newins NT5400E Series User manual

7
NT5400E series
Explosion Protected Type
2
-
Wire Temperature Transmitter
http://www.newins.co.kr
WARNING / CAUTION / NOTE
1. Checking the
Accessories
2
. Part Name
3. Installation
4.
Terminal Diagram
5.
Features
6
. General Specification
7
. Major Function
8
. Operation and Setting Mode
9
. Ordering Code
contents

※ Be sure to observe following warning / cautions and those provided in the text.
In order to secure safety in handing the instrument.
WARNING
General
‣ In order to prevent electric shock, be sure to disconnected this
instrument from the main power source when wiring.
Protective
Grounding
‣ In order to prevent electric shock ; be sure to provided protective
grounding prior to turning on this instrument.
Do not cut a protective grounding conductor disconnected
protective grounding.
Power
Source
‣ Make sure that the supply voltage for this instrument conforms to
the voltage source.
‣ Attach protective cover prior to turning on this instrument.
Fuse
‣ In order to prevent a fire, use only our specified fuse.
‣ Don't short-circuit a fuse.
Working
Environment
‣ Do not operate this instrument in the environment where it is
exposed to a combustible, explosive, corrosive gas or water, steam.
Input and
Output
wiring
‣ Provide input and output wiring after turning off the power.
CAUTION
Inside of
instrument
‣ Do not disassemble the inside of the instrument.
‣ Prevent inflow of dust, water, oil and wiring dregs in to the
instrument.
Input and
Output wiring
‣ Do not use empty terminals for other purposes such as
relaying, etc.
‣ Wire correctly after checking the polarity and purpose of the
terminal.
‣ When wiring the instrument, separate from high voltage
cables, power lines, and motor lines to prevent inductive noise.
Transportation
‣ When transporting this instrument or the equipment with this
instrument incorporated in it, take measures to prevent
opening the door and falling out the inner module.
NOTE
Instruction
manual
‣ Deliver this instruction manual to an end user.
‣ prior to handing the instrument be sure to read this manual.
‣ If you have any question on this manual or fine any errors
omissions in this manual, contact our sales representative
‣ After reading this manual, keep it carefully by the instrument.
‣ When the manual, is lost or stained, contact our sales
representative.
‣ It is prohibited to copy or reproduce this manual without our
permission.
Checking the
accessories
‣ Upon delivery instrument, unpack and check its accessories and
appearance. if there are missing accessories or damage on the
appearance contact our dealer where you purchased the
instrument or our sales representative.
Installation
‣ When installing this instrument, put on a protective gear such
as safety shoes, helmet, etc. for your safety.
Maintenance
‣ Only our serviceman or persons authorized by NEWINS are
allowed to remove and take the inner module, the main unit
and printed circuit boards apart.
Disposal
‣ Disposed the used products in a correct way.
‣ Do not incinerate plastics of m
aintenance parts and
replacement parts. A harmful gas mat be produced.
‣
To dis
posed of this instrument, consign to the special agent as
an industrial waste.
Cleaning
‣ Use dry cloth to clean the surface of this instrument
‣ Do not use any organic solvent.
‣ Cleaning the instrument after turning off the power.
Revisions
‣ This instruction manual is subject to change without prior
notice.
Evasion of
responsibility
guarantee
‣ Be sure to observe the caution in operating, maintaining, and
repairing this instrument. We will not be responsible for or
guarantee the damage resulting from negligence of
them.

3
2
4
5
MODE
5 4 0 0
NEWINS
EXIT
1
1.
Checking the Accessory
when you received, please check the Insufficient accessories and defective products shape.
If the lack of parts, please contact the company.
Transmitter
User manual
2. Part Name
① Measured value display
②
MODE
: Storage the set data and change the operation menu
③ : Enter into the data setting mode and modify the changed location
④ : Change the data value
⑤
E X I T
: Out of mode
3. Installation
Outside dimension
---
Transmitter
---
Temperature Sensor

