NIVELCO MultiCONT Owner's manual

BKI 11 ATEX 0017
prw2101a0600p_01
1 / 105
Manufacturer:
H-1043 Budapest, Dugonics u. 11.
Tel.: (36-1) 889-0100 Fax: (36-1) 889-0200
sales
NIVELCO Process Control Co.
E-mail: @nivelco.com www.nivelco.com
MultiCONT

prw2101a0600p_01
2 / 105

prw2101a0600p_01
3 / 105
TABLE OF CONTENTS
1. INTRODUCTION.............................................................................................. 5
1.1. THE HART SYSTEM .................................................................................. 6
1.1.1. The Communication .......................................................................................... 6
1.1.2. The structure of the system............................................................................... 6
1.1.2.1 Point-to-point connection ...................................................................... 7
1.1.2.2 Multipoint connection (Multidrop). Multiple slaves connected in parallel.8
1.1.3. Properties of HART-capable devices ................................................................ 9
1.1.4. HART Command set ......................................................................................... 9
1.1.4.1 Universal commands .......................................................................... 10
1.1.4.2 General commands............................................................................. 11
1.1.4.3 Device –specific commands ............................................................... 11
2. TECHNICAL DATA........................................................................................ 12
2.1. ACCESSORIES......................................................................................... 13
3. ORDER CODE ............................................................................................... 14
3.1. DIMENSIONS............................................................................................ 15
3.2. CONDITIONS OF USE OF THE EX UNITS ....................................................... 16
4. ELECTRICAL CONNECTION ....................................................................... 17
4.1. ARRANGEMENT OF THE CABLE TERMINALS ............................................... 17
4.1.1. Four relays version.......................................................................................... 17
4.1.2. Five relays version .......................................................................................... 17
4.2. WIRING................................................................................................... 19
4.2.1. Wiring .............................................................................................................. 19
4.2.1.1 Wiring of 2-wire units (transmitters) .................................................... 19
4.2.1.2 Wiring of 4-wire units (transmitters with separate power supply)........ 20
4.2.1.3 Wiring of Combined Systems (containing both 2- and 4-wire
transmitters) ....................................................................................................... 21
4.2.2. Wiring of Universal Interface Modules (PJK-100)............................................ 22
5. PROGRAMMING OF MultiCONT.................................................................. 23
5.1. STEPS OF PROGRAMMING......................................................................... 24
5.1.1. Scrolling and selecting menu items................................................................. 25
5.1.2. Activation (of devices, relays and current outputs) selection (of language,
operation mode, etc.) ...................................................................................... 26
5.1.3. Assignment of outputs (relay and current) to the device ................................. 27
5.1.4. Entering parameter values .............................................................................. 28
5.1.5. Editing character variables (e.g. Short TAG)................................................... 29
5.2. STEPS OF PUTTING INTO OPERATION A MultiCONT NETWORK................... 29
5.2.1. Preparation of the Transmitters and the Universal Interface Modules. ............30
5.2.1.1 Preparation of the Transmitters...........................................................30
5.2.1.2 Preparing of the Universal Interface Modules......................................31
5.2.2. Wiring...............................................................................................................31
5.2.3. Putting the MultiCONT into operation ..............................................................32
5.3. MAIN MENU............................................................................................. 33
5.4. MultiCONT CONFIGURATION................................................................... 34
5.4.1. DEV detect:......................................................................................................35
5.4.2. EXT detect: ......................................................................................................40
5.4.3. Main Display: ...................................................................................................40
5.4.3.1 Source .................................................................................................41
5.4.3.2 Rounding .............................................................................................42
5.4.3.3 Stepping ..............................................................................................42
5.4.4. List display .......................................................................................................43
5.4.5. User Display:....................................................................................................44
5.4.5.1 Editing the user display .......................................................................44
5.4.5.2 The resulted user displays...................................................................45
5.4.6. HART ...............................................................................................................46
5.4.6.1 MultiCONT Short TAG.........................................................................46
5.4.6.2 Polling Address....................................................................................47
5.4.6.3 Message..............................................................................................47
5.4.6.4 Description...........................................................................................47
5.4.6.5 Date.....................................................................................................48
5.4.6.6 Command Set......................................................................................48
5.4.7. USER RS485...................................................................................................51
5.4.8. Data Logger .....................................................................................................51
5.4.8.1 Trend logger ........................................................................................53
5.4.8.2 Time-window TOT (Total flow logging)................................................55
5.4.8.3 Time-window FM (Flow Maximum logging) .........................................55
5.4.8.4 Using a memory card for logging.........................................................56
5.4.8.5 File system of the SD card and file content of a logging entry.............58
5.4.9. Secret code......................................................................................................62
5.4.10. Language.........................................................................................................63
5.4.11. Background lighting .........................................................................................63
5.4.12. Report: .............................................................................................................64

