Norcros Triton Shower tower User manual

INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER
2180363B Feb 2003
Shower Tower
manual mixer
Installation and
Operating
Instructions

Shower tower
CONTENTS Page
Introduction 1
Safety warnings 1
Main components 2
Site requirements 3
Typical installations 4 - 5
Preparing the mixer valve 6
Siting of shower 6
Installation 6 - 8
Using the mixer control lever 9
Using the diverter valves 9
Adjusting the sprayhead 10
Maintenance 10
Spare parts 11
Fault finding 12 - 13
Guarantee, service policy, etc. rear cover
UKAS
QUALITY
MANAGEMENT
003

Shower tower
1
INTRODUCTION
This book contains all the necessary fitting and
operating instructions for your Triton Shower
Tower manual mixer shower. Please read them
carefully.
Read through the whole of this book before
beginning your installation.
The shower installation must be carried out by a
suitably competent person and in sequence of
this instruction book.
Care taken during the installation will ensure a
long and trouble free life from your shower.
This shower tower is designed to operate on
the higher pressure systems found in the UK up
to a maximum of 6 bar running pressure.
The shower MUST NOT be subjected to water
temperatures above 80°C.
This mixer shower is suitable for fully
modulating type combination boilers and multi-
point hot water heaters. It is also suitable for
thermal storage, unvented systems and
pumped gravity systems.
Important: Before installing with a gas
instantaneous water heater, ensure it is
capable of delivering hot water at a
minimum switch-on flow rate of 3 litres per
minute. At flow rates between 3 and 8 litres
per minute, the appliance must be capable of
raising the water temperature to a minimum
of 52°C. Water temperature at the inlet to
the mixer must remain relatively constant
when flowrate adjustments are made (refer to
the water heater operating manual to confirm
compatibility with this shower tower).
This shower tower is supplied with an integral
single check valve and integral large area filter
in each inlet elbow. Inlet connections are by
braid hoses having 1/2” BSP unions.
SAFETY WARNINGS
a Layout and sizing of pipework must be such
that when other services are used, pressures
at the shower control inlets DO NOT fall
below the recommended minimum.
b DO NOT choose a position where the
shower could become frozen.
c DO NOT connect this mixer shower to any
form of tap or fitting not recommended by
the manufacturer.
d The sprayhead must be regularly cleaned to
remove scale and debris.
e Conveniently situated isolating valves in
each inlet supply must be fitted as an
independent method of isolating the
shower should maintenance or servicing be
necessary.
f If it is intended to operate the shower in
areas of hard water (above 200 ppm
temporary hardness), a scale inhibitor may
have to be fitted. For advice on the Triton
scale inhibitor, please contact Customer
Service.
g Do not operate the shower outside the
guidelines as laid out in ‘site requirements’.
Replacement parts can be ordered from Triton
Customer Service. See ‘spare parts’ for details
and part numbers.
Due to continuous improvement and updating,
specification may be altered without prior notice.
To ensure the product suitability for
commercial and multiple installations, please
contact Triton’s specification advisory service
prior to installation.
Telephone: (024) 7632 5491
Facsimile: (024) 7632 4564

Shower tower
2
MAIN COMPONENTS
Thank you for purchasing our high quality
product. Check components and quantity
before installation. In the unlikely event of
anything being amiss, please contact Triton
Customer Service.
Pack contents
Showertower body - 1 off
Fixed head - 1 off
Handset and hose - 1 off
Manual mixer valve control lever - 1 off
Diverter valves - 3 off
Body jets - 3 off
Elbows with filters and check valves - 2 off
Hanging brackets - 2 off
Screws and wall plugs - 4 off
Guarantee.
Important notes before you start
This product has passed a factory control test
before reaching you. Do not attempt to
dismantle or modify it.
●Ensure there are no hidden service pipes and
cables where you intend to drill.
●Ensure the hot and cold supply pipes are
flushed out before final connection to the unit.
●The working pressure of this product is 0.5
bar – 6 bar. (7 bar static)
●Please be aware of your safety while drilling
and installing.
Showertower
body
Fixed head
Body
jets
Diverter valve
(fixed head)
Diverter valve
(body jets)
Diverter valve
(handset)
Mixer
control
lever
Handset
Handset
hose
Handset
bracket
Outlet
connector
Fig.2
WARNING!
The shower tower mixer valve is NOT
thermostatic and will NOT prevent
water flowing from the spray outlets
should there be a loss of one supply to
the inlets.
This product is NOT suitable for low
pressure gravity fed supplies unless a
suitable pump is also installed.

