Next ATS 16 User manual

www.nextups.eu! ! ATS!16!v1.0*
User Guide
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
Automatic Transfer Switch
(ATS 16)
*
*
*
*
*
*
*
*
*
*
*

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!1! ATS!16!v1.0!
*
Table of Contents
1.*Introduction ................................................................2*
2.*Product Overview ........................................................2*
3.*Important Safety Warnings...........................................3*
4.*Operation Indicators & Status.......................................3*
5.*Installation ..................................................................5*
6.*Operation....................................................................6*
7.*Communication Port.....................................................6*
8.*Trouble Shooting .........................................................8*
9.*Specifications ..............................................................9*
10.*Appendix: ................................................................. 10*
*

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!2! ATS!16!v1.0!
*
1. Introduction
This ATS 16 product is designed with two independent power inlets to supply
power to the load from a primary power source. Should primary power source
fail, the
secondary will automatically back up the connected equipment without any
interruption. The transfer time from one line to another is seamless to the
connected equipment. After switching to a secondary power source, the ATS 16
can
also switch power back to the primary input when power to the primary input is
restored.
Package contents:
!ATS 16 module
!User manual
!mounting brackets
2. Product Overview
Front View:
(1) Power switch for input source A
(2) Power switch for input source B
(3) Circuit breaker for output 2
(4) Circuit breaker for output 3
(5) USB communication port
(6) RS-232 communication port
(7) Communication slot
(8)Operation indicators (please refer to section 4 for the details)
*Back View
*
(1) Contact port (please refer to section 7 for the details)
(2) Output receptacles “Output 3” (IEC 10A)
(3) Output receptacles “Output 2” (IEC 10A)
(4) Output receptacle “Output 1” (IEC 16A)
(5) Input source A connector
(6) Input source B connector

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!3! ATS!16!v1.0!
*
3. Important Safety Warnings
Before using the unit, please read all instructions and cautionary
markings on the unit, this manual and the batteries.
*
WARNING!! The ATS 16 must be connected to earth when in use.
In line with current regulations, only use the cables that have been supplied with
the machine. The power supply socket must be easily accessible to the operator.
WARNING!! The ATS 16 has been designed exclusively to operate indoors. It is
advisable to install it in areas where no inflammable liquids or gases, or other
harmful or noxious substances, have been stored.
*
ATTENTION!! A soft damp cloth may be used to clean the outside of the machine
(always with the system disconnected from the mains power supply and users).
*
Do not use any type of solvent as this may damage the external finishing of the
machine.
*
ATTENTION!! The ATS 16 has been designed exclusively for professional use.
NOTE: These instructions may be modified by the wiring regulations in force in
the country where the ATS 16 is purchased.
4. Operation Indicators & Status
*
*
*
*
*
(1) Source preference selector
(2) Priority setting LEDs
(3) Power source status LEDs
(4) Output source LEDs
(5) Fault indicator
(6) Alarm mute button

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!4! ATS!16!v1.0!
*
*
Indication
type
LED
description
LED
status
*
Condition
*
Alarm
*
*
Priority
setting
LEDs
Source A (2)
ON
*
Source A is priority
*
OFF
Source B (2)
OFF
Source A (2)
OFF
*
Source B is priority
*
OFF
Source B (2)
ON
*
*
*
*
*
*
Power
source
status
Status of
source A (3)
OFF
Inlet A has no power input
OFF
*
ON
Inlet A has power input, and
power is OK
*
OFF
*
Flashing
Inlet A has power input, but
power is out of SPEC
*
OFF
Status of
source B (3)
OFF
Inlet B has no power input
OFF
*
ON
Inlet B has power, and power is
OK
*
OFF
*
Flashing
Inlet B has power input, but
power is out of SPEC
*
OFF
*
*
*
*
*
*
*
Output
status
Output from
source A (4)
*
ON
*
*
Power A is output
*
*
OFF
Output from
source B (4)
*
OFF
Output from
source A (4)
*
OFF
*
*
Power B is output
*
*
OFF
Output from
source B (4)
*
ON
Output from
source A (4)
*
OFF
*
*
NO OUTPUT
*
*
OFF
Output from
source B (4)
*
OFF
*
Alarm
Fault (5)
OFF
Alarm not present
OFF
ON
Alarm present
Continuously

