Nord Drivesystems SK PAR-2H User manual

About this document
BU 0040 GB-1611 Subject to technical alterations 1
GB
BU 0040
Control and Parameter Boxes for
NORDAC Frequency Inverters

NORDAC Control and Parameter Boxes
2Subject to technical alterations BU 0040 GB-1611
Intended use of the frequency inverter
The compliance with the operating instructions is necessary for fault-free operation and the
acceptance of possible warranty claims. These operating instructions must be read before
working with the device!
These operating instructions contain important information about service. They must therefore
be kept close to the device.
The control and parameter boxes are only intended for use with NORD frequency inverters or
their accessories (optional modules).
All details regarding technical data and permissible conditions at the installation site must be
complied with.
Commissioning (implementation of the intended use) is not permitted until it has been ensured
that the machine complies with the EMC directive 2004/108/EEC and that the conformity of the
end product meets the machine directive 2006/42/EEC (note EN 60204).
©Getriebebau NORD GmbH & Co. KG, 2011

About this document
BU 0040 GB-1611 Subject to technical alterations 3
Documentation
Designation: BU 0040 DE
Part No.: 607 04 01
Device types: SK PAR-2H, SK PAR-2E,
SK PAR-3H, SK PAR-3E
SK CSX-3H, SK CSX-3E
SK SSX-3A1
SK POT1-1
Suitable for frequency inverter series:
NORDAC SK 200E, SK 300E2, SK 500E, SK 700E, SK 750E2
NORDAC vector mc2
Version list
Designation of previous versions Software
Version
Comments
BU 0300 DE, August 2008
Part No. 607 0801 / 3208
V 3.9 R0 Revised version of issue 4907 (December 2007)
BU 0300 DE, March 2009
Part No. 607 0801 / 1009
V 4.0 R3 Addition of the products SK PAR-3H and SK CSX-3H
BU 0040 DE, April 2011
Part No. 607 0801 / 1611
V 4.2 R1 Restructuring of manual, addition of the products
SK PAR-3E, SK CSX-3E, SK SSX-3A and SK POT1-1
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 •D-22941 Bargteheide •Germany •http://www.nord.com/
Tel.: +49 (0) 45 32 / 401-0 •Fax +49 (0) 45 32 / 401-555
NOTE
This supplementary operating manual is only valid in conjunction with the operating manual
supplied for the respective frequency inverter.
1Not for "vector mc"
2Only SK PAR-2H and SK PAR-2E

NORDAC Control and Parameter Boxes
4Subject to technical alterations BU 0040 GB-1611
1 GENERAL INFORMATION ............................................................................ 6
1.1 Features...................................................................................................................7
1.1.1 ParameterBox, SK PAR-2H ........................................................................7
1.1.2 SimpleBox (SK CSX-3x) .............................................................................7
1.1.3 SetpointBox (SK SSX-3A)...........................................................................7
1.1.4 Control box (SK POT1-1) ............................................................................7
1.2 Delivery....................................................................................................................8
1.3 Scope of supply......................................................................................................8
1.4 Certifications...........................................................................................................8
1.4.1 European EMC Directive.............................................................................8
1.4.2 RoHS compliance .......................................................................................8
2 PARAMETER BOXES.................................................................................... 9
2.1 Installation...............................................................................................................9
2.1.1 SK PAR-2H - Handheld Version .................................................................9
2.1.1.1 Connection to trio SK 300E/750E.........................................................9
2.1.1.2 Connection variants ............................................................................10
2.1.2 SK PAR-2E - built-in version.....................................................................11
2.1.2.1 Mechanical installation in a control panel ...........................................11
2.1.2.2 Electrical connection...........................................................................12
2.1.2.3 Connection to inverter.........................................................................13
2.1.3 SK …-3H – Handheld Version ..................................................................14
2.1.3.1 SimpleBox SK CSX-3H – Handheld Version......................................14
2.1.3.2 ParameterBox SK PAR-3H – Handheld Version ................................14
2.1.3.3 Electrical Connection ..........................................................................14
2.1.4 SK …-3E - built-in version.........................................................................16
2.1.4.1 SimpleBox SK CSX-3E – Built-in Version ..........................................16
2.1.4.2 ParameterBox Version SK PAR-3E– Built-in Version ........................16
2.1.4.3 Mechanical installation in a control panel ...........................................17
2.1.4.4 Electrical Connection SK …-3E ..........................................................18
2.2 Functions of the Parameter Boxes....................................................................19
2.2.1 SimpleBox .................................................................................................19
2.2.1.1 Display ................................................................................................19
2.2.1.2 Operation ............................................................................................20
2.2.2 ParameterBox ...........................................................................................24
2.2.2.1 Display ................................................................................................24
2.2.2.2 ControlBox mode ................................................................................25
2.2.2.3 Operation ............................................................................................26
2.2.3 Data transfer with NORD CON .................................................................31
2.3 System parameters..............................................................................................33
2.3.1 Description of parameters .........................................................................33
2.3.1.1 Parameter display...............................................................................33
2.3.1.2 Inverter parameterisation....................................................................35
2.3.1.3 Parameter administration....................................................................35
2.3.1.4 Options................................................................................................36
2.3.2 Table of possible error messages.............................................................37
2.4 Technical data.......................................................................................................39
2.5 Accessories for NORDAC parameterisation boxes ........................................40
2.5.1 SK IC1-232/485 interface converter..........................................................40
2.5.2 Cable-Adapter assignment........................................................................40
2.5.2.1 Adapter list ..........................................................................................40
2.5.2.2 Assignment of parameterisation box - frequency inverter ..................41

