Norgren NC-MP-4A4B-12DLA/AL1403 User manual

Operation Manual
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
Before arting work read these inructions.
This manual contains proprietary information. No part of this
publication may be reproduced, transcribed or transmitted
in any form without the written consent of the publisher.
Every eort has been made to ensure that the information
contained in this manual is accurate. All rights reserved.

OM-IO-Link Maer.0201/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
Contents
1. Preliminary note 4
1.1. Legal and copyright information 4
1.2. Purpose of the document 4
1.3. Explanation of Symbols 5
1.4. Modiication history 5
2. Safety instructions 6
2.1. General 6
2.2. Required background knowledge 6
2.3. Safety symbols on the device 6
2.4. Tampering with the unit 6
3. Intended use 7
3.1. Permitted use 7
3.2. Prohibited use 7
4. Function 8
4.1. Parameter setting 8
4.2. Visual indication 8
4.3. PROFINET 8
4.4. IO-Link 9
4.4.1. IO-Link supply 9
4.4.2. Digital inputs 9
4.4.3. Digital outputs 9
4.5. Voltage output 9
5. Mounting 10
5.1. Installing the device 10
6. Electrical connection 11
6.1. Notes 11
6.2. Connect PROFINET ports 12
6.3. IO-Link Ports verbinden 13
6.4. Ground the device 14
6.5. Connect the device 15
7. Operating and display elements 16
7.1. Overview 16
7.2. LED indicators 17
7.2.1. Status LEDs 17
7.2.2. Ethernet ports 17
7.2.3. Voltage supply 18
7.2.4. IO-Link Ports (Class B) 18
7.2.5. IO-Link Ports (Class A) 18
8. Setup 19
8.1. Parameter setting options 19
9. Coniguration 20
9.1. LR DEVICE 20
9.1.1. Remarks 21
9.1.2. First access with LR DEVICE to the IO-Link master 22
9.1.3. IoT: Conigure access rights 23

OM-IO-Link Maer.0301/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
9.1.4. IoT: Conigure the interface to LR AGENT or LR SMARTOBSERVER 24
9.1.5. Fieldbus: Conigure IP settings 24
9.1.6. IO-Link ports: Activate data transfer to LR AGENT or LR SMARTOBSERVER 25
9.1.7. IO-Link ports: Set the operating mode Pin 2 (UA) 25
9.1.8. IO-Link Ports: restrict current intensity 26
9.1.9. IO-Link ports: Set the operating mode Pin 4 27
9.1.10. IO-Link ports: Set the device validation and data storage 28
9.1.11. IO-Link Ports: Set fails-safe values 29
9.1.12. Info: Show device information 29
9.1.13. Firmware: Reset device to factory settings 30
9.1.14. Firmware: Reboot the device 30
9.1.15. Conigure IO-Link devices 31
9.2. PROFINET 32
9.2.1. Install GSD Files 32
9.2.2. Integrate the IO-Link master in the project 33
9.2.3. Conigure the IO-Link master 34
9.2.4. Conigure IO-Link ports 37
9.2.5. Conigure IO-Link devices 39
9.2.6. Read and write process data 39
9.2.7. Read I&M datasets 40
9.2.8. Detect diagnostics and alarms 40
10. Operation 41
10.1. Use web-based management 41
11. Maintenance, repair and disposal 42
11.1. Cleaning process 42
11.2. Update the irmware 43
11.3. Exchanging the IO-Link device 44
12. Factory Settings 45
13. Accessories 46
14. Appendix 47
14.1. Technical data 47
14.1.1. Application 47
14.1.2. Electrical data 48
14.1.3. Inputs/outputs 50
14.1.4. Inputs 50
14.1.5. Outputs 50
14.1.6. Interfaces 51
14.1.7. Environmental conditions 51
14.1.8. Approvals / tests 51
14.1.9. Mechanical data 51
14.1.10. Electrical connection 52
14.2. PROFINET 53
14.2.1. Device structure 53
14.2.2. Parameter data 54
14.2.3. Cyclic data 60
14.2.4. Acyclic data 66
15. Index 69

