manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Festo
  6. •
  7. I/O System
  8. •
  9. Festo CPX-F8DE-P User manual

Festo CPX-F8DE-P User manual

CPX-F8DE-P
Input module
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Deutschland
+49 711 347-0
www.festo.com
Operating instruction
8174423
2022-09c
[8174425]
Translation of the original instructions
© 2022 all rights reserved to Festo SE & Co. KG
PI PROFIBUS PROFINET®, PROFIsafe® are registered trademarks of the respec-
tive trademark owners in certain countries.
1Safety instructions
WARNING
Non-observance of safety instructions can result in death, serious injuries or
major material damage.
• Observe the safety instructions and warnings.
1.1 Intended use
The input module CPX-F8DE-P is intended for reliable recording and evaluation of
signals of connected sensors.
The input module provides up to eight secure inputs that can be used by a
higher-order safety controller in a safety function. The communication with the
higher-level safety control is implemented by the secure PROFIsafe protocol via a
PROFIBUS or PROFINET IO fieldbus connection.
The inputs on the input module can be combined for multi-channel sensor appli-
cations. Two inputs combined form a channel pair, which is set separately with
one of 11 function modes. The function modes influence the evaluation of the
input signals and optionally the generation of clock signals.
The characteristics of the inputs comply with the IEC 61131-2 standard for Type 2
digital inputs.
The input module CPX-F8DE-P is a product with safety-relevant functions. The
input module is intended for installation in machines or automation-technology
systems and may be used only as follows:
–in excellent technical condition
–in its original condition, without unauthorised modifications
–exclusively in the configurations stated here
è 5.5 Function modes of the input module
–within the limits of the product defined by the technical data
è 7 Technical data
–in an industrial environment.
NOTICE
Note that the safety engineering system limits of the input module are also its
physical limits.
1.2 Rules for product configuration
Operation of the input module CPX-F8DE-P is permissible exclusively in Festo CPX
terminals.
• Comply with all technical operating limits è 7 Technical data.
Otherwise, malfunctions can occur.
Operation of the CPX-F8DE-P is permitted only in combination with the following
PROFIsafe-capable bus nodes, recognisable by the product labelling on the bus
nodes è 2 Product identification.
Bus node from revision Network protocol
CPX-FB131) 30 PROFIBUS
CPX-FB332) 21 PROFINET IO
CPX-M-FB342) 21 PROFINET IO
CPX-M-FB352) 21 PROFINET IO
CPX-FB432) 50 PROFINET IO
CPX-M-FB442) 50 PROFINET IO
CPX-M-FB452) 50 PROFINET IO
1) è Description of CPX-FB13
2) è Description of CPX-(M)-FB33/34/35/43/44/45
Tab. 1: Permissible PROFIsafe-compatible CPX bus nodes
The CPX-F8DE-P may only be operated with the following manifold blocks:
Manifold block Application examples
CPX-M-AB-4-M12X2-5POL-T Connection of OSSD sensors with a current consumption up to 0.7 A
–Power supply via contacts T0, T2, T4, T6.
Connection of sensors for mechanical switch contacts.
–Clock signals via contacts T0 … T7.
CPX-M-AB-4-M12X2-5POL Connection of OSSD sensors with a current consumption up to 2 A.
CPX-AB-8-KL-4POL Connection of sensors via the terminal strip.
CPX-AB-ID-P Setting of a coded identifier using an 8x DIL switch.
–It is not possible to connect sensors.
Tab. 2: Permissible manifold blocks
The CPX-F8DE-P may only be operated with the following interlinking blocks:
Interlinking block Power supply
CPX-M-GE-EV without
CPX-M-GE-EV-S-7/8-CI P-4P with system supply, connection: 7/8" (4-pin)
CPX-M-GE-EV-S-7/8-5POL with system supply, connection: 7/8" (5-pin)
CPX-M-GE-EV-S-PP-5POL with system supply, connection: push-pull (5-pin)
CPX-M-GE-EV-S-M12-5POL with system supply, connection: M12 (5-pin)
CPX-M-GE-EV-Z-7/8-5POL with additional supply, connection: 7/8" (5-pin)
CPX-M-GE-EV-Z-PP-5POL with additional supply, connection: push-pull (5-pin)
CPX-M-GE-EV-W-M12-5POL with forwarding supply, connection: M12 (5-pin)
Tab. 3: Permissible interlinking blocks
Detailed information about the product, the supported product versions and
required software versions as well as the permissible components of the
CPX terminal can be found in the CPX system description P.BE-CPX-SYS-...