prw2101a0600p_01
4 / 105
5.4.13. Prog CS........................................................................................................... 64
5.5. PROGRAMMING DEVICES.......................................................................... 65
5.6. REMOTE PROGRAMMING .......................................................................... 66
5.6.1. Editing the linearisation table .......................................................................... 68
5.7. RELAY CONFIGURATION........................................................................... 69
5.7.1. Relay Selection ............................................................................................... 69
5.7.2. Properties of the selected relay....................................................................... 70
5.7.3. Relay programming......................................................................................... 71
5.7.3.1 Source selection ................................................................................. 71
5.7.3.2 Function.............................................................................................. 72
5.7.3.3 Configuring parameters ...................................................................... 80
5.7.3.4 Invert................................................................................................... 81
5.7.3.5 Deleting TOT ...................................................................................... 81
5.7.3.6 Refreshing TOT .................................................................................. 82
5.7.3.7 Testing................................................................................................ 82
5.8. OPERATION AND PARAMETERS OF CURRENT OUTPUTS .............................. 84
5.8.1. Selection of Current outputs............................................................................ 84
5.8.2. Properties of the selected Current Output....................................................... 85
5.8.3. Current Output programming .......................................................................... 85
5.8.3.1 Source selection ................................................................................. 85
5.8.3.2 Function.............................................................................................. 86
5.8.3.3 Parameter configuration ..................................................................... 87
5.8.3.4 Testing................................................................................................ 87
5.9. THE BOOT PROCESS ............................................................................... 88
5.10. MEASUREMENT MODES ........................................................................... 90
5.11. SAVING,LOADING THE CONFIGURATION OF THE MULTICONT..................... 91
6. ERROR CODES............................................................................................. 92
7. HARDWARE PROTECTION OF THE SETTINGS ........................................ 94
8. FUSE REPLACEMENT ................................................................................. 95
9. SERVICING.................................................................................................... 96
9.1. BOX MESSAGES:..................................................................................... 96
9.2. OTHER MESSAGES:................................................................................. 97
9.3. TROUBLESHOOTING................................................................................. 98
9.3.1. It is impossible to enter the „Main menu”/”Relays” or „Main menu”/„Current
outputs” menu: ................................................................................................ 98
9.3.2. It is impossible to enter the „Main menu”/”Devices” menu: ............................. 98
9.3.3. A „Please wait” message appears upon selecting „DEV detect”.................... 98
9.3.4. The result of „DEV detect” is the „No device” message .................................. 98
9.3.5. The unit does not start up when switched on ..................................................98
9.3.6. The „Response” error entry is too frequent......................................................98
9.4. ADDITIONAL INFORMATION ........................................................................99
9.4.1. Problems that may occur during remote programming:...................................99
9.4.2. MultiCONT transmits the parameters without examining them, and the testing is
done by the device...........................................................................................99
9.4.3. Use of Second HART Master ( Hand-Held or HART modem + Eview
configuration software) ....................................................................................99
9.4.4. Upon exiting remote programming, the unit tests to see if the transmitter really
exited the remote programming mode.............................................................99
9.4.5. When a transmitter does not respond, then „Response” error is entered into the
table, but upon termination of the error (the device responds), this entry is
automatically cleared from the table (and does not need to be acknowledged)99
9.4.6. Upon exiting the menu, MultiCONT immediately saves the modifications.......99
9.4.7. The error list is cleared when the device is put off...........................................99
Appendix 1. ManufacturerID codes of HART-capable devices 100
Appendix 2. The menu system of the MultiCONT P-200 101-102
Appendix 3. Relay programming 103
Appendix 4. Current output programming 104
Appendix 5. Measurement mode 105