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!5! ATS!16!v1.0!
*
*
5. Installation
NOTE: Before installation, please inspect the unit. Be sure that
nothing inside the package is damaged.
*
Mounting the Unit
The unit can be mounted in a standard 19" rack. Fasten the mounting brackets to
the unit using the screws provided. With brackets attached securely, users can
mount the unit in a standard 19" rack as shown below.
*
*
*
NOTE: If the temperature around the unit will rise above 40 °C, ventilation is
required
*
Connecting the Unit
For connecting the ATS 16, plug “input source A connector” and “input
source B connector” to the two independent power sources or UPSs depending
using the SCHUCKO-IEC or IEC-IEC 16A cables supplied.
Plug the user load to the output 10A (“Output 1 and 2”) or 16A (“Output 3”)
sockets depending on user’s requirements.

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!6! ATS!16!v1.0!
*
PIN #
SIGNAL
1
VBUS
2
D-
3
D+
4
GND
*
6. Operation
Power On/Off
Put the input power switch in “ON” position. The output will then be supplied by
the source set as selected.
******Setting priority of power source
It is possible to set the power source preference to supply the output by pushing
the button of “source preference selector”. The default power source is “Source A”.
*
*
Function
*
Description
*
Default
Possible
configuration
Source perference
selector
Selection of input that
normally supplies the load
*
Source A
•Source A
•Source B
*
7. Communication Port
The ATS 16 is supplied with the following communication ports:
!Serial port is available with RS232 com. port and USB com. port on the front
panel.
NOTE: the use of one port automatically excludes the other.
!Contacts port on the rear panel.
Serial Ports: RS-232 & USB connectors
*
*
*
*
*
RS-232 connector USB connector
PIN #
NAME
TYPE
SIGNAL
1
*
*
*
2
TX
OUT
Serial line TX
3
RX
IN
Serial line RX
4
*
*
*
5
GND
POWER
*
6
+12V
POWER
*
7
*
*
*
8
*
*
*
9
*
*
*
NOTE: The utilization of the communication port is optional and it is not necessary
for the correct functioning of the ATS 16.

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!7! ATS!16!v1.0!
*
Contact Ports
The contacts port is formed using six (6) pins numbered from left to right (see fig.
1), which can be connected to an external monitoring system (such as a BMS) in
order to monitor the operational status of the ATS 16.
The external equipment must respect the voltage and current characteristics of
contacts port.
*
Fig. 1: Focus on contacts port.
*
The contacts port provides the following pins:
•Pin 1: common contact.
•Pin 2: “Source B” active contact (if the contact between “pin 1” and “pin 2” is
closed, output is supplied by “Source B”).
•Pin 3: “Source A” active contact (if the contact between “pin 3” and “pin 1” is
closed, output is supplied by “Source A”).
•Pin 4: “Source A” status OK contact (if the contact between “pin 4” and “pin 1”
is closed, “Source A” is present and regular).
•Pin 5: “Source B” status OK contact (if the contact between “pin 5” and “pin 1”
is closed, “Source B” is present and regular).
•Pin 6: Status OK contact (if the contact between “pin 6” and “pin 1” is closed,
ATS 16 functioning status is regular).
*
The following diagram shows the functioning of the contacts port.
*
*
*
*
*
*
*
*
*
Fig. 2: Contacts port basic diagram.
*
ATTENTION: The pins of the contact port are able to carry maximum current of
8A and maximum voltage of 250Vac.

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!8! ATS!16!v1.0!
*
8. Trouble Shooting
Use the table below to solve minor problems.
*
Problem
Possible Cause
Solution
*
*
The ATS 16 with
the mains voltage
present, does don’t
turn on.
(The LEDs does not
flash and no alarm
sounds.)
No connection with
input plugs
Connect the mains to the input plugs
as indicated in the installation section.
Input switch in
“OFF” position
Turn the
position.
input
switches
in
“ON”
*
Input power failure
Check that the mains voltage is present
or check if the UPS supplying the ATS
16 is powered on.
*
Protective device
upstream activated
Reset the protective device. Warning:
check that there is no overload or
short-circuit at the output of the UPS.
*
*
*
*
*
*
*
*
*
The load is not
powered.
No connection with
output sockets
*
Connect the load to the output sockets
*
*
*
*
*
*
*
Intervention of 10A
thermal protection
The thermal protection device will
operate in the event of a short circuit
or overload on one of the 10A output
sockets. The thermal protection can be
reset by pushing the button in which
will result in the power being
reconnected to the load. Therefore
prior to attempting a reset of the
thermal protection, please check the
connected loads rating and/or
determine if there are any problems.
Then once reset, reconnect each load
one at a time to ensure no problems
exists.
*
The display shows
nothing or provides
incorrect
information.
*
There is power
supply problem in
display.
Shut down the ATS 16 completely and
wait for a few seconds.
Switch the ATS 16 on again, if the
problem persists, contact the nearest
technical support centre.
The display is off
but the load is
powered.
There is power
supply problem in
display.
*
Contact the nearest NEXT UPS
Systems technical support centre.
If there is any abnormal situations occur, which doesn't list above, please call the
NEXT UPS Systems service people immediately for professional examine.