è www.festo.com/sp.
Information about permissible configurations of the CPX terminal in com-
bination with the input module can also be found in the catalogue
è www.festo.com/catalogue.
1.3 Foreseeable misuse
The following foreseeable misuse is among those not approved as intended use:
–outdoor operation
–use in non-industrial areas
–use outside the limits of the product defined in the technical data
–use with inappropriate function modes
–unauthorised modifications.
NOTICE
The use of connection and interlinking blocks that are not specified is not permis-
sible è 1.2 Rules for product configuration.
NOTICE
The use of the input module CPX-F8DE-P for implementation of safety circuits is
not permissible in the following cases:
• in a CPX terminal equipped with CPX-FEC or CPX-CEC
• in a CPX terminal of variant P
• in configurations other than the configurations stated
è 5.5 Function modes of the input module.
NOTICE
In the event of damage caused by unauthorised manipulation or use other than
the intended use, the guarantee will be invalidated and the manufacturer will not
be liable for damages.
1.4 Achievable safety classification
The CPX-F8DE-P can be used to implement safety functions up to:
–Performance Level e, Cat. 4 in accordance with EN ISO 13849-1
–Safety integrity level SIL 3 in accordance with EN 61508
–Performance Limit SIL CL 3 in accordance with EN 62061.
The achievable safety classification of the overall safety device depends on the
set function mode as well as other components used to implement the safety
function.
•Make sure that the overall safety function of the system is analysed and
validated.
It is the responsibility of the operator to determine and verify the required
safety classification (safety integrity level, performance level and category) of
the system.
• Be aware of the residual risks that remain in your system despite the meas-
ures to integrate safety in the design, despite safety precautions and despite
the supplementary protective measures.
The residual risks are determined, among other things, by your safety regula-
tions and the safety characteristics of your system.
NOTICE
• Test the functionality of the safety device at adequate intervals. Recommenda-
tion:
• at least 1x per year for PL d
• at least 1x per month for PL e
The operator is responsible for selection of the type of test and the time intervals
between the tests.
• Choose the test so that smooth functioning of the safety device in interaction
with all components can be verified and is documented.
1.5 Failures due to a common cause (Common Cause Failure – CCF)
Common cause failures cause the loss of the safety function, since all channels in
a multichannel system fail simultaneously.
The following measures ensure that common cause failures are prevented:
• Comply with operating voltage limits
• Comply with signal voltage limits
• Comply with temperature and environmental conditions.
The application may result in additional measures to avoid common cause fail-
ures.
1.6 Requirements for product use
• Make this brief description available to the design engineer, installation tech-
nician and personnel responsible for commissioning the machine or system in
which this product is used.
• Keep this brief description throughout the entire product lifecycle.
• Make sure that the specifications in the documentation are observed at all
times. Also comply with the documentation for the other components and
modules (e.g. bus nodes, pneumatics).
•Take into consideration the legal regulations applicable for the location as
well as:
–instructions and standards
–regulations of the testing organisations and insurers
–national specifications.
•Remove all packaging, such as foils, caps and cardboard. The material used
in the packaging has been specifically chosen for its recyclability (exception:
oiled paper = residual waste).
•Assembly must be performed in a professionally correct manner. To maintain
the IP degree of protection:
–screw the manifold block tightly to seal it è 4.2 Disassembly and mounting
–mount cable entry and seals in a professionally correct manner
–seal unused connections with cover caps.
•Make sure that after a safety requirement the safety control unit monitors and
controls the restart of the system.
•Make sure that, after every safety requirement resulting from a self-diagnostic
test, the system does not automatically eliminate errors and restart itself.
1.7 Technical prerequisites
General information on correct and safe use of the product, which must be
observed at all times:
•Comply with the technical operating limits è 7 Technical data.
Only then is operation of the product guaranteed in accordance with the
relevant safety regulations.
•When connecting standard auxiliary components, also observe the specified
critical limits for temperatures, electrical data and torques.