Shower tower
3
SITE REQUIREMENTS
The installation must be in accordance with
Water Regulations and Byelaws.
Minimum running water pressure: 0.5 bar
Maximum running water pressure: 6 bar
Maximum static water pressure: 7 bar
For otimum performance an operating
pressure of 3 bar running is required.
Both hot and cold supplies should be at
nominally equal pressures with a minimum flow
rate of 8 litres per minute to both inlets.
While the shower tower is operational (open
outlet), inlet pressures must not be capable of
exceeding 6 bar. For effective operation of the
internal seals, the maximum static pressure
must not be exceeded.
Note: On sites where the running pressure is
above 6 bar, the use of a suitably sized pressure
reducing valve fitted in the cold mains supply
pipework can provide nominally equal pressures
at the showertower.
For a satisfactory performance from the shower
tower both cold and hot inlet supplies must be
from a balanced supply.
Additional isolating valves must be fitted as an
independent means of isolating the water
supplies should maintenance be necessary.
The pipework should be installed such that the
flow is not significantly affected by other taps
and appliances being operated elsewhere on
the premises.
Note: Where thermal store systems and
instantaneous gas water heaters are used, if
excessive draw offs take place the boiler may
not be able to maintain an adequate output
temperature. This could result in the
showertower temperature becoming noticeably
cooler.
DO NOT use jointing compounds on pipework.
Water temperature requirements
Recommended maximum 65°C.
BS6700 recommends the temperature of stored
water should never exceed 65°C.
A stored water temperature of 60°C is
considered sufficient to meet all normal
requirements and will minimise the effects of
scale in hard water areas.
Temperature adjustment range
The mixed water temperature can be adjusted
from cold through to the temperature of hot
water available from the hot water appliance.
Flow rate performance
For all systems, the ability to use showerheads
and body jets simultaneously is dependent on
domestic hot water pressures and flow rates.

Shower tower
4
TYPICAL SUITABLE INSTALLATIONS
a) Instantaneous gas-heated systems,
e.g. combination boilers (fig.2)
The shower tower can be installed with a
multipoint gas water heater or combination
boiler of a fully modulating design (i.e. to
maintain relatively stable hot water
temperatures).
A drop tight pressure reducing valve MUST be
fitted if the supply pressures exceed 6 bar
running.
An expansion vessel (as shown in fig.2) MUST
be fitted, and regularly maintained, to ensure
the shower mixer is not damaged by excess
pressures. This may already be installed within
the boiler (check with manufacturer) and is in
addition to the normally larger central heating
expansion vessel.
The layout and sizing of pipework MUST be
such that nominally equal inlet supply pressures
are achieved and the effects of other draw-offs
are minimised.
b) Unvented mains pressure systems
(fig.3)
The shower tower can be installed with an
unvented, stored hot water cylinder.
For systems with no cold water take off after
the appliance reducing valve, it will be
necessary to fit an additional drop tight
pressure reducing valve when the mains
pressure is over 6 bar. The drop tight pressure
reducing valve must be set at the same value as
the unvented package pressure reducing valve.
Note: An additional expansion vessel (fig.3)
may be required if a second pressure reducing
valve is installed. This does not apply to
packages with a cold take off after the pressure
reducing valve to the cylinder.
The layout and sizing of pipework MUST be
such that nominally equal inlet supply pressures
are achieved and the effects of other draw-offs
are minimised.
Service
valve
Balanced cold mains supply
Cold mains supply
Shower
tower
Expansion
vessel
Pressure
reducing valves
Stop tap
Unvented
hot water
storage unit
Safety devices
not shown
Service
valve
Fig.3
(diagrammatic view
– not to scale)
CH flow
Cold
mains
supply
Hot water
CH return
Service
valves
Shower
tower
Stop
tap
Expansion
vessel
Pressure
reducing valve
Combination
boiler
Fig.2 (diagrammatic view – not to scale)

Shower tower
5
Blender
valve
Flow
Cold mains supply
Hot
water
Stop tap
Expansion
vessel
Pressure
reducing valve Return
Service
valves
Shower
Tower
Boiler
Fig.4
(diagrammatic view
– not to scale)
Isolating switch
or pull cord
switch (both
fused at 3A)
Hot water
cylinder
Shower
tower
Service
valve
Cold supply
Hot supply
Alternative
supply
Cold
water
mains
supply
Ring main
Drain
valve
Gate
valve
Service
valve
Other
draw-offs
Stop valve
Cold
water
cistern
Pump
Fig.5
(diagrammatic view
– not to scale)
c) High output thermal store systems
(fig.4)
Packages of this type, fitted with a blender valve
can be used. A drop tight pressure reducing
valve MUST be fitted if the supply pressures
exceed 6 bar running.
An expansion vessel (as shown in Fig.4) MUST
be fitted, and regularly maintained, to ensure
the unit is not damaged by excess pressures.
This may already be installed externally or
internally within the thermal store (check with
thermal store manufacturer).
d) Pump assisted gravity fed systems
(fig.5)
The pump MUST be fed from a cold water
cistern and hot water cylinder providing
nominally equal pressures. The pump must be
capable of maintaining a minimum running
pressure of 1 bar.