Contents
BU 0040 GB-1611 Subject to technical alterations 5
3 CONTROLBOXES........................................................................................ 42
3.1 SK SSX-3A – Simple Setpoint Box ....................................................................42
3.1.1 Installation .................................................................................................42
3.1.2 Connection ................................................................................................42
3.1.3 Operating modes.......................................................................................43
3.1.3.1 Operating mode 485C (Control mode via RS485)..............................44
3.1.3.2 Operating mode IO-C (Control mode via DI1/DO1 of the SK 2xxE)...46
3.1.3.3 Operating mode IO-S
(Setpoint mode via DI1 of the frequency inverter) ..............................49
3.1.4 Technical data...........................................................................................52
3.2 Control box (SK POT1-1).....................................................................................53
3.2.1 Installation .................................................................................................53
3.2.1.1 Overview .............................................................................................53
3.2.1.2 Control connections ............................................................................54
3.2.2 Parameterisation .......................................................................................57
3.2.3 Technical data...........................................................................................57
4 MAINTENANCE AND SERVICING INFORMATION.................................... 58
5 KEYWORD INDEX ....................................................................................... 59

NORDAC Control and Parameter Boxes
6Subject to technical alterations BU 0040 GB-1611
1 General information
NORDAC control and parameter boxes enable parameterisation, control and display of the operating parameters
of the inverter series NORDAC SK 200E, SK 300E, SK 500E, SK 700E, SK 750E and vector mc.
Various versions of the control and parameter boxes are available. The box to be used with a particular inverter
series can be obtained by reference to the overview tables in Sections 2.5.2, 3.1.2 and 3.2.1.
1. For service and commissioning directly on the system the handheld versions of the parameter boxes
(SK PAR-2H, SK PAR-3H and SK CSX-3H) are recommended. These handheld units can be used for
parameterisation and display.
2. The built-in versions of the parameter boxes (SK PAR-2E, SK PAR-3E and SK CSX-3E), for
installation in a control panel enable control and monitoring of up to 5 frequency inverters (SK CSX-… 1
frequency inverters) in a control cabinet.
3. The Simple Setpoint Box SK SSX-3A is primarily intended to control SK 200E series frequency inverters
and can be sued both as a handheld unit and a wall-mounted unit.
4. The SK POT1-1 control box is a simple manual control unit for the control of NORDAC frequency
inverters with an enabling signal and setpoint. The control box can also be used as a wall-mounted unit.
The ParameterBox (SK PAR-xx) has a storage capacity which can store the complete data records for up to 5
inverters.
In order to archive the data, the ParameterBox SK PAR-2x can be connected to a PC via an interface converter
(SK IC1-232/485). In order to connect the SK PAR-3H, only a common USB connection cable (USB2.0
connection cable, A-series plug to B-series plug) is required. The NORD CON software necessary for this can be
downloaded free of charge from the Getriebebau NORD internet page http://www.nord.com.
It is also possible to transfer data from the PC to the ParameterBox. For this, a previously saved or created data
set is required (see Section 2.2.3). This is then recognised by the NORD CON Software.
WARNING
The SK PAR-3H ParameterBox must never be connected simultaneously to the frequency
inverter and the PC, as otherwise this may cause damage, especially to the PC.
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to safety
and warning instructions.
Installation or removal of modules or electrical connections must only be carried out when no
voltage is present. For detailed information, please refer to the relevant frequency inverter
manual.