1.8 Training of qualified personnel
The device may only be commissioned by trained, qualified control and automa-
tion technology technicians, who are familiar with:
–the installation and operation of control systems
–the applicable instructions for operating safety engineering systems
–the applicable instructions for accident prevention and occupational safety
–the documentation for the product.
NOTICE
Work on safety engineering systems may only be carried out by qualified per-
sonnel trained in safety engineering.
1.9 Product conformity
The product-relevant directives are listed in the declaration of conformity
è www.festo.com/sp.
Product conformity
in accordance with EU EMC Directive
in accordance with EU Machinery Directive
in accordance with EU RoHS Directive
to UK EMC Regulations
to UK Supply of Machinery Regulations
to UK RoHS Regulations
Tab. 4: Product conformity
1.10 UL/CSA certification
Certain configurations of the product have been certified by Underwriters Labora-
tories Inc. (UL) for the USA and Canada.
These configurations bear the following mark:
UL Recognized Component Mark for Canada and the United States
Only for connection to an NEC Class 2 supply.
Raccorder Uniquement a un circuit de Classe 2.
Observe the following if your application must be in compliance with the UL
requirements:
–Regulations for compliance with the UL certification can be found in the sepa-
rate UL-specific special documentation.
The relevant technical data in that documentation also takes priority if it does
not influence the safety engineering values in an impermissible manner.
–The technical data in this documentation may show values deviating from this.
1.11 Specified standards
Version
EN ISO 13849-1:2015 EN 61508 Part 1-7:2010
EN ISO 13849-2:2012 EN 62061:2021
EN 13851:2019 IEC 61131-2:2017
EN 60529:1991 + A1:1999 +
A2:2013 + AC:2019
IEC 60204-1:2018
Tab. 5: Standards specified in the document
1.12 Transport and storage conditions
• Protect the product from excessive stress factors during transport and
storage, such as:
–mechanical loads
–impermissible temperatures
–moisture
–aggressive atmospheres.
•Store and transport the product in its original packaging. The original pack-
aging offers sufficient protection from typical stresses.
1.13 Service
Contact your local Festo Service centre in the event of technical problems.
2 Product identification
The product identification is the module identifier plus the product labelling. The
module identifier can be seen through the transparent covering on the manifold
block.
Module identifier Meaning
F8
DI
P
FP
0
1
2
3
4
5
6
7
1
–Module identifier 1:
F8DIP (F=Safety; 8=Number; D=Digital;
I=Inputs; P=PROFIsafe)
Tab. 6: Module identifier
The product labelling enables identification of the product and shows the fol-
lowing information, for example:
Product labelling (example) Meaning
CPX-F8DE-P Order reference
2597424 Part number
MM-YYYY:XX Rev XX MM = manufacturing month
YYYY = manufacturing year
XX = plant number
Rev XX = revision code
CE, UKCA and DataMatrix code Identification
12345678901234 14-character serial number
Festo SE & Co. KG Manufacturer
DE-73734 Esslingen Manufacturer’s address
Tab. 7: Product labelling (example)
Additional information can be found in the CPX system description CPX-SYS-...
• Before using an input module, check whether the revision of the bus node
corresponds to the requirements of the input module
è Tab. 1 Permissible PROFIsafe-compatible CPX bus nodes.
This brief description applies to the following product
Product Part number Revision1)
CPX-F8DE-P 2597424 Rxx
1) xx stands for a number from 01 to 99
Tab. 8: Applicability
3 Connection and display components
3.1 Design of the input module
1 2 3
4
5
6
7
8
9
10
Fig. 1: Design of the input module CPX-F8DE-P
1
Manifold block CPX-M-AB-4-
M12X2-5POL(-T)
2
Manifold block CPX-AB-8-
KL-4POL
3
Manifold block CPX-AB-ID-P with
internal 8x DIL switch for coding
4
Electronics module CPX-F8DE-P
5
10-way DIL switch for PROFIsafe
address
6
Interlinking block with busbars,
e.g. CPX-M-GE-EV
7
Product labelling
8
Electrical plug connector
between electronics module and
manifold block
9
LEDs of the electronics module
10
Retaining screws
NOTICE
Malfunctions possible due to missing shielding.
• Use only metal interlinking blocks.