Shower tower
6
Height of
sprayhead
and shower
to suit user’s
requirement.
Sprayhead can
be mounted
either side of
shower tower
Fig.7 (diagrammatic view – not to scale) SITING OF THE SHOWER
Refer to fig.7 for correct siting of the shower.
Position the shower on the wall so that all
controls can be comfortably reached whilst
using the shower.
IMPORTANT: The hot entry piping is on the
left-hand side of the mixer body.
INSTALLATION
General conditions
Note: The outlet of the shower must not be
connected to anything other than the hose and
sprayhead supplied.
DO NOT use jointing compounds on any pipe
fittings for the installation.
Use only the fittings supplied.
DO NOT solder fittings within the vicinity of the
shower tower as heat transfer can damage the
seals and valve components.
Note: Suitable isolating valves (complying with
Water Regulations and Byelaws) MUST be fitted
on the hot and cold water supplies to the
shower tower as an independent means of
isolating the water supplies should maintenance
or servicing be necessary.
When connecting pipework avoid using tight
90° elbows. Swept or formed bends will ensure
optimum performance.
IMPORTANT: The water circuit should be
installed such that the flow is not
significantly affected by other taps and
appliances being operated elsewhere on the
premises. Water pressure must not fall below
specification of the shower.
Note: Hot water pipe entry must be made to
the left-hand side inlet.
WARNING!
THE SHOWER MUST NOT BE
POSITIONED WHERE IT WILL BE
SUBJECT TO FREEZING CONDITIONS.

Shower tower
7
Instantaneous Gas Water Heaters
In order to ensure the optimum performance
from the shower when connected to an
instantaneous water heater, the appliance must
be capable of raising the temperature of the
incoming water to a minimum of 52°C and
delivering a flow rate of not less than eight litres
per minute.
Fitting the pipework
Establish the required position of the shower
tower and mark two holes for the incoming
water supplies.
The suggested final separation between pipe
centres is 150mm (fig.8).
Remove the plaster and brickwork (or
plasterboard) to the depth required and chase
out the additional areas to facilitate the
incoming pipework.
Complete the outlet pipework with a standard
15mm x 1/2” BSP female thread elbow or
straight coupler (depending on direction of
entry supplies).
It is prefereable to flush the pipework
(fig.9) to clear the system of debris and
check for leaks before connecting to the
elbows.
Complete any plastering and tiling.
Note: Pipes can be surface mounted but cut-
outs must be fashioned in the top or bottom of
the shower tower.
Fitting the hanging brackets
Using the centres of the supply holes as the
datum line (fig.10) mark the position for the
four locating screws for the hanging brackets,
ensuring they align vertically and horizontally.
The holes should be 6mm in diameter and
30mm deep; the distance between the two
hanging brackets should be 215.5mm.
Drill and plug the wall using the wallplugs
provided (the wallplugs are suitable for most brick
walls - use an appropriate masonry drill, but if the
wall is plasterboard or a soft building block, use
special wallplugs and a suitable drill bit).
150 mm
470
mm
215.5
mm
To suit user's
requirement
88 mm
Floor level
Hot
pipe
Cold
pipe
Four
hanging
bracket
holes
1/2" BSP
female fittings
Approx. 150mm
Fig.8
Fig.9
Fig.10

Check valve
Filter
Elbow
Apply PTFE tape
to threads
Shower tower
8
Fig.11
Fig.13
Fig.12
Fig.14
Secure the hanging brackets to the wall using
the screws supplied (fig.11).
Fitting the shower tower body
Wrap the supplied elbow threads with PTFE
tape and connect them to the hot and the cold
water pipes. Tighten to prevent leaking and
ensure the elbows face upwards (fig.12).
Fit the filter and check valve onto the elbow to
prevent debris entering the the mixer valve
(fig.13).
Facing the front of the shower tower body,
connect the left-hand flexible hose inside the
unit to the hot water elbow, and then connect
the right-hand flexible hose to the cold water
elbow (fig.14).
Screw tightly to avoid leaking. Note there is a
gasket on each hose which must be in place.
Hitch the two hooks inside the shower body
onto the hanging brackets on the wall. Ensure
the installation is stable.
Fitting the hose and sprayhead
Screw the fixed head (fig.15) to the topmost
outlet connector of the shower tower body,
making sure the sealing washer is in place.
Screw tight to ensure no leakage.
Connect the swivel nut of the shower hose to
the bottom outlet connector (fig.16) on the
shower tower body. Screw the other end of the
hose to the handset then locate the handset
into the handset bracket.
Check the pipework for stability and
tightness to avoid leaks before using the
shower tower.
Note: DO NOT use silicon sealant around the
shower tower since it may be necessary to
access and clean the inlet filters periodically.