1 General information
BU 0040 GB-1611 Subject to technical alterations 7
1.1 Features
1.1.1 ParameterBox, SK PAR-2H
•Illuminated, high resolution LCD graphics screen
•RS 485 communication interface (SK PAR-3H: RS 485 and RS 232)
•Central unit for up to 5 inverters interlinked via RS 485
•Supply voltage 4.5VDC to 30VDC
•5V (or 24 V) direct current supply from the frequency inverter can be used
•5 complete inverter data records can be stored in the memory, loaded and processed
•SK PAR-2x: with interface converter (SK IC1-232/485) connection to a standard RS 232 PC interface;
SK PAR3H via USB interface. In this case no interface converter is required3
•For use as a display for various operating parameters
•Protection class IP 54. For information, see Technical Data, Section 2.4.
•Automatic inverter detection
•Large-screen display of individual operating parameters
•Standardisation of individual operating parameters to display specific system data
•Control in various languages (see parameter (P1301))
•Error message display in plain language
•Direct control of an inverter possible
•ControlBox function possible
1.1.2 SimpleBox (SK CSX-3x)
•4-digit, 7-segment display
•5V (or 24V) direct current supply directly from the frequency inverter can be used
•For use as a display for various operating parameters
•Protection class IP 54. For information, see Technical Data, Section 2.4.
•Direct control of an inverter possible
•LEDs for parameter set display
1.1.3 SetpointBox (SK SSX-3A)
•4-digit, 7-segment display
•24V direct current supply direct from the frequency inverter can be used
•3 operating modes with automatic detection (depending on the connection)
- RS485 in control mode (SK 2xxE, SK 300E, SK 5xxE, SK 700E*, SK 750E*)
- IO communication in control mode (SK 2xxE only)
- IO communication in setpoint mode (SK 2xxE only)
•Protection class IP 54
•Wall-mounting possible
* only with optional RS485 interface
1.1.4 Control box (SK POT1-1)
•Direction switch with "0" position for selection of the direction of rotation of the drive unit
•10kOhm potentiometer for the continuous setting of setpoints between 0 and 100%
•Approx. 3m long connecting cable with open ends for permanent connection to the relevant digital and
analog input terminals of the frequency inverter
•The box can be wall-mounted
•Protection class IP 66
3For SK PAR-3H directly via USB port (USB2.0)