prw2101a0600p_01
5 / 105
Thank you for choosing a NIVELCO instrument.
We are sure that you will be satisfied throughout its use!
1. INTRODUCTION
The MultiCONT unit is a universal interface between NIVELCO’s HART-capable intelligent level transmitters and the other elements of the process control system
like the PC-s , PLC-s, displays and the actuators. Besides its role as an interface, the MultiCONT ensures the powering of the 2-wire transmitters while being capable
of complex control tasks. The MultiCONT unit supports communication with a maximum of 15 standard or 4 Ex certified NIVELCO’s HART-capable 2- and / or 4-wire
transmitters. If MultiCONT is used with NIVELCO’s MicroTREK microwave level transmitters the maximum number of transmitters in a loop should not exceed 8 pcs.
for normal transmitters and 2 pcs. for Ex version transmitters. If a system contain more transmitters than one MultiCONT can handle, further MultiCONT units can be
wired in series via an RS485 line. Remote programming of the transmitters and downloading of the parameters and measured data is possible using the MultiCONT.
The various outputs such as 4 … 20 mA, relays and digital outputs can be controlled using measured values and new values calculated from the measured values.
Measured values (Primary Value and three additional values) are able to be logged.
Large DOT matrix LCD panel facilitate a wide variety of display functions including tank content visualisation. The type and number of outputs of the basic unit can be
expanded with external (relay and/or current output) PJK-100 type Universal Interface Modules. The total number of relays included in the MultiCONT and in the
modules must not be more than 64, while that of the analog outputs (4…20 mA outputs) can be maximum 16. A further restriction is that there can be a maximum of
32 Universal Interface Modules.
Explosion proof certified versions of the MultiCONT should be installed outside the hazardous area.

prw2101a0600p_01
6 / 105
1.1. THE HART SYSTEM
The HART (Highway Addressable Remote Transducer – bus addressable field devices) is a digital communication protocol developed by ROSEMOUNT for industrial
measurement applications. A digital signal of small amplitude is placed on the widely used standard 4…20mA output current, and due to its symmetric sinusoidal
nature and its small amplitude, it does not affect the accuracy of the output current. Since no extra cable is needed for signal transfer, the already existing cable can
be used to realize the transfer. The identification, programming and querying of the transmitters can be done using this communication.
This diagram shows the output signal of a
4…20mA transmitter (device) and the
superimposed HART signal, which is essentially a
0.5 mA modulation of the output current..
t
I
out
[mA]
20 mA
4 mA
1
I
o
+ 0.5 mA
I
o
I
o
– 0.5 mA
0
The enlarged picture shows that HART
communication uses frequency modulation, and
logical „1” is assigned to 1200 Hz, while „0” is
assigned to 2200 Hz. This is called FSK
(Frequency-Shift Keying) modulation. The
communication is realized with systematic series
of impulses above described.
1.1.1. The Communication
The HART communication is basically a master-slave type, which means that the transmitter – slave – only sends a response when the master (of which there can be
only one in the system) sends a query. The master can be a Hand-held Communicator, a PC with a HART modem or a universal interface, in this case, a MultiCONT
(naturally, only one can be active). The communication uses standard commands (see chapter 1.1.3)
1.1.2. The structure of the system
The system must contain a 230..1000 resistor to guarantee that the HART signal of small amplitude will not load the power supply of unknown output impedance.