4Installation
WARNING
Electric voltage
Injury caused by electric shock, damage to machine and to system.
• Only use PELV circuits in accordance with IEC 60204-1 (protective extra-low
voltage, PELV) for the electrical power supply.
• Observe the general requirements of IEC 60204-1 for PELV circuits.
• Use only voltage sources that guarantee a reliable electric separation of oper-
ating and load voltage in accordance with IEC 60204-1.
• Always connect all power circuits for the operating and load voltage supplies
UEL/SEN, UVAL and UOUT.
Protection from electric shock (protection from direct and indirect contact) in
accordance with IEC 60204-1 (Electrical equipment of machines, General require-
ments) is guaranteed with the use of PELV circuits.
NOTICE
Electronics modules include electrostatically sensitive devices.
Incorrect handling can cause damage to the electronics modules.
• Observe the handling specifications for electrostatically sensitive devices.
•Discharge static electricity from your body before assembling or disassembling
modules to protect the modules.
Observe the instructions for electrical power supply (Protective Extra-Low Voltage,
PELV) to CPX terminals in the CPX system description CPX-SYS-... .
Monitoring of the sensor wiring for cross circuits depends on the functional
modes used è 5.5 Function modes of the input module.
• Switch off the supply voltages before assembly or installation.
•Switch on the electrical supply voltage only when the product is completely
mounted and all installation work is finished and checked.
4.1 Setting the PROFIsafe address
The electronics module of the CPX-F8DE-P includes a 10x DIL switch for setting an
address for the PROFIsafe communications. The CPX-F8DE-P must be disassem-
bled in order to change the address.
NOTICE
Damage to the electronics module due to incorrect handling.
Before mounting and removal è 4.2 Disassembly and mounting:
• Switch off operating voltage supply.
NOTICE
This PROFIsafe module accepts every PROFIsafe host address and thus fulfils the
requirements for PROFIsafe address type 1.
1. Remove manifold block è 4.2 Disassembly and mounting.
2. Carefully set the PROFIsafe address at the 10x DIL switch with a small screw-
driver. Permitted addresses: 1 … 1022 (binary coded).
10x DIL
switch
Address value Addressing example
DIL 1 = 1
DIL 2 = 2 + 2
DIL 3 = 4
DIL 4 = 8
DIL 5 = 16
DIL 6 = 32
DIL 7 = 64 + 64
DIL 8 = 128
DIL 9 = 256
DIL 0 = 512 + 512
= 578
3. Replace the manifold block è 4.2 Disassembly and mounting.
4.2 Disassembly and mounting
The plugs connected to the manifold block can remain attached while disassem-
bling the manifold block.
For disassembly è Fig. 1:
1. Switch off the operating and load voltage supply of the CPX terminal.
2. Unscrew retaining screws aJ.
3. Carefully lift off manifold block 1, 2 or 3.
4. If required: carefully remove the electronics module 4 from the busbars.
For mounting:
•Prior to mounting make sure that the PROFIsafe address on the electronics
module is set correctly è 4.1 Setting the PROFIsafe address.
NOTICE
•Make sure that the interlinking block (è Fig. 1, 6 ) is clean and free from
foreign matter, especially in the area of the contact rails.
• Check seal and seal surfaces. Replace damaged parts.
• Make sure the connecting surfaces are clean. This serves to maintain the
sealing effect and avoid contact errors.
1. Place the electronics module 4 in the proper position and without jamming
into the interlinking block 6 and press it in until it stops.
2. Align manifold block 1, 2 or 3 and place it on the electronics module.
3. Screw retaining screws aJ into the existing threads.
4. Tighten retaining screws crosswise.
Tightening torque: 0.9 … 1.1 Nm.
4.3 Pin allocation on the manifold block
Pin allocation CPX-M-AB-4-M12X2-5POL CPX-M-AB-4-M12X2-5POL-T1)
2
3
1
5
4
X1
1: 24 V
2: E1
3: 0 V
4: E0
5: FE
X3
1: 24 V
2: E5
3: 0 V
4: E4
5: FE
X1-T
1: T0
2: E1
3: 0 V
4: E0
5: T11)
X3-T
1: T4
2: E5
3: 0 V
4: E4
5: T51)
X2
1: 24 V
2: E3
3: 0 V
4: E2
5: FE
X4
1: 24 V
2: E7
3: 0 V
4: E6
5: FE
X2-T
1: T2
2: E3
3: 0 V
4: E2
5: T31)
X4-T
1: T6
2: E7
3: 0 V
4: E6
5: T71)
1) Never connect pin 5 to functional earth (FE) on this manifold block.