NORDAC Control and Parameter Boxes
8Subject to technical alterations BU 0040 GB-1611
1.2 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or loose
parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
1.3 Scope of supply
Standard version:
The scope of supply includes one of the following devices,
Type Version IP protection class Part Number Comments
SK PAR-2E Installation IP 54 - front panel 278910110
SK PAR-2H Handheld IP 54 278910100 Incl. connection cable:
M12 plug connector, length approx. 3m
SK PAR-3E Installation IP 54 - front panel 275281414
SK PAR-3H Handheld IP 54,
IP 20 on plug
275281014 Incl. connection cable:
* RJ12-RJ12, length approx. 2m
* USB, length approx. 1m
SK CSX-3E Installation IP 54 - front panel 275281413
SK CSX-3H Handheld IP 54,
IP 20 on plug
275281013 Incl. connection cable:
* RJ12-RJ12, length approx. 2m
SK SSX-3A Handheld (wall-
mounting possible)
IP 54 275281513 Incl. M12 screw cable connector
SK POT1-1 Handheld (wall-
mounting possible)
IP 66 278910120 Incl. connection cable: length approx.
3m
Incl. M16 screw cable connector for SK
2xxE, SK 300E, SK 750E
Available accessories: (For details see Section 2.5)
- Interface converter for connecting SK PAR-2x to a PC
- Various adapter plugs for connecting the parameter boxes to NORDAC frequency inverters
- Operating instructions as PDF file on CD ROM including NORD CON, (PC-based
parameterisation software)
- also available free of charge under www.nord.com
1.4 Certifications
1.4.1 European EMC Directive
If the control and parameter boxes are installed according to the
recommendations in this instruction manual, they meet all of the requirements of
the EMC directive according to the EMC product standard for motor-operated
systems EN 61800-3.
1.4.2 RoHS compliance
NORDAC control and parameter boxes are designed to be RoHS compliant
according to Directive 2002/95/EEC.

2 Parameter Boxes – Installation
BU 0040 GB-1611 Subject to technical alterations 9
2 Parameter boxes
With the aid of parameter boxes it is possible to control or adapt the parameterisation of a frequency inverter or its
intelligent optional modules (e.g field bus modules). The SimpleBox versions only allow access to the frequency
inverter.
2.1 Installation
2.1.1 SK PAR-2H - Handheld Version
The SK PAR-2H ParameterBox is a compact control
device for direct connection to the frequency inverter. A
suitable connection cable with an M12 plug contact is
included with the device. Direct connection of the
ParameterBox to the NORDAC SK 300E and the SK
750E is possible without additional components. Special
connection cables are required for connection to other
NORDAC frequency inverters. These are described in
further detail in Section 2.1.1.2 "Connection variants".
2.1.1.1 Connection to trio SK 300E/750E
Direct connection to the trio SK 300E can be made using
the available M12 socket. With the appropriate
components the high level of protection (IP54) is retained
for the entire unit.
After the mains voltage is switched on the corresponding
device type is automatically recognised.
M12 plug Description Cable
2 (white) + 4.5V… 30V,
approx. 1.3 W
1 (brown) GND
4 (black) P+ (A) (RS485 +)
3 (blue) P- (B) (RS485 -)
Length 3m
4 x 0.75mm2
1
4
2
3

NORDAC Control and Parameter Boxes
10 Subject to technical alterations BU 0040 GB-1611
2.1.1.2 Connection variants
trio SK 300E
SK 750 E
SK 52xE
SK 53xE
vector mc
SK 700E
SK 5xxE
SK 200E
SK 700E
(>22KW)
PC / laptop
NORD CON
Software
NORDAC Frequency inverter
Modules/options
Direct to terminals
(RS485)
SK CU1-STD
SK CU1-USS
Direct connection
to device
SK IC1-232/485
Part. No. 276970020
+
USB 5V Adapter
Part. No. 278910220
Connecting cable
Direct to system connector
Connection cable M12 socket–> wires
M12 So / wires
Part. No. 278910200
Connection cable M12 socket -> RJ12
RH12 / M12 So
Part. No. 278910230
Connection cable M12 socket -> SUB-D
M12 So / Sub-D So
Part. No. 278910210
ParameterBox
SK PAR-2H
Part. No. 278910100