OM-IO-Link Maer.0401/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
1. Preliminary note
Content
Legal and copyright information 4
Purpose of the document 4
Explanation of Symbols 4
Modiication history 5
1.1. Legal and copyright information
1.2. Purpose of the document
© All rights reserved by IMI Norgren. No part of this manual may be reproduced and used without the consent of IMI Norgren.
All product names, pictures, companies or other brands used on our pages are the property of the respective rights owners:
• AS-i is the property of the AS-International Association, (→ www.as-interface.net)
• CAN is the property of the CiA (CAN in Automation e.V.), Germany (→ www.can-cia.org)
• CODESYS™ is the property of the 3S – Smart Software Solutions GmbH, Germany (→ www.codesys.com)
• DeviceNet™ is the property of the ODVA™ (Open DeviceNet Vendor Association), USA (→ www.odva.org)
• EtherNet/IP® is the property of the → ODVA™
• EtherCAT® is a registered trade mark and patented technology, licensed by Beckhoff Automation GmbH, Germany
• IO-Link® is the property of the → PROFIBUS User Organization, Germany (→ www.io-link.com)
• ISOBUS is the property of the AEF – Agricultural Industry Electronics Foundation e.V., Deutschland (→ www.aef-online.org)
• Microsoft® is the property of the Microsoft Corporation, USA (→ www.microsoft.com)
• Modbus® is the property of the Schneider Electric SE, France (→ www.schneider-electric.com)
• PROFIBUS® is the property of the PROFIBUS User Organization, Germany (→ www.proibus.com)
• PROFINET® is the property of the → PROFIBUS User Organization, Germany
• Windows® is the property of the → Microsoft Corporation, USA
This document is only for device types “IO-Link master - PROFINET gateway 8 port
IP 65 / IP 66 / IP 67” (Part. no.: NC-MP-4A4B-12DLA/AL1403).
It is part of the device and contains information about the correct handling of the product.
Read this document before using the device.
Keep this document during the service life of the device.

OM-IO-Link Maer.0501/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
Version Topic Date
00 New creation of document 12/2020
1.3. Explanation of Symbols
1.4. Modiication history
Important note
Non-compliance can result in malfunction or interference
Information
Supplementary note
Request for action
Reaction, result
→ "see"
abc Cross-reference
123 Decimal number
0x123 Hexadecimal number
0b010 Binary number
[…] Designation of pushbuttons, buttons or indications
WARNING
Warning of serious personal injury.
Death or serious irreversible injuries may result.
CAUTION
Warning of personal injury.
Slight reversible injuries may result.
NOTICE
Warning of damage to property

OM-IO-Link Maer.0601/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
2.4. Tampering with the unit
This document is intended for specialists. Specialists are people who, based on their relevant training and experience, can
identify risks and avoiding potential hazards that may be caused during operation or maintenance of the product.
The document contains information about the correct handling of the product.
2.2. Required background knowledge
2.3. Safety symbols on the device
2. Safety instructions
Content
General 6
Required background knowledge 6
Safety symbols on the device 6
Tampering with the unit 6
2.1. General
The plant manufacturer is responsible for the safety of the plant in which the device is installed.
If the device is used in a way that is not intended by the manufacturer, the
protection supported by the device may be impaired.
Non-observance of the instructions, operation which is not in accordance with use as prescribed below,
wrong installation or incorrect handling can affect the safety of operators and machinery.
Observe these operating instructions.
Adhere to the warning notes on the product.
General warning
Observe instructions in chapter „Electrical connection“ (→ Electrical connection (→ S. 12))!
WARNING
Tampering with the unit.
> In case of non-compliance:
• Possible effects on safety of operators and machinery
• Expiration of liability and warranty
Do not open the devices!
Do not insert any objects into the devices!
Prevent metal foreign bodies from penetrating!