Tab. 9: Pin allocation on the manifold block CPX-M-AB-4-M12X2-5POL(-T)
CPX-AB-8-KL-4POL
Pin allocation X1, X2, X3, X4 Pin allocation X5, X6, X7, X8
X1
0: 24 V
1: 0 V
2: E0
3: FE1)
X2
0: T0
1: T1
2: E1
3: FE1)
X3
0: 24 V
1: 0 V
2: E2
3: FE1)
X4
0: T2
1: T3
2: E3
3: FE1)
X5
0: 24 V
1: 0 V
2: E4
3: FE1)
X6
0: T4
1: T5
2: E5
3: FE1)
X7
0: 24 V
1: 0 V
2: E6
3: FE1)
X8
0: T6
1: T7
2: E7
3: FE1)
1) FE = functional earth
Tab. 10: Pin allocation on the manifold block CPX-AB-8-KL-4POL
5Commissioning
5.1 Starting behaviour of the input module
The following LEDs are used for commissioning and on-site diagnostics and are
located under the transparent cover of the input module:
1
2
3
4
Fig. 2: LED display of the input module
CPX-F8DE-P
1
Module error LED (red)
2
FP-LED (green) – fail-safe mode pro-
tocol
3
Channel error LED (red); one per input
channel
4
Status LED (green); one per input
channel
NOTICE
The LED display of the input module is not designed for safety purposes.
• Please note that these LEDs should not be used for evaluation during safety-
related activities.
When the operating voltage supply UEL/SEN is switched on, the module error LED
1 lights for approx. 500 ms.
The FP-LED 2 flashes until the input module is correctly parameterised by a
PROFIsafe master.
The following LEDs are on in the normal operating status:
–FP-LED 2
–Status LEDs 4 of the active input channels
The status LEDs on inactive input channels and the module error LEDs 1 and
channel error LEDs 3 do not light.
NOTICE
The identifier of the LEDs corresponds to the physical contacts E0 to E7.
• Note the special position of the input signals in the input image of the CPX-
F8DE-P.
Additional information can be found in the CPX system description CPX-SYS-...
5.2 Parameter
CBUS parameter1)
Offset Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Comment
22 0 0 0 0 0 0 0 0 Defined PROFIsafe
address
(è 4.1 Setting the
PROFIsafe address)
low, high
16 bits = 2 bytes
23 0 0 0 0 0 0 0 0
1) Read-only access
Tab. 11: Parameter
5.3 I/O image
The safety features of PROFIsafe mean that the input module CPX-F8DE-occupies
7 bytes for outputs and 6 bytes for inputs in the process image of the CPX
terminal.
Output image (PAA)
The output image consists of 7 bytes as follows:
–3 bytes output data (F-user data) è Tab. 12 Bit pattern of the output data
(F-user data, bytes 0, 1 and 2)
–1 control byte in the PAA (for PROFIsafe communication)
–3 CRC bytes (for PROFIsafe communication).
Bit pattern of the output data
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0 1/0 1/0
1 = channel-based passivation, 0 = module-based passivation
1 = acknowledgment of a channel error
1 8 4 2 1 8 4 2 1
Function mode for channel pair 7/6 Function mode for channel pair 5/4
28 4 2 1 8 4 2 1
Function mode for channel pair 3/2 Function mode for channel pair 1/0
Tab. 12: Bit pattern of the output data (F-user data, bytes 0, 1 and 2)
Input image (PAE)
The input image consists of 6 bytes as follows:
–2 bytes input data (F-user data) è Tab. 13 Bit pattern of the input data (F-user
data, byte 0 and byte 1)
–1 status byte in the PAE (for PROFIsafe communication)
–3 CRC bytes (for PROFIsafe communication).