2 Parameter Boxes – Installation
BU 0040 GB-1611 Subject to technical alterations 11
2.1.2 SK PAR-2E - built-in version
The SK PAR-2E ParameterBox is a compact control device for control panel installation. Up to 5 frequency
inverters can be connected via the internal connection terminals. Protection class IP54 is complied with on the front
panel.
2.1.2.1 Mechanical installation in a control panel
For installation in the control cabinet door or the control panel, a cut-out of 137mm x 82mm (tolerance +/- 1mm)
must be made. The sealed unit must be inserted in the pre-processed cabinet panel. There are 6 screws (M3 x
7mm) for securing the unit to the interior of the control panel. The ParameterBox is now mounted securely on the
control cabinet door and has maximum protection class IP54 on the front side, if mounted correctly.
With the built-in model, the electrical connection of the ParameterBox SK PAR-2E can be made via the internal
screw terminals 14. The precise assignment of the terminals can be seen in the following section.
137 mm
82 mm
136 mm
162 mm
35 mm
80 mm
35 mm
100 mm
73 mm
146 mm
90 mm
+/-1mm
+/-1mm
Control cabinet front
Control cabinet interior
Seal
Fastening screws
6 x M3 x 7mm
(nuts and washers are included)
Seal

NORDAC Control and Parameter Boxes
12 Subject to technical alterations BU 0040 GB-1611
2.1.2.2 Electrical connection
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to safety
and warning instructions.
Installation or removal of modules or electrical connections must only be carried out when no
voltage is present. For detailed information, please refer to the relevant frequency inverter
manual.
The SK PAR-2E ParameterBox is connected via the 6-pin screw connector or the RJ12 plug. The power supply can
either be from the inverter or a separate supply unit. The permissible voltage range is +4.5V to +30V DC.
Number Description RJ 12
42 + 4.5V… 30V / 1.3W 6
40 GND 3
73 P+ (A) (RS485 +) 1
74 P- (B) (RS485 -) 2
- - 4
- - 5
RS485_A
RS485_B
GND
TXD
RXD
+5V
+5V - 30V
1 2 3 4 5 6
A termination resistor (220Ω) for the RS485 bus system is integrated into the module. Therefore the ParameterBox
should only be connected as the first or last participant.
The terminals are designed for 0.14 mm² - 1.5 mm2. A flexible cable with a cross section of 4 x 0,75mm2is
recommended.
The maximum possible connection cross section is 1.5mm2. With the use of certain wire end sleeves, the possible
cross-section may be reduced.
Schaltschrank
Gear unit motor with FI in field
SK PAR-2E
Part No. 278910110 SK 5xxE SK 700E vector CT
SK 2xxE
SK 300E
SK 750E
vector mc
Power supply
Data cable

2 Parameter Boxes – Installation
BU 0040 GB-1611 Subject to technical alterations 13
2.1.2.3 Connection to inverter
A shielded signal cable should be used for the data cable between the ParameterBox and the inverter. The power
supply to the ParameterBox must be between +4.5V and +30V.
Please use the following connections to connect the ParameterBox with the corresponding inverter. The
connections apply for fixed connection to the particular inverter via the terminal bar. However, these must always
be compared with the labelling on the ParameterBox.
SK 700E / SK 750E
(with option…)
Description vector mc
RS485
vector
(CT / VT) SK 300E
SK 52xE
SK 53xE
X7: SK CU1-STD SK CU1-USS
+5V / +15V 15 - 42 42 42 42
GND 16 - 40 40 40 40
P+ (A), RS485 + 17 21 73 73 73 73
P- (B), RS485 - 18 22 74 74 74 74
NOTE
Each further frequency inverter which is to be operated simultaneously on the bus cable is only
connected in parallel to the cables RS485+ and RS485-. Under no circumstances may the
power supplies of the frequency inverters (5V) be connected to each other.
For the following series of devices the RS485 data connection is also possible via the RJ12 plug socket which is
integrated into the inverter.
Description SK 2xxE
Integrated
6-pin RJ12
socket
SK 300E
Integrated
4-pin M12
connector
SK 5xxE
Integrated
6-pin RJ12
socket
SK 700E >22KW
Integrated
6-pin RJ12
socket
SK 700E ≤22KW
(with option…) …-
RS2)
Integrated
6-pin RJ12
socket
SK 750E
Integrated
4-pin M12
connector
+5V 6 ("24V") 2 6 6 (6) * 2
GND
3 1 3 3 (3) * 1
P+ (A)
(RS485 +) 1 4 1 1 1 4
P- (B)
(RS485 -) 2 3 2 2 2 3
* For inverters SK700E up to 22KW with the option …-RS2 an external power supply (+4.5V - + 30V) must be provided for the ParameterBox.
Note: In order to connect the ParameterBox to the RJ12 socket of the frequency inverter, a standard
RJ12 (6-pole) patch cable with a length of up to 3 m can be used.
If the ParameterBox is supplied from an external power source (+4.5 to +30V) according to the
voltage, the data cables can also be considerably longer.
As standard, the 4-pin M12 connector (plug) is available for connection of the ParameterBox to a
decentralised frequency inverter (SK 300E/ SK750E).
ATTENTION
In order to avoid damage, if an external power supply to the ParameterBox is used, care must
be taken that the output voltage of this external source is higher than that of the inverter voltage
(however, max. 30V DC).
(E.g.: SK520E: 5V internal supply→External supply for the ParameterBox >5V!)