OM-IO-Link Maer.0701/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
The IO-Link master serves as a gateway between intelligent IO-Link devices and the PROFINET
network. The device is designed for use without a control cabinet in the plant construction.
The device may not be used beyond the limits of the technical data (→ Technical data (→ S. 53))!
3.1. Permitted use
3.2. Prohibited use
3. Intended use
Content
Permitted use 7
Prohibited use 7

OM-IO-Link Maer.0801/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
4. Function
4.1. Parameter setting
4.2. Visual indication
4.3. PROFINET
Content
Parameter setting 8
Visual indication 8
PROFINET 8
IO-Link 9
Voltage output 9
The device provides the following coniguration options:
• Parameter setting of the IO-Link master of the NC-MP-4A4B-12DLA/AL1403 with
parameter setting software LR DEVICE and/or PROFINET projection software
• Parameter setting of the connected IO-Link devices (sensors, actuators) with parameter
setting software LR DEVICE and/or PROFINET projection software
• Storage of parameter sets of the connected IO-Link devices for automatic recovery (data storage)
The device has the following visual indicators:
• Status and error indication of the gateway, of the PROFINET connection and of the system
• Status display of the voltage supply
• Status and activity display of the Ethernet connection
• Status, error and short circuit/overload indication of the IO-Link ports
The device offers the following ProiNet functions:
• PROFINET RT Device (Conformance Class C)
• 2-port switch for access to the PROFINET interface; integrated switch complies with RT and IRT according to PROFINET V2.3
• Gateway for transmission of the process and parameter data between the
connected IO-Link devices and the higher-level PROFINET controller
• Coniguration in Run (CiR)
• Supported protocols: SNMP, LLDP, MRP, DCP, RTA, RTC Class 1 (not synchronised)
• Proinet functions: FSU, I&M0 - 4 read / write, S2 redundancy
• Device description: GSDML ile
The following IO-Link functions:
• IO-Link master (IO-Link revision 1.0 and 1.1)
• 8 IO-Link ports for connection of IO-Link devices
• Provision of process data of the connected IO-Link devices for LR
SMARTOBSERVER monitoring software (→ www.norgren.com)

OM-IO-Link Maer.0901/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
The following IO-Link functions:
• IO-Link master (IO-Link revision 1.0 and 1.1)
• 8 IO-Link ports for connection of IO-Link devices
• Provision of process data of the connected IO-Link devices for LR
SMARTOBSERVER monitoring software (→ www.norgren.com)
The device has 8 supplies for IO-Link devices (sensors, actuators).
The X1...X4 ports are class B ports. The ports X5...X8 are Ports Class A.
The pin 2 (UA) of the X1...X4 ports supports different operating modes
(disconnected from power, supply voltage UA, digital output).
The current intensity of the supply voltages US and UA of the X1...X4 ports can be adjusted.
The current intensity of the supply voltage US of the ports X5...X8 can be set.
Every supply provides short circuit monitoring.
The device ensures ire protection for connected IO-Link devices by providing an energy-
limited circuit at the ports (according to IEC61010-1 and Class 2 to UL1310).
The device has 4 additional digital inputs (type 2 according to EN 61131-2).
The digital inputs are on pin 2 of the ports X5...X8.
All inputs refer to the potential of the device supply (pin 3).
The device has 4 digital outputs that can be activated as an option (switching output DC-13 according to IEC 60947-5-1, 20 W).
The digital outputs are connected to pin 2 of the X1...X4 ports.
The digital outputs are supplied with the UA voltage. They refer to the potential of UA (pin 5).
The device has a voltage output (XD2) to supply an additional device. This makes it possible to
supply several Norgren NC range devices with one voltage source (daisy chain).
4.4.1. IO-Link supply
4.4. IO-Link
4.4.2. Digital inputs
4.4.3. Digital outputs
4.5. Voltage output

OM-IO-Link Maer.010 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
5. Mounting
Content
Installing the device 10
5.1. Installing the device
Disconnect power before installation.
Please observe the maximum tightening torque.
Use a plane mounting surface for installation.
Fix the unit to the mounting surface using 2 M5 mounting screws and washers.
• Tightening torque: 1.8 Nm