Bit pattern of the input data: byte 0 and byte 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 E7 E5 E3 E1 E6 E4 E2 E0
Input image
1Q7 Q5 Q3 Q1 Q6 Q4 Q2 Q0
Qx = 1: signal Ex is valid
Qx = 0: signal Ex is invalid, incorrect input function due to function mode/channel
error/module error
Tab. 13: Bit pattern of the input data (F-user data, byte 0 and byte 1)
5.4 Safe system status
Whenever an error is diagnosed in the input information for the module, the
reaction depends on the selected module operating mode:
–With the “module-based passivation” operating mode (PAA byte 0, bit 1 = 0),
the module passivation is performed in accordance with the PROFIsafe specifi-
cation.
–For the operating mode “channel-based passivation” (PAA byte 0, bit 1 = 1), the
relevant channel bits (Ex, Qx) in the input image (PAE byte 0 and 1) are set to
logic zero.
Module passivation is based on the PROFIsafe specification in the case of a
diagnosed internal module error.
The PROFIsafe timeout is the system reaction to a massive, stochastic failure of
the module hardware.
5.5 Function modes of the input module
The input module CPX-F8DE-P includes various function modes for implementa-
tion of safety circuits with recommended sensors (è Tab. 28 Recommended
sensors). The function modes can be set separately for every channel pair.
NOTICE
The following applies for all applications of sensors and switches in combination
with the corresponding function modes of the input module CPX-F8DE-P:
The achievable safety integrity level, performance level and category of your
system are limited by the component of the safety chain with the lowest charac-
teristic value.
• Use only switches and sensors that meet the safety engineering requirements
of the application.
• When using well-tried components in accordance with EN 13849-2, Table D.3,
calculate the safety classification from the manufacturer’s specifications.
The specifications of the switches and sensors include information on safety
engineering considerations and operating conditions.
NOTICE
Some function modes may restrict the manifold blocks that can be selected.
• Make sure that the manifold block required for the safety function is used.
NOTICE
Malfunctions at unused inputs are possible.
• Make sure that function mode 0 is always set for unused channel pairs.
For function modes with clock signals:
• Clock outputs T1, T3, T5 and T7 have the same clock signal.
• Clock outputs T0, T2, T4, and T6 are out of phase to one other and to
T1/T3/T5/T7.
Function mode 0 – no signal evaluation
Circuit diagram /channel pair connec-
tions
Comment
T0/ T2/ T4/ T6/
24 V 24 V 24 V 24 V
0 V
E1 E3 E5 E7
E0 E2 E4 E6
T1/
FE
T3/
FE
T5/
FE
T7/
FE
Signals are not evaluated on channel pairs with
this function mode.
When switching on the input module, all channel
pairs are in this mode by default.
This function mode is used for initial commis-
sioning of wiring and sensors.
Both channels always generate a logic 0 as input
information and a logic 1 as qualifier in the input
image.
The signals of connected sensors are displayed
only at the status LEDs.
Functional safety
There is no safety-oriented evaluation in function mode 0.
Tab. 14: Function mode 0
Function mode 1 – 1oo1 (T0, T2, T4, T6 static on)
Circuit diagram /channel pair connec-
tions
Comment
24 V 24 V 24 V 24 V
0 V
T0/ T2/ T4/ T6/
E1 E3 E5 E7
E0 E2 E4 E6
T1/
FE
T3/
FE
T5/
FE
T7/
FE
Signal evaluation of up to 2 independent single-
channel switches/sensors (N/O or N/C) per
channel pair.
In this function mode, T0, T2, T4 and T6 are at
static 24 V DC.
Functional safety
–PL c, Cat. 1/SIL 1
with switch/sensor tried and tested in accordance with EN 13849-2, Table D.3,
and with wiring protection of the customer application according to EN 13849-2, Table D.4
Tab. 15: Function mode 1 – 1oo1
Function mode 2 – 1oo1 test (T0, T2, T4, T6 static off)
Circuit diagram /channel pair connec-
tions
Comment
0 V
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1/
FE
T3/
FE
T5/
FE
T7/
FE
Signal evaluation of up to 2 single-channel
switches/sensors (N/O or N/C) per channel pair.
In this function mode, T0, T2, T4 and T6 are not
connected to voltage.
Function mode 2 can be used as a test mode
when you connect sensors for function mode 1.
A safety control that alternately uses the function
mode 1 and 2 can in this way generate user-spe-
cific test signals and evaluate whether a zero
crossover has taken place.