prw2101a0600p_01
7 / 105
1.1.2.1 Point-to-point connection
When a master (communicator or HART modem with PC or MultiCONT) and a slave are alone in a system, we talk of a point-to-point connection
Transmitter
I+
I–
SH
L+
L–
MultiCONT
250
+Us
Universal interface
RS485
In this case the flowing current is the output current of the transmitters, so if permitted by the loop voltage, even a local indicator can be included into the loop.
Essentially, the minimal voltage specified in the manual must be kept on the terminals of the transmitters.
Since the speed of transfer is 1200bit/sec, communication is slow, because the master queries and the slave responds. This can be speeded up if the querying is left
out, and the slave responds continuously every given period of time until the master stops the transfer in the break between 2 data transmissions. This is called “burst
mode”.

prw2101a0600p_01
8 / 105
1.1.2.2 Multipoint connection (Multidrop). Multiple slaves connected in parallel.
HART’s addressing system can handle 15 devices whereby they are wired in parallel. In this case, the current is the sum of the currents of all the devices in the loop,
which has not informative value. So in this case, the output current of the transmitters should be set to multidrop mode, which means a constant current of 4mA. This
automatically happens when the polling address is set between 1..15. (if the polling address is 0, then we should have only one transmitter with 4…20mA output, if
the polling address is 1…15, then we will have a constant 4 mA). There is a deviation possibility for transmitters whose output current can be programmed to an
arbitrary fixed value, however in this case, the minimal voltage drop on the terminal of the transmitters must be the minimum specified voltage, otherwise the
transmitter(s) will not be able to work (measure or respond)
T 1ransmitter
Transmitter 2
T 3ransmitter
T 15ransmitter
I+
I–
SH
L+
L–
MultiCONT
250
+Us
....
Universal interface
RS485
820
*
In a Multidrop system, the „burst mode” does not work
* An 820 ohm resistor should be connected between the L- and SH terminals of the Ex version MultiCONT when it is used with the 3 (max. allowed) Ex version
MicroTREK microwave level transmitter.

prw2101a0600p_01
9 / 105
1.1.3. Properties of HART-capable devices
These are programmed into the unit during manufacturing, some can be configured using a HART MASTER, others cannot (they can be reconfigured only by the
manufacturer)
Short TAG 8 character device ID. Can be reconfigured.
Short address Used to differentiate the 0…15 devices. There cannot be 2 identical „short addresses” in one system. Can be reconfigured
Message A max 32-character arbitrary comment that can be assigned to the device and is generally operation-related.
Can be reconfigured
Descriptor A max 16-character arbitrary comment that can be assigned to the device and is generally material-related.
Can be reconfigured
Date Date. Can be assigned to the device. Can be reconfigured
Factory ID Factory ID. For NIVELCO devices: 151, cannot be reconfigured
Device type ID Device type ID, cannot be reconfigured
Device ID The manufacturer’s electronic production number, cannot be reconfigured
The Factory ID, the Device Type ID and the Device ID together form the “Long Address”.
SW version ( Software version ): Software version of the device (see device manual)
HW version ( Hardware version ): Hardware version of the device (see device manual)
Apart from this, they provide the specification of the HART version according to which the device’s commands work
1.1.4. HART Command set
We have seen how to build up a HART system. Using the HART commands, we can decide what the devices should do. Naturally, an ultrasonic transmitter needs
commands different from those of a temperature transmitter or maybe a valve, so quite a large number of commands would be needed. Every command has a one-
byte identifier. The 31st command enables expansion, and in this case the next 2 bytes form the code of a command (0…65535). HART commands can be divided in
to 3 classes:
universal commands 0..30
general commands 32..121
device-specific commands 128..253
In all cases, the commands contain an address (this can be short, long address, TAG), which determines the corresponding device.
Two devices with the same address cannot be connected together!!