OM-IO-Link Maer.01101/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
6. Electrical connection
Content
Notes 11
Connect PROFINET ports 12
IO-Link Port connection 13
Ground the device 14
Connect the device 15
6.1. Notes
A qualiied electrician must connect the unit.
The national and international for regulations setting up electrical equipment must be complied with.
The unit is only suitable for operation using SELV/PELV voltages.
Please note the information concerning IO-Link wiring!
This unit contains components that may be damaged or destroyed by electrostatic discharge (ESD).
Please observe the required precautions against electrostatic discharge!
The IP rating of the overall system depends on the protection ratings of the individual
devices, the applied connection elements and the corresponding protective caps.
Provide cables with a strain relief depending on the mounting conditions to avoid ex-
cessive strain on the installation points and the M12 connections.
Ensure correct it and proper assembly of the M12 connecting parts. If these instruc-
tions are not complied with, the speciied protection rating cannot be guaranteed.
For UL applications:
To connect the IO-Link master and the IO-Link devices, only use UL-certiied cables of the CYJV or PVVA cat-
egory with a minimum temperature of 80 °C (75 °C in case of maximum ambient temperature of 40 °C).
Wiring: → Technical data (→ S. 53)
By means of basic insulation according to EN61010-1, the circuits are separated from each other and from device surfaces that
could be touched (secondary circuit with 30 V DC maximum, supplied from mains circuit up to 300 V overvoltage category II).
By means of basic insulation according to EN61010-1, the communication interfaces are separated from each other
and from device surfaces that could be touched (secondary circuit with 30 V DC maximum, supplied from mains circuit
up to 300 V overvoltage category II). They are designed for network environment 0 according to IEC TR62102.

OM-IO-Link Maer.012 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
6.2. Connect PROFINET ports
Connect the device via the M12 socket XF1 and/or XF2 with the PROFINET
network (e.g. PROFINET PLC, additional PROFINET device)
• Tightening torque: 0.6. 0.8 Nm
Connect the device via the M12 socket XF1 and/or XF2 with the IT network
(e.g. PC with parameter setting software LR DEVICE, PC with monitoring software LR
SMARTOBSERVER)
• Tightening torque: 0.6. 0.8 Nm
To connect the devices, use M12 connectors with protection rating IP 65 / IP 66 / IP 67 or
higher (→ Accessories (→ S. 51)).
Cover the unused sockets with M12 protective caps ( art. no.: E73004).
• Tightening torque 0.6. 0.8 Nm
13
NC-MP-4A4B-12DLA
>
6.2 Connect PROFINET ports
►
Connect the device via the M12 socket XF1 and/or XF2 with the
PROFINET network (e.g. PROFINET PLC, additional PROFINET
device)
§
Tightening torque: 0.6. 0.8 Nm
►
Connect the device via the M12 socket XF1 and/or XF2 with the IT
network (e.g. PC with parameter setting software LR DEVICE, PC
with monitoring software LR SMARTOBSERVER)
§
Tightening torque: 0.6. 0.8 Nm
►
To connect the devices, use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 or higher (→Accessories (→S. 51)).
►
Cover the unused sockets with M12 protective caps ( art. no.:
E73004).
§
Tightening torque 0.6. 0.8 Nm

OM-IO-Link Maer.01301/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
Connect the connector of the IO-Link devices to the M12 sockets X1…X8.
• Torque to 0,6...0,8 Nm
• Maximum cable length per port: 20m
Use M12 connectors with at least protection class IP65 / IP6 / IP67 for the connection (→
Accessories (→ S. 51)).
Seal unused sockets with M12 sealing caps.
• Torque: 0,6...0,8 Nm
6.3. IO-Link Port connection
Wiring Notes:
• The power supply of the connected IO-Link devices may only be provided via the NC-MP-4A4B-12DLA/AL1403
• The ports of the device meet the requirements of the IO-Link speciication 1.0 to 1.1.2
• The additional digital output ports X1 … X4 (pin 2) meet the requirements of utilization category DC-13 according
to standard IEC 60947-5-1: 20W. The connected electronics must be electrically designed for this.
• The additional digital input of ports X5 … X8 (pin 2) meet the requirements of type 2 behavior according
to standard EN 61131-2. The connected electronics must be designed electrically for this.
CAUTION
Connection of IO-Link Class A devices Class with Class B ports with 4/5 pole connectors
> Risk of ire
> Impairment of electrical safety
> Malfunctions
To connect IO-Link Class A devices to Class B ports, use 3-pole connectors only!
Detailed information: → IO-Link planning directive (→ www.io-link.com)
14
NC-MP-4A4B-12DLA
CAUTION
Connection of IO-Link Class A devices Class with Class B ports with 4/5 pole connectors
Risk of fire
Impairment of electrical safety
Malfunctions
To connect IO-Link Class A devices to Class B ports, use 3-pole connectors only!
>
6.3 IO-Link Port connection
Wiring Notes:
•
The power supply of the connected IO-Link devices may only be provided via the NC-MP-4A4B-12DLA
•
The ports of the device meet the requirements of the IO-Link specification 1.0 to 1.1.2
•
The additional digital output ports X1 …X4 (pin 2) meet the requirements of utilization category
DC-13 according to standard IEC 60947-5-1: 20W. The connected electronics must be
electrically designed for this.
•
The additional digital input of ports X5 …X8 (pin 2) meet the requirements of type 2 behavior
according to standard EN 61131-2. The connected electronics must be designed electrically for
this.
•
Detailed information: →IO-Link planning directive (→www.io-link.com)
►
Connect the connector of the IO-Link devices to the M12
sockets X1…X8.
§
Torque to 0,6...0,8 Nm
§
Maximum cable length per port: 20m
►
Use M12 connectors with at least protection class IP65 / IP6 /
IP67 for the connection (→Accessories
(→S. 51)).
►
Seal unused sockets with M12 sealing caps.
§
Torque: 0,6...0,8 Nm