Software-generated test signals only work with
the following manifold blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
Safety requirements cannot be evaluated by the
safety control unit during the test period.
Function mode 2 can be alternatively used to
reset sensors with self-monitored electronic out-
puts.
Functional safety
–PL c, Cat. 1/SIL 1
with switch/sensor tried and tested in accordance with EN 13849-2, Table D.3,
and with wiring protection of the customer application according to EN 13849-2, Table D.4
Tab. 16: Function mode 2 – 1oo1 test
Function mode 3 – 1oo1 T (with clock signal monitoring)
Circuit diagrams /channel pair con-
nections
Comment
0 V
A T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
Signal evaluation of up to 2 independent
single-channel switches/sensors per channel
pair with individually clocked sensor power via
T0, T2, T4, T6 and with common clock signal via
T1, T3, T5, T7.
This function mode is used to detect short circuits
and cross circuits.
Circuit diagram A
2 single-channel switches/sensors (N/O or N/C).
Safety-related evaluation only with manifold
blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
Circuit diagram B
2 single-channel safety sensors with test input.
Safety-related evaluation only with manifold
block CPX-AB-8-KL-4POL.
8 safety sensors can be connected to this mani-
fold block.
24 V
0 V
B
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
Functional safety
–PL c, Cat. 1/SIL 1
with switch/sensor tried and tested in accordance with EN 13849-2, Table D.3
–to PL c, Cat. 3/SIL 2
with certified switches/sensors of an appropriate safety classification
and with wiring protection of the customer application according to EN 13849-2, Table D.4,
and with testing of the safety application once a year
–to PL e, Cat. 3/SIL 3
with certified sensor of an appropriate safety classification
and with wiring monitoring by the connected sensor (circuit diagram B).
Tab. 17: Function mode 3 – 1oo1 T
Function mode 4 – 1oo1 D (antivalent)
Circuit diagrams /channel pair con-
nections
Comment
0 V
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
Signal evaluation of up to two independent dual-
channel switches/sensors (internally antivalent,
N/O or N/C) or up to 4 operationally tested
switches per channel pair.
The clock signals at E1, E3, E5 and E7 are wired
as a mirror image of E0, E2, E4, E6. This function
mode tests the switch function and wiring of the
sensors.
–Use only sensors with antivalent outputs in
which the one contact opens before the other
contact closes.
–Ensure that the N/O and/or N/C switches of
sensors are connected with the appropriate
clock signal connections for the channel pair
è Circuit diagram.
–Note that before every actuation a zero cross-
over is required (normally closed contact of
the N/C switch closed).
Safety-related evaluation only with the following
manifold blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
0 V
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
Functional safety
–PL e, Cat. 3/SIL 3
with 2 independent switches/sensors operationally tested according to EN 13849-2, Table D.3,
these switches/sensors are to be implemented as independent systems in the customer applica-
tion
–to PL e, Cat. 3/SIL 3
with certified switches/sensors of an appropriate safety classification.
Tab. 18: Function mode 4 – 1oo1 D
Function mode 5 – 1oo2 (equivalent)
Circuit diagram /channel pair connec-
tions
Comment
A T0/ T2/ T4/ T6/
E1 E3 E5 E7
E0 E2 E4 E6
T1/
FE
T3/
FE
T5/
FE
T7/
FE
24 V
0 V
24 V 24 V 24 V
Signal evaluation of a sensor (typically OSSD),
which switches both signals of the channel pair
simultaneously.
The sensor can monitor short circuits and cross
circuits.
Circuit diagram A
A dual-channel switch/sensor (internally equiva-
lent) per channel pair with uniformly unclocked
sensor power.
In this function mode, T0, T2, T4 and T6 are at
static 24 V DC.
Circuit diagram B
OSSD sensor
FE connection of the sensor via the M12 plug
connector fitting of the module
B
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
FE
0 V
24 V 24 V 24 V 24 V
Functional safety
–to PL d, cat. 2 / SIL 2
with certified switches/sensors of an appropriate safety classification
and with automatic testing of the safety function by the machine within 24 hours
–to PL d, cat. 2 / SIL 3
with certified switches/sensors of an appropriate safety classification
and with wiring protection of the customer application according to EN 13849-2, Table D.4,
and with automatic testing of the safety function by the machine within 24 hours
–to PL e, Cat. 4/SIL 3
with certified sensor (OSSD) of an appropriate safety classification
and with wiring monitoring by the connected sensor (circuit diagram B).