prw2101a0600p_01
10 / 105
1.1.4.1 Universal commands
These are commands understood by all devices, and to which all devices give the same reply.
0. Read unique identifier
the addressed device provides the following in it’s reply:
Manufacturer’s code (provided by the HART foundation, see appendix)
Product code (provided by manufacturer, see chapter 5.2.1.1)
Universal command table code ( HART 5 )
Device ID
Software version
Hardware version
Device status
1. Read primary variable
This reads the digital value (Primary Value) that the transmitter sends to the 4…20 mA output.
The unit also belongs to the numeric value.
2. Read output current in mA and in percent of range
3. Read output current and four dynamic variables
The primary, secondary, tertiary and quaternary variables are transmitted.
The secondary, tertiary and quaternary variables are specified in the manual of the given device.
6. Modify (short) polling address (Write polling address)
If there is more than one device in the loop (multidrop), each device must have a different address.
In this case, the address should be configured before connecting the device to avoid errors caused by devices with the same addresses replying at the same
time.
11. Read unique device identifier associated with tag
Devices are queried based on their short TAG and not based on their addresses.
As a result, there must not be more than one device with exactly the same short TAG.

prw2101a0600p_01
11 / 105
12. Read device message
This reads the 32 character message stored in the non-volatile memory of the device (e.g. T18 35% HCL TANK)
13. Read the 8 character ”short TAG”, 16 character descriptor and date
14. Read PV sensor information
15. Read output information
16. Read final assembly number
17. Write 32 character message
18. Write the 8 character ”short TAG”, 16 character descriptor and date
19. Write final assembly number
1.1.4.2 General commands
These commands do not need to be understood by all devices. If not understood, nothing happpens, however, if understood, then it must be interpreted according to
the standard. Many such commands exist, the most important ones are the following:
34: damping (writing settling time)
35: measurement range (writing of upper and lower limits, and/or dimension)
36: Upper limit now! (sets the upper limit – 20 mA)
37: Lower limit now! (sets the lower limit – 4 mA)
40: setting constant current output (can be very useful during testing)
41: Device self-test, sends back the result.
42: Master reset (setting factory default)
50: Reading assignment status of the primary variable (PV), the secondary variable (SV), the tertiary variable (TV) and the quaternary variable (QV). This can
not always be read unambiguously, in most cases it can be found in the manual of the device.
109: Switching „Burst” mode on and off.
1.1.4.3 Device –specific commands
These commands are specified by the manufacturer. A description of the commands can be found in the device manual.

prw2101a0600p_01
12 / 105
2. TECHNICAL DATA
TYPE P -2-
Transmitter Power Supply 30 V DC / 60 mA (For Ex Version: 25 V DC / 22 mA)
Display 128 x 64 dot-matrix
Analogue Max. 2 galvanically isolated 4 … 20 mA outputs,
max load of 500 ohm, with over-voltage protection
Relay Max. 5 SPDT, 250 V AC, AC1. 5 A
RS 485 interface Galvanically isolated, HART / MODBUS protocol
HART
Output signal level: 0.5 ±0.1 Vpp trapezoid 1200 / 2200 Hz
Minimum level of Input signal: 50 mVpp
Inbuilt sensor resistance: 250 ohm.
Outputs
Logger Capacity: FLASH = 65000 entry; SD card (max 2 GB) = depends on the card!
TYPE P -2-
Power Supply, Relays, analogue 4 … 20 mA 0.5 … 2.5 mm2wire cross-section
RS 485 interface Shielded, twisted cable pair with a cross section of 0.5 … 2.5 mm2
Connecting
cables
HART line
Below1500 m shielded, twisted cable pair with a min.cross section of 0.5mm
Above 1500 m shielded, twisted cable pair, with a min. cross section of 0.8mm
max. resistance : 75 ohm, max.capacitance : 200 nF
Number of powered transmitters Max. 15 non-Ex (max. 4 Ex) transmitters
Power supply /
Power consumption /
max. power supply
85 … 255 V AC 50 … 60 Hz / 12 VA / 255 Veff
11.4 … 28 V AC 50 … 60 Hz / 12 VA / 28 Veff
11.4 … 40 V DC / 11 W / 40 V DC
Fuse 85 … 255 V AC 50 … 60 Hz T400 mA
11.4 … 28 V AC 50 … 60 Hz és 11.4 … 40 V DC T1A
Housing material Polycarbonate (PC)
Mounting Wall mounted
Ambient Temperature -20 °C … +50 °C
Ingress protection IP 65
Ex marking II (1) G [Ex ia Ga] IIB
Intrinsically safe output limitation data Uo= 30 V Io= 140 mA Po= 1 W
Lo= 4 mH Co= 200 nF
Electrical protection Class I / III
Mass 0.9 kg

