum change @25℃ < 0.1mm ≥ /FS
14. Sensor Operating Temperature : -30~100℃
15. Operating condition
Operating Temp/Humidity : -30~70℃, 10~90%
Storage Temp/Humidity : -30~70℃, 10~90%
16. etc
Weight : 200g
Body material : Aluminum (ALDC, 8S)
Degree of protection : IP-67
Process Connection : PT 1/2
1. Unit function(
)
- Set the unit user.
- mmH2O, Pa, Bar
2. Sensor compensation function(
)
- The function is useful for compensating error by long sensor line or changed zero point by
aged sensor.
Ex) Before sensor adjust = 5.10bar
After sensor adjust
= measured value + compensated value
= 5.10 - 0.10
= 5.00bar
측정치
5.10
보정후
5.10-0.10
=5.00
-0.10
보정치
0 0 0 0S - A D
3. Cut-Off function(
)
- This function is used when you want to indicate the indicated value as 0.00 up to a
specific indication value
0
2.50
5.00
10.00
6.00 12.00 20.00
bar
mA
Cut-off : 2.50
Indication value ZERO notation
output current(Fixed at 4.00 mA)
0.0~2.0bar(Absolute pressure)
0.0~5.0bar(Absolute pressure)
0.0~20.0bar(Absolute pressure)
Before
5.10
After
5.10-0.10=5.00
-0.10
Compensated Value