NORDAC Control and Parameter Boxes
14 Subject to technical alterations BU 0040 GB-1611
2.1.3 SK …-3H – Handheld Version
2.1.3.1 SimpleBox SK CSX-3H – Handheld Version
The SK CSX-3H SimpleBox is a compact control device for
direct connection to the frequency inverter via the RJ12
diagnostic socket. A normal RJ12 -patch cable ("Modular
cable RJ12 (6/6) - RJ12 (6/6), 1:1 assignment") with a
length of up to 3m can be used for connection.
If the SimpleBox is supplied from a power source with a
higher voltage (e.g. 24VDC from SK 200E), the cable can be
considerably longer.
2.1.3.2 ParameterBox SK PAR-3H – Handheld Version
The SK PAR-3H ParameterBox is a compact control device
for direct connection to the frequency inverter via the RJ12
diagnostic socket. A normal RJ12 -patch cable ("Modular
cable RJ12 (6/6) - RJ12 (6/6), 1:1 assignment") with a
length of up to 3m can be used for connection.
If the ParameterBox is supplied from a power source with a
higher voltage (e.g. 24VDC from SK 200E), the cable can be
considerably longer.
A normal USB device connection cable (USB2.0 connection
cable, Series A plug to Series B plug) is required to connect
a PC or laptop.
WARNING
The SK PAR-3H ParameterBox must never be connected simultaneously to the frequency
inverter and the PC, as otherwise this may cause damage, especially to the PC.
2.1.3.3 Electrical Connection
The parameter boxes SK CSX-3H and SK PAR-3H are only
connected to a frequency inverter via the RJ12 socket. This
connection also provides the power supply to the box.
A termination resistor (220Ω) for the RS485 bus system is
integrated into the module. Therefore the ParameterBox
should only be connected as the first or last participant.
Connection of the SK PAR-3H ParameterBox to a PC is
made via the USB interface integrated into the box. This
connection also provides the power supply to the box.
The necessary driver software for the USB interface on the
PC is supplied with the enclosed CD "EPD", but is also
available free of charge on our Internet page
(www.nord.com).
RJ12 (RS485)
USB port

2 Parameter Boxes – Installation
BU 0040 GB-1611 Subject to technical alterations 15
Connection to the particular frequency inverter is made via the RJ12 connection sockets on the device. The
SimpleBox SK CSX-3H can only communicate with frequency inverters.
The contact assignment of the RJ-12 connection on the parameter box is as follows:
Description RJ 12
P+ (A) RS 485 + 1
P- (B) RS 485 - 2
GND 3
- 4
- 5
+ 4.5V… 30V,
approx.1.3 W 6
RS485_A
RS485_B
GND
TX D
RX D
+5V+4.5V- 30V
1 2 3 4 5 6
SK TI4-TU-BUS
SK200E SK700E
SK500E