USING THE MIXER CONTROL LEVER
Lift the lever up and water will flow from the
outlets, depending which has been selected via
the diverter valve. Press the lever down and the
water flow will cease (fig.17).
To obtain hot water turn the lever to the left. To
obtain cooler water turn the lever to the right
(fig.18).
Note: When showering is completed, close the
water supply off at the control lever. DO NOT
rely on the diverter valves to permanently shut
the water off.
USING THE DIVERTER VALVES
The diverter valves are combined on/off and
graduated flow controls.
Note: The diverter valves (fig.19) only operate
if the mixer control lever is on (lever up). The
temperature adjustment is controlled only from
the mixer control lever.
The upper diverter valve controls water
flow from the fixed head.
The middle diverter valve controls water
flow from the body jets.
The lower diverter valve controls water
flow from the handset.
Water volume increases by turning the diverter
valves counterclockwise. The water volume will
decrease by turning the diverter valves
clockwise.
CAUTION: It is recommended that persons
who may have difficulty understanding or
operating the controls should not be left
unattended while using the shower tower.
Special consideration should be given to young
children and the less able bodied.
On
Off
Shower tower
9
Washers
Sprayhead
Fig.15
Fig.16
Fig.17
Fig.19
Hot Cold
Fig.18

Shower tower
10
ADJUSTING THE SPRAYHEAD
Five sprayhead patterns are available (fig.20).
Adjustment is by turning the bezel on the
sprayhead in either direction until the desired
pattern is obtained.
MAINTENANCE
Clean the unit frequently and regularly with
clean water or mild liquid detergent then rinse
with clean water, and dry it with soft cotton
cloth.
DO NOT use acid or abrasive detergents.
Cleaning the sprayheads and diverters
To clean the sprayheads and diverters simply
rub the your thumb over the nozzles.
Should spare parts be required in the future,
contact Triton Customer Service – (024) 7637
2222
Fig.20

14
Shower tower
11
1
2
3
4
5
6
7
8
9
SPARE PARTS
Ref. Description Part No.
1Showerhead 7993102
2Handle cover – fixed head 7993089
3Handle cover – body jets 7993090
4Handle cover – handset 7993091
5Handle
6One-way jet 7993103
7Two-way jet 7993104
8PVC hose 7993100
9Hook
10 Hanging bracket
11 One-way valve
12 Filter 7993101
13 Elbow
14 Handset 7993105
15 Handset hose 7993094
10
11
12
13
15

Shower tower
12
The following can be carried out by a competent person
1.1 Not enough cold
water flowing through
shower.
1.2 Increase in the
ambient cold water
temperature.
1.3 Cold water supply
blocked.
1.4 High volume of cold
water drawn off elsewhere.
2.1 Not enough hot water
flowing through shower.
2.2 Decrease in the
ambient cold water
temperature.
2.3 Insufficient hot water
supplies from the heating
system.
2.4 Hot water supply
blocked or restricted.
3.1 Water supplies cut off.
3.2 Shower unit blocked.
3.3 Blockage in pipework.
3.4 Sprayhead blocked.
3.5 System not capable of
supplying multiple outlets
at the same time.
1.1.1 Turn temperature control anti-clockwise.
1.2.1 Turn temperature control anti-clockwise.
1.3.1 Turn shower off and consult a competent
plumber or contact Triton Customer Service.
1.3.2 Check filters are clean.
1.4.1 Reduce the simultaneous demand from
the supply.
2.1.1 Turn the temperature control clockwise.
2.2.1 Turn the temperature control clockwise.
2.3.1 Ensure heating appliance is set to
maximum or has sufficient stored hot water.
2.3.2 Ensure heating appliance is igniting by
trying a hot water tap elsewhere.
2.4.1 Turn shower off and consult a competent
plumber or contact Triton Customer Service.
2.4.2 Check filters are clean.
3.1.1 Check water elsewhere in house and if
necessary contact local water company.
3.2.1 Inspect the inlet filters. Clean if necessary.
3.3.1 Turn the shower off and consult a
suitably competent plumber.
3.4.1 Clean sprayhead.
3.5.1 Reduce the simultaneous demand.
3.5.2 Ensure stop/service valves are fully open.
3.5.3 Check if sufficient water pressure.
1Water too hot.
2Water too cold
3Water does
not flow or
shower pattern
collapses when
another outlet is
turned on.
Problem/Symptom Cause Action/Cure
FAULT FINDING