prw2101a0600p_01
13 / 105
2.1. ACCESSORIES
Warranty Card
User’s and Programming manual
Declaration of Conformity
2 universal cable gland sealings

prw2101a0600p_01
14 / 105
3. ORDER CODE
MultiCONT P – 2 –
EXPANSION CODE ENCLOSURE CODE INPUT CODE OUTPUT CODE POWER SUPPLY CODE
Expandable * R IP 65 wall enclosure W 1 HART unit 1 Display only 0 85 … 255 V AC 1
Standard E 2 HART units 2 1 relay 1 24 V AC / DC 2
IP 65 wall enclosure +
transparent cover C 4 HART units 4 2 relays 2 85 … 255 V AC Ex 5
8 HART units 8 3 relays 3 24 V AC / DC Ex 6
IP 65 wall enclosure +
transparent cover + logger D 15 HART units M 4 relays 4
5 relays D Ex: Ex ia
1x 4-20mA Analogue output F
1 relay + 1 x 4-20 mA Analogue output 5
2 relays + 1 x 4-20 mA Analogue output 6
3 relays + 1 x 4-20 mA Analogue output 7
4 relays + 1 x 4-20 mA Analogue output 8
2x 4-20mA Analogue output G
1 relay + 2 x 4-20 mA Analogue output H
2 relays + 2 x 4-20 mA Analogue output J
3 relays + 2 x 4-20 mA Analogue output K
4 relays + 2 x 4-20 mA Analogue output 9
RS 485 interface A
1 relay + RS 485 interface L
2 relays + RS 485 interface M
3 relays + RS 485 interface N
4 relays + RS 485 interface P
5 relays + RS 485 interface E
1x 4-20mA Analogue output + RS 485 interface B
1 relay + 1 x 4-20 mA output+ RS 485 interface R
2 relays + 1 x 4-20 mA output+ RS 485 interface C
3 relays + 1 x 4-20 mA output+ RS 485 interface S
4 relays + 1 x 4-20 mA output+ RS 485 interface T
2x 4-20mA + RS 485 interface U
1 relay + 2 x 4-20 mA output+ RS 485 interface V
2 relays + 2 x 4-20 mA output+ RS 485 interface W
3 relays + 2 x 4-20 mA output+ RS 485 interface X
4 relays + 2 x 4-20 mA output+ RS 485 interface Y
The order code of an Ex version should end in „Ex”.
* The system can be expanded using Relay, Analogue and Universal Interface Modules

prw2101a0600p_01
15 / 105
3.1. DIMENSIONS
160
166
89.5
AB BC
A
Pg9 or M16
B Pg11 or M20
C Pg11, Pg13.5 or M20
107160
193
A
Pg9 or M16
B Pg11 or M20
C Pg11, Pg13.5 or M20
CBB
A
75.575.5
11210
10
R2.7
R2.5
PW PC, PD ARRANGEMENT OF MOUNTING HOLES
PW PC PD