NORDAC Control and Parameter Boxes
16 Subject to technical alterations BU 0040 GB-1611
2.1.4 SK …-3E - built-in version
The SK CSX-3E and SK PAR3E are built-in versions of the parameter boxes described in Section 2.1.3 . If they are
correctly installed in the front of the control panel they comply with protection class IP 54.
2.1.4.1 SimpleBox SK CSX-3E – Built-in Version
The SK CSX-3E SimpleBox is a compact control device for
installation in a control panel and direct connection to the
frequency inverter via the RJ12 diagnostic socket. A normal
RJ12 -patch cable ("Modular cable RJ12 (6/6) - RJ12 (6/6),
1:1 assignment") with a length of up to 3m can be used for
connection.
If the SimpleBox is supplied from a power source with a
higher voltage (e.g. 24VDC from SK 200E), the cable can be
considerably longer.
2.1.4.2 ParameterBox Version SK PAR-3E– Built-in Version
The SK CSX-3H ParameterBox is a compact control device
for installation in a control panel and direct connection to the
frequency inverter via the RJ12 diagnostic socket. A normal
RJ12 -patch cable ("Modular cable RJ12 (6/6) - RJ12 (6/6),
1:1 assignment") with a length of up to 3m can be used for
connection.
If the ParameterBox is supplied from a power source with a
higher voltage (e.g. 24VDC from SK 200E), the cable can be
considerably longer.

2 Parameter Boxes – Installation
BU 0040 GB-1611 Subject to technical alterations 17
2.1.4.3 Mechanical installation in a control panel
For installation in the control cabinet door or the control panel, a cut-out of 109mm x 64mm (tolerance +/- 1mm)
must be made. The sealed unit must be inserted in the pre-processed cabinet panel. For attachment to the inside
of the control panel, 6 threaded pins (M4 x 16 mm) (approx. 7 mm projection in installed condition) and the
corresponding nuts are provided. The ParameterBox is now mounted securely on the control cabinet door and has
maximum protection class IP54 on the front side, if mounted correctly.
Electrical connection of the SK CSX-3E or SK PAR-3E parameterisation boxes is made via the RJ12 socket which
is accessible from the rear. The precise assignment of the terminals can be seen in the following section.
Control cabinet front
Control cabinet interior
Seal
Fastening bolts
6 x M4 x 16mm
(nuts and washers are included)
Seal

NORDAC Control and Parameter Boxes
18 Subject to technical alterations BU 0040 GB-1611
2.1.4.4 Electrical Connection SK …-3E
The parameter boxes SK CSX-3E and SK PAR-3E are only
connected to a frequency inverter via the RJ12 socket. This
connection also provides the power supply to the box.
A termination resistor (220Ω) for the RS485 bus system is
integrated into the module. Therefore the ParameterBox should
only be connected as the first or last participant.
In contrast to the handheld version SK PAR-3H, connection of
the SK PAR-3E ParameterBox to a PC is not possible.
Connection to the particular frequency inverter is made via the
RJ12 connection sockets on the device. The SimpleBox
SK CSX-3E can only communicate with frequency inverters.
The contact assignment of the RJ-12 connection on the parameter box is as follows:
Description RJ 12
P+ (A) RS 485 + 1
P- (B) RS 485 - 2
GND 3
- 4
- 5
+ 4.5V… 30V,
approx.1.3 W 6
RS485_A
RS485_B
GND
TX D
RX D
+5V+4.5V- 30V
1 2 3 4 5 6
SK TI4-TU-BUS
SK500E
SK200E
RJ12 (RS485)
Rear of parameterisation box
Similar to illustration
SK700E