4.1.1 Fit a pressure reducing valve.
5.1.1 Fit a pressure reducing valve
6.1.1 Renew mixer valve.
4Water too cold
5Shower
controls noisy
whilst in use.
6Shower will
not shut off
4.1 Running pressure in
excess of maximum
recommended.
5.1 Running pressure in
excess of maximum
recommended.
6.1 Pipework not flushed
before connecting the unit
(mixer valve control
damaged).
Shower tower
13
The following is recommended for a professional qualified installer only
Problem/Symptom Cause Action/Cure
FAULT FINDING

Service Policy
In the event of a complaint occurring, the
following procedure should be followed:
1Telephone Customer Service on (024) 7637
2222 (08457 626591 in Scotland and in Northern
Ireland), having available the model number and
power rating of the product, together with the
date of purchase.
2Triton Customer Service will be able to confirm
whether the fault can be rectified by either the
provision of a replacement part or a site visit from
a qualified Triton service engineer.
3If a service call is required it will be booked and
the date of call confirmed. In order to expedite
your request, please have your postcode available
when booking a service call.
4It is essential that you or an appointed
representative (who must be a person of 18 years
of age or more) is present during the service
engineer's visit and receipt of purchase is shown.
5A charge will be made in the event of an aborted
service call by you but not by us, or where a call
under the terms of guarantee has been booked
and the failure is not product related (i.e. scaling
and furring, incorrect water pressure, installation
faults).
6If the product is no longer covered by the
guarantee, a charge will be made for the site visit
and for any parts supplied.
7Service charges are based on the account being
settled when work is complete, the engineer will
then request payment for the invoice. If this is not
made to the service engineer or settled within ten
working days, an administration charge will be
added.
Replacement Parts Policy
Availability: It is the policy of Triton to maintain
availability of parts for the current range of
products for supply after the guarantee has
expired. Stocks of spare parts will be maintained
for the duration of the product’s manufacture and
for a period of five years thereafter.
In the event of a spare part not being available a
substitute part will be supplied.
Payment: The following payment methods can be
used to obtain spare parts:
1By post, pre-payment of pro forma invoice by
cheque or money order.
2By telephone, quoting credit card (MasterCard
or Visa) details.
3By website order, www.tritonshowers.co.uk
Triton Plc, Shepperton Park, Caldwell Road,
Nuneaton, Warwickshire. CV11 4NR
Triton Plc guarantee this product against all
mechanical defects arising from faulty
workmanship or materials for a period of one year
for domestic use only, from the date of purchase,
provided that it has been installed by a competent
person in full accordance with the installation and
operating instructions.
Any part found to be defective during this
guarantee period we undertake to repair or
replace at our option without charge so long as it
has been properly maintained and operated in
accordance with the operating instructions, and
has not been subject to misuse or damage.
This product must not be taken apart, modified or
repaired except by a person authorised by Triton
Plc. This guarantee applies only to products
installed within the United Kingdom and does not
apply to products used commercially.
This guarantee does not affect your statutory
rights.
What is not covered:
1Breakdown due to: a) use other than domestic
use by you or your resident family; b) wilful act or
neglect; c) any malfunction resulting from the
incorrect use or quality of gas or water or
incorrect setting of controls; d) faulty installation.
2Repair costs for damage caused by foreign
objects or substances.
3Total loss of the product due to non-availability
of parts.
4Compensation for loss of use of the product or
consequential loss of any kind.
5Call out charges where no fault has been found
with the unit.
6The cost of repair or replacement of
sprayheads, hoses, riser rails and/or wall brackets,
or any other accessories installed at the same
time.
7The cost of routine maintenance, adjustments,
overhaul modifications or loss or damage arising
therefrom, including the cost of repairing
damage, breakdown, malfunction caused by
corrosion, furring, pipe scaling, limescale, system
debris or frost.
TRITON STANDARD GUARANTEE
Customer Service
☎(024) 7637 2222
Scottish and Northern Ireland
Customer Service
☎08457 626591
Trade Installer Hotline
☎(024) 7632 5491
Fax: (024) 7632 4564
www.tritonshowers.co.uk
Table of contents