OM-IO-Link Maer.014 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
Ground the unit via the mounting screw of the upper mounting lugs.
• Tightening torque: 1.8 Nm
Optional: Connect pin 5 of the port XD1 or XD2 via an L-coded M12 connector with the FE
socket of the power supply.
6.4. Ground the device
The FE potential is connected to the following points of the device:
• Upper mounting lug of the housing
• Ports XD1 and XD2: Pin 5 (FE)
• Ports XF1 and XF2
To ensure the protection of the device against electrical interference and to ensure the safe function of the
device, the housing must be connected to the GND of the installation using the shortest possible route.
15
NC-MP-4A4B-12DLA
>
6.4 Ground the device
The FE potential is connected to the following points of the device:
•
Upper mounting lug of the housing
•
Ports XD1 and XD2: Pin 5 (FE)
•
Ports XF1 and XF2
To ensure the protection of the device against electrical interference and to ensure the safe
function of the device, the housing must be connected to the GND of the installation using the
shortest possible route.
►
Ground the unit via the mounting screw of the upper
mounting lugs.
§
Tightening torque: 1.8 Nm
►
Optional: Connect pin 5 of the port XD1 or XD2 via an L-
coded M12 connector with the FE socket of the power
supply.

OM-IO-Link Maer.01501/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
Disconnect power.
Connect the device via M12 socket X31 to US and UA supplying 24 V DC each
(20...30 V SELV/PELV; according to IEC 61010-1, secondary circuit with maximum
30 V DC, supplied from mains circuit up to 300 V of overvoltage category II).
• Tightening torque: 0.6. 0.8 Nm
• Recommended maximum cable length: 25 m
To connect the device, use L-coded M12 connectors with at least protection rating IP 65 / IP
66 / IP 67 (→ Accessories (→ S. 51)).
Optional: Supply of additional devices (Daisy chain):
Connect additional Master to M12 socket X32 of the NC-MP-4A4B-12DLA/AL1403 (Daisy-
chain function).
• Tightening torque: 0.6. 0.8 Nm
• Recommended maximum cable length: 25 m
To connect the device, use L-coded M12 connectors with at least protection
rating IP 65 / IP 66 / IP 67 (→ Accessories (→ S. 51)).
6.5. Connect the device
In case of cables that are longer than 25 m, take the voltage drop and the
necessary minimum supply voltage of 20 V into consideration!
CAUTION
Exceeding the maximum input current of 12 A
> Fire hazard
Select IU and IA of the power supplies US and UA taking into account the derating
characteristics of the NC-MP-4A4B-12DLA/AL1403 (→ Derating behavior (→ S. 54))!
16
NC-MP-4A4B-12DLA
>
6.5 Connect the device
►
Disconnect power.
►
Connect the device via M12 socket X31 to US and UA supplying 24
V DC each (20...30 V SELV/PELV; according to IEC 61010-1,
secondary circuit with maximum 30 V DC, supplied from mains
circuit up to 300 V of overvoltage category II).
§
Tightening torque: 0.6. 0.8 Nm
§
Recommended maximum cable length: 25 m
►
To connect the device, use L-coded M12 connectors with at least
protection rating IP 65 / IP 66 / IP 67 (→Accessories (→S. 51)).
Optional: Supply of additional devices (Daisy chain):
►
Connect additional Master to M12 socket X32 of the NC-MP-
4A4B-12DLA (Daisy-chain function).
§
Tightening torque: 0.6. 0.8 Nm
§
Recommended maximum cable length: 25 m
►
To connect the device, use L-coded M12 connectors with at least
protection rating IP 65 / IP 66 / IP 67 (→Accessories (→S. 51)).
In case of cables that are longer than 25 m, take the voltage drop and the necessary minimum
supply voltage of 20 V into consideration!
CAUTION
Exceeding the maximum input current of 12 A
Fire hazard
Select IU and IA of the power supplies US and UA taking into account the derating
characteristics of the NC-MP-4A4B-12DLA (→Derating behavior (→S. 54))!