2 Parameter Boxes – Display and control
BU 0040 GB-1611 Subject to technical alterations 19
P1
P2
P1
P2
P1
P2
P1
P2
2.2 Functions of the Parameter Boxes
2.2.1 SimpleBox
2.2.1.1 Display
After connection of the SimpleBox and switching on the mains voltage (or the 24V DC control voltage) of the
frequency inverter, communication between the frequency inverter and the SimpleBox commences automatically.
After brief illumination of all he display segments and diodes of the box a
bus scan is carried out while the middle bars of the display (4-digit, 7-
segment display) may flash rapidly.
If the bus scan is completed successfully, the frequency inverter power
appears briefly in the display (e.g.: 0.37 = 0.37 KW). This step is skipped if
the SimpleBox is connected to a frequency inverter which is already in
operation.
The horizontal bars which then appear in the display indicate that the
frequency inverter is ready for operation.
If a jog frequency value is pre-set in parameter P113, or a minimum
frequency is pre-set in P104, the display flashes with this initial value.
If the frequency inverter is enabled, the display changes automatically to the operating value selected in parameter
>Selection Display value< P001 (factory setting = current frequency).
The actual parameter set is shown by the 2 LEDs next to the display on the left in binary code.
After the frequency inverter is switched off, an "OFF" appears briefly in the
display before the display is completely switched off.
"OFF" is also shown in the display if the SimpleBox is operated via an
external 24V control voltage, although the power supply (230V or 400V) is
inactive.
In this state, almost unrestricted parameterisation of the inverter (no measurement of motor resistance or
parameter identification is possible (P208 / P220)) can be carried out as described in the following section.
However, control (enabling) is not possible due to the lack of the power supply.
NOTE
The digital frequency setpoint is factory set to 0Hz. To check whether the motor is working, a
frequency setpoint must be entered with the or keys or a jog frequency via the respective
parameter >Jog frequency< (P113).
Settings should only be implemented by qualified personnel, strictly in accordance with the
warning and safety information.
ATTENTION: The motor may start immediately after pressing the START key !

NORDAC Control and Parameter Boxes
20 Subject to technical alterations BU 0040 GB-1611
2.2.1.2 Operation
Switching on the frequency inverter. The frequency inverter is now enabled with the set jog frequency
(P113). A preset minimum frequency (P104) may at least be provided. Parameter >Interface< P509 and
P510 must = 0.
Switching off the frequency inverter. The output frequency is reduced to the absolute minimum
frequency (P505) and the frequency inverter shuts down.
7-segment
LED display
4-digit
Operating mode Display Comments
Ready for operation
without setpoint present
Display of 4 static underscores.
If the underscores flash slowly:
the frequency inverter is not ready for operation (e.g.:)
•Starting disabled:
Function “Safe pulse block“ or
Fast stop active
•enable signal before the frequency inverter is ready for
operation.
Ready for operation
with setpoint present
Numbers flash slowly:
A starting setpoint (P104 / P113 in keyboard operation)
(e.g.: 5.3Hz) is indicated. This frequency is immediately
used on being enabled.
In operation
Display of actual frequency.
In case of fault
Display of an actual and active error message.
Slow flashing of the display indicates that the fault is no
longer present and the error message can be
acknowledged.
Parameterisation
Display of parameter number or parameter value.
1. Parameter group
(e.g.: Motor data (P2 - -))
2. Parameter number
(e.g.: Nominal speed (P202))
3. Parameter value
(e.g.: 1360min-1))
The LEDs indicate the actual operating parameter set in the operating display (P000) and the actual
parameter set being parameterised during parameterisation. In this case the display is coded in binary
form.
LEDs
P1
P
2
1
2
= P1
2
1
= P2
1
2
= P3
2
1
= P4
The motor rotation direction changes when this key is pressed. "Rotation to the left" is indicated by a
minus sign.
Attention! Take care when operating pumps, screw conveyors, ventilators, etc. →You can disable the
key with parameter P540.
Press key to increase the frequency. During parameterisation, the parameter number or parameter
value is increased
Press the key to reduce the frequency. During parameterisation, the parameter number or parameter
value is reduced.
Press "ENTER" to store an altered parameter value, or to switch between parameter number or
parameter value.
NOTE: If a changed value is not to be stored, the key can be used to exit the parameter without
storing the change.
P1
P2
P1
P2
P1
P2
P1
P2
P1
P2
P1
P2
P1
P2
O
K
This manual suits for next models
7
Table of contents
Popular Control Unit manuals by other brands

Innogy
Innogy SHC manual

Agilent Technologies
Agilent Technologies VPI Series instruction manual

Graco
Graco E-Flo 24P821 Instructions-parts list

Siemens
Siemens SINUMERIK 840D Description of Functions

Siemens
Siemens VAG60 Series Mounting instructions

EB TECHNOLOGY
EB TECHNOLOGY Nologo START-S102 Instruction and warnings for the installer