
8
2.6 Setting the heating current monitoring
Select “Overcurrent” in the engineering menu, then press the <Set> key.
In the upcoming modication dialogue you determine whether the current monitoring shall take place
with a xed (Fixed) or a floating over current threshold (Float).
Factory setting: Float
Setting range: Float (floating over current threshold) or Fixed (fixed over current threshold)
Notes on settings
For the heating current monitoring, there are two over current thresholds:
– The threshold for the excess current is set to 135% of the maximum nominal current (violet, narrow
dashed line in the following diagram). This threshold value is xed and leads always to a draining
of the cylinder and to an emergency shut-down (Error E25) when exceeded.
– The threshold for the over current is set to 125% of the maximum nominal current (W24/E24). If
this threshold value is exceeded the unit tries to reduce the current under 125 % by repetitive drain-
ings. If after 5 repetitive drainings the current value is still above the threshold value of 125 % the
unit goes on error (Error 24).
This threshold is xed based on the maximum nominal current if Fixed is selected (light blue, con-
tinuous line in the following diagram).
With the function Float the over current threshold (red, dash-dotted line in the following diagram)
can be attened. The function Float allows a faster reaction to changes of the control signal.
Overcurrent
Fixed
Float
Float
Esc Set
Engineering
GFCI :Set
Overcurrent :Float
Min.Request :25/20%
Drain Cool :On
Stop Mode :Set
Esc Set
Example:
Nominal current at 100% steam pro-
duction with 400V 10kg/h = 10 A
Actual steam demand 30%
––> Current setpoint value = 3 A
Draining as a result of over current at
4.5 A with setting “oat”
Draining as a result of over current at
12.5 A with setting “Fixed”
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
Draining characteristics with over current
Nominal current 100%
Current setpoint value
Draining if current value exceeds the set point value by a factor of 1.5 (setting “Float”)
Draining if current value reaches 125 % of the maximum nominal current value (setting “Fixed”)
Forced draining if current value reaches 135 % of maximum nominal current value
Current value in %
Steam production demand in %