OM-IO-Link Maer.016 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
17
NC-MP-4A4B-12DLA
Content
Overview ...............................................................................................................................................17
LED indicators....................................................................................................................................... 18
7 Operating and display elements
>
7.1 Overview
1
Status LEDs RDY, BF and SF (→Status LEDs
(→S. 18))
2
Status LEDs LNK and ACT of the PROFINET
interfaces 1 (XF1) and 2 (XF2) (→Ethernet ports
(→S. 18))
3
Status LEDs US and UA of the voltage supply
(XD1/XD2) (→Voltage supply (→S. 19))
4
Status LEDs IOL and UA/DO of the IO-Link Class B
ports (X1...X4) (→IO-Link Ports (Class B) (→S. 19))
5
Status LEDs IOL and DI of the IO-Link Port Class A
(X5...X8) (→IO-Link Ports (Class A) (→S. 20))
7. Operating and display elements
Content
Overview 16
LED indicators 17
Status LEDs RDY, BF and SF (→ Status LEDs (→ S. 18))
Status LEDs LNK and ACT of the PROFINET interfaces 1
(XF1) and 2 (XF2) (→ Ethernet ports (→ S. 18))
Status LEDs US and UA of the voltage supply (XD1/XD2) (→ Voltage supply (→ S. 19))
Status LEDs IOL and UA/DO of the IO-Link Class B ports
(X1...X4) (→ IO-Link Ports (Class B) (→ S. 19))
Status LEDs IOL and DI of the IO-Link Port Class A
(X5...X8) (→ IO-Link Ports (Class A) (→ S. 20))
1
1
2
2
2
3
3
4
4
4
4
4
5
5
5
5
5

OM-IO-Link Maer.01701/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
The device only has the following LED indicators:
The RDY LED shows the status of the gateway.
The BF LED (Bus Failure) shows the status of the PROFINET connection. The
SF LED (System Failure) shows the status of the system.
Each Ethernet port has 2 LEDs (LNK and ACT). The LEDs indicate the status of the Ethernet connection.
7.2. LED indicators
7.2.1. Status LEDs
7.2.2. Ethernet ports
Status LED Description
RDY green on Status: OK
ashes 5 Hz Status: Error
ashes (200 ms on, 800 ms off) Status: Firmware update is running
off Status: Gateway not running or gateway booting
BF red on Bus error
ashes 1 Hz No connection to the PROFINET controller
off error-free
SF red on • Error in gateway
• At least 1 IO-Link device sends warning / alarm (temperature, over/under current, over/under voltage, shortcut)
off
error-free
Status LED Description
LNK green on Ethernet connection established
off No Ethernet connection
ACT yellow ashes Data is transmitted via the Ethernet interface.
off No data transmission