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!9! ATS!16!v1.0!
*
9. Specifications
*
MODEL
*
ATS 16
*
INPUT
*
Input Voltage
*
220/230/240 VAC
*
Acceptable Input Voltage Range
*
180 - 258 VAC
*
Input Frequency
*
50 Hz/60 Hz
*
Maximum Input Current
*
16 A
*
OUTPUT
*
Output Voltage
*
220/230/240 VAC
*
Maximum Output Current
10 A for IEC-C13 outlets
16 A for IEC-C19 outlet
CONNECTION
*
Input
*
2 x IEC-C20 inlets
*
Output
8 x IEC-C13
1 x IEC-C19
*
Communication
*
USB/RS-232
*
TRANSFER TIME
*
9-12ms (Typical)
*
PHYSICAL
*
Dimension, D X W X H (mm)
*
330 X 483 X 44
*
Net Weight (kgs)
*
5.0
*
ENVIRONMENT
*
Operating Temperature
*
0-95 % RH @ -5°C- 45°C (non-condensing)
*
NEXT Partnr
*
NEXT UPS Systems Part number
*
88009

www.nextups.eu!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!10!ATS!16!v1.0!
*
10. Appendix:
Input Voltage and Frequency Thresholds
*
FUNCTION
*
DESCRIPTION
DEFAULT
SETTING
*
Acceptable input
voltage range for
Source A
Source A will be power source during
this range. When input voltage of
source A is beyond this range, ATS
16 will automatically switch to
power from Source B.
*
*
*
180V – 258V
*
*
Return voltage point
for Source A
When input voltage of Source A is
back to normal, the ATS 16 will
switch back to Source A. (Setting
Source A as priority power source
and Source B is powering)
*
*
Low point: 190V
High point: 248V
*
Acceptable input
voltage range for
Source B
Source B will be power source during
this range. When input voltage of
source B is beyond this range, ATS
16 will automatically switch to
power from Source A.
*
*
*
180V – 258V
*
*
Return voltage point
for Source A
When input voltage of Source B is
back to normal, the ATS 16 will
switch back to Source B. (Setting
Source B as priority power source
and Source A is powering)
*
*
Low point: 190V
High point: 248V
*
Acceptable input
frequency for Source
A
Source A will be power source during
this range. When input frequency of
source A is beyond this range, ATS
16 will automatically switch to
power from Source B.
*
*
*
45Hz – 55Hz
*
Acceptable input
frequency for Source
B
Source B will be power source during
this range. When input frequency of
source B is beyond this range, ATS
16 will automatically switch to
power from Source A.
*
*
*
45Hz – 55Hz
*
*
Table of contents
Other Next Switch manuals
Popular Switch manuals by other brands

PKP
PKP PSA10 instruction manual

W.E. Anderson
W.E. Anderson FlotecT V4 series Specifications-installation and operating instructions

Atlona
Atlona Omega AT-OME-ST31 Manuals

EtherWAN
EtherWAN EX46910F installation guide

StarTech.com
StarTech.com SV211HDUA4K quick start guide

Atlona
Atlona AT-HDVS-200-TX-WP installation guide

HP
HP 6200YL Access security guide

Honeywell
Honeywell RTS-CSA Technical manual

Pico Macom
Pico Macom TSMS-16A Installation and operation manual

IBM
IBM 8285 Nways Installation and user guide

Supermicro
Supermicro SSH-C48Q user manual

Dwyer Instruments
Dwyer Instruments 1910-00 Installation and operating instructions