prw2101a0600p_01
16 / 105
3.2. CONDITIONS OF USE OF THE EX UNITS
The units should be mounted outside the hazardous zone!
Device should be protected against direct sunshine!
The power supply and ambient temperature values must not exceed the specifications in the Technical data!
Transmitters installed in hazardous areas must only be connected to the L+ and L- terminals!
The housing of the transmitter must be grounded!
The transmitters must be connected using shielded, twisted cable pairs!

prw2101a0600p_01
17 / 105
4. ELECTRICAL CONNECTION
4.1. ARRANGEMENT OF THE CABLE TERMINALS
4.1.1. Four relays version
1 2 3
4 5 6
789
16 17
18 19
10 11 12
13 14 15
20 21 22
23 24 25
MAINS RELAY 1
RELAY 2
RELAY 3
RELAY 4
CURRENT
OUT 1
CURRENT
OUT 2
USER RS485
MODULE RS485
ABCOM
ABCOM
DEVICES
26 27 28
LLSH+-
11.4 ... 28V
AC
11.4 ... 40V
DC
85 ... 255V
AC
()
+-()
**
*
After loosening and removing screws fastening the
cover the cables can be connected. The same cable
should not be used for AC and DC as well as for SELV
and mains voltage.
For wiring of the transmitters shielded, twisted cable
pair (STP) should be used with the length depending
on the number of connected units and the electrical
properties of cable.
RS485 interface: A: TRD+
B: TRD–
COM: shielding
* Only PR types
** Non-Ex versions only
4.1.2. Five relays version
1 2 3
4 5 6
789
10 11 12
13 14 15
20 21 22
23 24 25
MAINS RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5 USER RS485
MODULE RS485
ABCOM
ABCOM
DEVICES
26 27 28
LLSH+-
11.4 ... 28V
AC
11.4 ... 40V
DC
85 ... 255V
AC
()
+-()
16 17 18

prw2101a0600p_01
18 / 105
Cabel Capacitance (pF / m)
Number of
Transmitters 65 95 160 225
1 2800 2000 1300 1000
5 2500 1800 1100 900
10 2200 1600 1000 800
15 1850 1400 900 700
Shielding of the connecting cable between the transmitter and the controller should be grounded at one end, connected either to the internal or external part of the
earthing screw.
Intrinsically safe (Ex) transmitters should be connected through the terminals L+, L– to the controller. These points are galvanically isolated from the other parts of the
electronics. Power supply for the Ex transmitter is current-, voltage- and power-limited.

prw2101a0600p_01
19 / 105
4.2. WIRING
4.2.1. Wiring
Before wiring, please check: if the units (order codes) are HART-capable, the value of the loop current and also if there are two or more units with the same “Short
address”. (See 5.2. Steps of commissioning)
4.2.1.1 Wiring of 2-wire units (transmitters)
Shielding grounded
at the MultiCONT
In non-Ex versions only
Transmitter 1
T 2ransmitter
T 3ransmitter
T Nransmitter
I+
I–
SH
L+
L–
MultiCONT
250
+Us
Shielded twisted
cable pair
Universal interface
USER
RS485
Non-Ex area
Ex area
PJK-100
Universal interface
modules
MODULE
RS485

prw2101a0600p_01
20 / 105
4.2.1.2 Wiring of 4-wire units (transmitters with separate power supply)
85...255 VAC
11.4...28 VAC
11.4...40 VDC Shielding grounded
at the MultiCONT
I+
I– SH
L–
MultiCONT
250
Transmitter 1
T 2ransmitter
T 3ransmitter
T 15ransmitter
Shielded twisted
cable pair
Universal interface
USER
RS485
MODULE
RS485
PJK-100
Universal Interface
Modules
Table of contents