Power Supply
DC 24V
1
20Ω
+ -
INDICATOR
CONTROLLER
CONVERTER
RECORDER
TRANSMITTER
4.00~20.00mA
+
-
+
-
2
3FG
2-Wire System
5. Terminal Diagram
1. Terminal wiring
2. A power source wiring
1. For an electric shock prevention to turn on electricity to the machinery and tools which
after one sees a protective ground connection surely.
2. To the electric wire terminal to use the insulation sleeve compression terminal.
3. The device's power supply voltage to match the voltage of the power is in check.
4. For the protection of life to turn on an electric current to the instrument after
attaching the cover.
Caution
1. To all the member front line 600V vinyl insulation front lines (JIS C3307), or to use the
front line of above considerable width.
2. To the protective ground terminal to connect above of 3rd type(to connect below earth
resistance 100Ω and smallest size 1.6
㎜
).
3. Other protection devices and grounding, the grounding in public may be affected by
noise. Accordingly the public are advised not to other devices.
Attention
5. Features
1. Multi-Range input(TC, RTD, Volt, mV, mA, Etc)
2. High accuracy 16bit A/D converter
3. Selectable moving average filter
4. Built-in multiple function
5. DC 4.00~20.00mA 2-wire loop power
6. 4 Digit LCD for parameter alteration and PV output on the spot.
6. General Specification
1. Input Type
Multi range input -Free input selection by code
Sensor Type
Range
Scale
Simbol
TC
B(PR 30%)
0~1800℃
-
TC-B
R(PR 13%)
0~1750℃
-
TC-R
S(PR 10%)
0~1750℃
-
TC-S
K(CA)
-200~1350℃
-
TC-K
E(CRC)
-200.0~700.0℃
-
TC-E
J(IC)
-199.9~800.0℃
-
TC-J
T(CC)
-199.9~400.0℃
-
TC-T
Volt
mV
-100.0~100.0
mV
-1999~9999
MV
Volt
-10.0~10.0V
-1999~9999
V
mA
mA
4.00~20.00
mA
-1999~9999
MA
PT
Pt100Ω
-199.9~800.0℃
-
D-PT
JPt100Ω
-199.9~800.0℃
-
J-PT
※ mA input needs 20Ω 0.05% 25ppm resistance spiral on outside
2. Measuring and displaying interval
200ms(mV, Volt, mA type)
400ms(TC, RTD type)
3. Input resistance : Volt type 400kΩ, Other type 1MΩ
4. Signal source resistance
PT100Ω..30Ω/Line, Others type 300Ω/Line
5. CMRR(Common Mode Rejection Ratio) : 140dB or more
6. NMRR(Normal Mode Rejection Ratio) : 60dB or more
7. Moving average filter : Selectable(None 4, 8, 16)
8. Accuracy : ±0.25% FS
9. Power : DC 9~35V
10. Output : 2-wire DC 4.00~20.00mA
: load limit(Vsp9V)/0.022=RΩ
11. Operating condition
Operating Temp/Humidity : -20~60℃, 0~100% RH
Storage Temp/Humidity : -20~70℃, 5~95% RH
12. Body material : SUS 304 (Ex d ⅡC T6)
13. Degree of protection : IP-65
14. Weigh : 1.5kg
Mounting : Filed Mount