OM-IO-Link Maer.018 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
The port for the voltage supply (XD1) has the LEDs with the designation US
and UA. The LEDs indicate the status of the supply voltage.
Each IO-Link Port Class B has 2 LEDs with the designation IOL and UA/DO.
The LEDs show the status of the IO-Link ports.
7.2.3. Voltage supply
7.2.4. IO-Link Ports (Class B)
Status LED Description
US green on Supply voltage US is connected
off either there is no supply voltage or the connected supply voltage is too low
UA green on Supply voltage UA is connected
Off either there is no supply voltage or the connected supply voltage is too low
Status LED Description
IOL yellow Off Port congured as DI/DO: pin 4 (C/Q) = OFF
on Port congured as DI/DO: pin 4 (C/Q) =ON
green ashing 1 Hz Port congured asIO-Link: no IO-Link device found
Flashing with 2 Hz Port congured asIO-Link: Status PREOPERATE
on Port congured asIO-Link: Status OPERATE
red Flashing with 2 Hz Port conguration error or short circuit / overload on US
on Transmission error
UA/DO yellow Off Digital output: Pin 2 (UA) = OFF
on Digital output: Pin 2 (UA) = ON
green Off IO-Link type A supply: Pin 2 (UA) = OFF
on IO-Link type B supply: Pin 2 (UA) = ON (not switchable)
red on Error: Overcurrent or undervoltage
Each IO-Link Port Class A has 2 LEDs labelled IOL and DI. The LEDs indicate the status of the IO-Link port.
7.2.5. IO-Link Ports (Class A)
Status LED Description
IOL yellow Off Port congured as DI/DO: pin 4 (C/Q) = OFF
on Port congured as DI/DO: pin 4 (C/Q) =ON
green ashing 1 Hz Port congured asIO-Link: no IO-Link device found
Flashing with 2 Hz Port congured asIO-Link: Status PREOPERATE
on Port congured asIO-Link: Status OPERATE
red Flashing with 2 Hz Port conguration error or short circuit / overload on US
on Transmission Error
DI yellow Off digital input: pin 2 = OFF
on
digital input: pin 2 = ON

OM-IO-Link Maer.01901/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
8.1. Parameter setting options
The device can be conigured with the following options:
• Software LR DEVICE (→ LR DEVICE (→ S. 23)
• PROFINET projecting software (→ PROFINET (→ S. 35)
When the supply voltages have been switched on, the NC-MP-4A4B-12DLA/AL1403 starts with the factory settings.
The LEDs signal the current operating status of the device and the ports (→ LED indicators (→ S. 18)).
8. Setup

OM-IO-Link Maer.020 01/21
IO Link Maer - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All irmware and electronic iles are provided by ifm.
9. Coniguration
9.1. LR DEVICE
Content
LR DEVICE 20
PROFINET 32
Content
Remarks 21
First access with LR DEVICE to the IO-Link master 22
IoT: Conigure access rights 23
IoT: Conigure the interface to LR AGENT or LR SMARTOBSERVER 24
Fieldbus: Conigure IP settings 24
IO-Link ports: Activate data transfer to LR AGENT or LR SMARTOBSERVER 25
IO-Link ports: Set the operating mode Pin 2 (UA) 25
IO-Link Ports: restrict current intensity 26
IO-Link ports: Set the operating mode Pin 4 27
IO-Link ports: Set the device validation and data storage 28
IO-Link Ports: Set fails-safe values 29
Info: Show device information 29
Firmware: Reset device to factory settings 30
Firmware: Reboot the device 30
Conigure IO-Link devices 31
On delivery, the NC-MP-4A4B-12DLA/AL1403 is conigured with the factory settings
(→ Factory Settings (→ S. 50)). Required software: LR DEVICE (1.6.x or higher) (Part.-no.: QA0011/QA0012)
Popular I/O System manuals by other brands

Moxa Technologies
Moxa Technologies ioLogik E2242 user manual

National Instruments
National Instruments sbRIO-9219 Operating instructions and specifications

Measurement Computing
Measurement Computing PCI-DIO48H user guide

Masibus
Masibus MAS-DI-16-D Series user manual

ICP DAS USA
ICP DAS USA ET-7000/PET-7000 Series user manual

Doepke
Doepke Dupline operating instructions

M-system
M-system R7F4DC-DA16A-J instruction manual

ICP DAS USA
ICP DAS USA WF-2060 quick start

Acromag
Acromag Acropack AP440 Series user manual

Bentel Security
Bentel Security M-IN/OUT manual

Festo
Festo CPX-F8DE-P operating instructions

Automationdirect.com
Automationdirect.com Productivity 1000 P1-08ND3 manual