7.00
3.50
0.00
4.00 12.00 20.00
m
mA
Setting to
Sensor Type :
High Range : 20.00
Low Range : 4.00
High Scale : 7.00m
Low Scale : 0.00m
20.00
12.00
4.00
0.00 3.50 7.00
mA
m
Setting to
High Out Scale : 7.00m
Low Out Scale : 0.00m
Before
510
After
510-10=500
-10
Compensated Value
OUT
Y = X
IN
If X > 0
Y = √{(pv-low scale)
x (high scale-low scale)}
+ low scale
If X <= 0 Y = 0
PV
MODE
O U T
MODE
0 0 0 0
MODE
PV
PV
S E N S
F - S L
.
H - R N
L - R N
H - S C
L - S C
+
TC/RTD
mV / Volt / mA
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODEMODE
MODE
L I N
0 0 0.0
1 0 0 0
0 0 0 0
MODE
.
.
U N I T
MODE
MODE
M V
℃
5 0 0.0
.
MODE
MODE
0 0 0 0
S - A D
1 0 0 0H - O T
MODE
MODE
MODE
0 0 0 0L - O T
MODE
MODE
A U 4
F I L T
MODE
MODE
.
.
.
PV
MODE
7. Major Function
1. display scaling function(mV, Volt, mA only)
This function changes and sets the display value according to scale and input range.
Ex) In case of input range 4.00~20.00mA
and Level 0.00~7.00m
2. Output scaling function
This function can change the 4.00~20.00mA value as the output scale.
Ex) In case of display value 0.00~7.00m,
Output 4.00~20.00mA
3. Sensor compensation function
The function is useful for compensating error by long sensor line or changed zero point by
aged sensor.
Ex) Before sensor adjust
= 510℃ After sensor adjust
= measured value + compensated value
= 510 - 10 = 500℃
4. Function(mV, Volt, mA type only)
Pass the input as it is.
Used for general input type and linearity input.
Pass the input after √. Used for flow rate by orifice.
Like level measuring, when it does not display measuring under zero, it always can
display zero by using limit function.
5.Filter function
Filter is moving average filter and it has 4 kinds of function.
NONE
It displays the change of input without filter.
AV 4, 8,16
It displays in recent input No 4,8,16 sample average.
Setting filter function delays response.
Do not use filter when high speed response is needed.
When output and display value are changed by irregular input, it is possible to get regular input
and display value by using filter function.
8. Operation and Setting Mode
It is All reset when ship the goods from factory.
If you want initialize all parameter, please reset the instrument.
Push the
MODE
and
E X I T
at the same time and ON the power.
It is initialized and operation by new setting value.
1.Operation Mode
2. Setting Mode
◉ Make flickering the wanted place by and
setting the value for data setting.
◉ Push the , the figure repeat to 0,1,2…
9,0 and the best position repeat to 0,1,
2…,9,-,-1,0 . If you want to output the
mode,
◉ push the then will go out into the PV
value Mode.
Initialization of the data (All Reset)
CAUTION
S - R T
L I M T
L I N
◉ Change the setting push at the
same time to move setting mode.
◉ Move to display mode in every mode push
the
◉ DATA setting method
① Setting the decimal point by
② Flickering the purpose digit by
③ Selecting the data by
④ Setting data by pushing the "mode"
⑤ Decimal point can set only the input
range high or input scale high mode.

9.
Ordering Code
NT54
Description(Basic)
Input element
B
0
B
R
0
R
S
0
S
K
0
K
J
0
J
E
0
E
T
0
T
V
1
mV(-100~100mV)
V
2
V(-10~10V)
A
0
mA(4~20mA)
P
1
Pt100Ω at 0℃
P
2
JPt100Ω
Z
0
Others element
Explosion proof
E
Ex d II C T6
Sensor
Consult
※ Purchase & A/S
* Seoul Office :
(Sales Department)
(Koin B/D, 801) 274-8
Youm chang-Dong, Kangseo-gu, Korea
Tel : +82-2-2668-3333, Fax : +82-2-2668-5100
* Head Office :
(Factory)
301Dong 1101Ho, Buchen Techno-park Ⅲ 36-1
Samjeong-dong, Ojeong-Ku, Buchen-City,
Gyeonggi-do, KOREA
Tel : +82-32-624-0770, Fax : +82-32-624-0772
http://www.newins.co.kr
E-mail : sales@newins.co.kr
Table of contents
Other newins Transmitter manuals
Popular Transmitter manuals by other brands

Monte Carlo Fan Company
Monte Carlo Fan Company ESSWC-10 Installation and operation instruction

Vega
Vega VEGADIF 65 operating instructions

Philips
Philips HC 8372 user manual

Freecast
Freecast SH800T user manual

EBS
EBS LX20G Installation and programming manual

Becker
Becker Centronic EasyControl EC411 Assembly and operating instructions