Tab. 19: Function mode 5 – 1oo2
NOTICE
Note on function mode 5
Malfunction during use of OSSD sensors on the manifold block
CPX-M-AB-4-M12X2-5POL-T.
The connection of an FE contact to Pin 5 on an M12 socket causes a short circuit.
This causes malfunctioning signals T1, T3, T5 and T7.
The input module reports module error 02: “Short circuit 0 V at clock signal
output T1357”.
• Connect the FE contact of a sensor only to the M12 plug screw connection of
the module.
Function mode 6 – 1oo2 T (equivalent, with clock signal monitoring)
Circuit diagram /channel pair connec-
tions
Comment
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
0 V
Signal evaluation of a dual-channel switch/sensor
(internally equivalent) per channel pair with indi-
vidually clocked power supply.
This function mode is used to detect short circuits
and cross circuits.
This function mode is particularly suitable for
applications that expect fast reactions (e.g. emer-
gency stop, certified switches/sensors).
Safety-related evaluation only with the following
manifold blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
Functional safety
–to PL e, Cat. 3/SIL 2
with certified switches/sensors of an appropriate safety classification
–to PL e, Cat. 4/SIL 3
with certified switches/sensors of an appropriate safety classification
and with automatic testing of the safety function by the machine within 24 hours
–to PL e, Cat. 4/SIL 3
with certified switches/sensors of an appropriate safety classification
and with wiring protection of the customer application according to EN 13849-2, Table D.4.
Tab. 20: Function mode 6 – 1oo2 T
Function mode 7 – 1oo2 D (two-hand control device EN 13851 Type IIIc)
Circuit diagram /channel pair connec-
tions
Comment
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
0 V
Signal evaluation of up to 2 dependent two-
channel switches/sensors (internally antivalent,
N/O or N/C) per channel pair, with time moni-
toring of signal change.
The clock signals at E1, E3, E5 and E7 are wired as
a mirror image of E0, E2, E4, E6.
–Pressing both pushbuttons within 500 ms gen-
erates a logic 1 in the input image of the
channel pair.
–Note that a zero crossing is required before
every actuation (both N/C standby contacts
closed).
–Use only antivalent switches in which the one
contact opens before the other contact closes.
–Ensure that the N/O and/or N/C switches of
sensors are connected with the appropriate
clock signal connections for the channel pair
è Circuit diagram.
Safety-related evaluation only with the following
manifold blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
Functional safety
–PL e, Cat. 4/SIL 3
with 2 switches/sensors, wiring and safety function in accordance with EN 13851 Type IIIC.
Tab. 21: Function mode 7 – 1oo2 D
Function mode 8 – 1oo2 T (equivalent, with clock signal monitoring, robust)
Circuit diagram /channel pair connec-
tions
Comment
0 V
T0 T2 T4 T6
E1 E3 E5 E7
E0 E2 E4 E6
T1 T3 T5 T7
Signal evaluation of mechanical contacts on a
two-channel switch/sensor (internally equivalent)
or of 2 independent, tried and tested switches.
This function mode is equivalent to function
mode 6, but is insensitive to bouncing contacts
due to extended evaluation time.
This function mode is thus not suitable for appli-
cations that expect fast reactions (e.g. light cur-
tain).
–Note the extended reaction time.
–Use this function mode only with an intended
maximum request rate of 1 per 60 s.
Safety-related evaluation only with the following
manifold blocks:
–CPX-M-AB-4-M12X2-5POL-T
–CPX-AB-8-KL-4POL.
Functional safety
–to PL e, Cat. 3/SIL 2
with certified switch/sensor of an appropriate safety classification or 2 independent tried and
tested switches in accordance with EN 13849-2, Table D.3
–to PL e, Cat. 4/SIL 3
with certified switch/sensor of an appropriate safety classification or 2 independent tried and
tested switches in accordance with EN 13849-2, Table D.3,
and with automatic testing of the safety function by the machine within 24 hours
–to PL e, Cat. 4/SIL 3
with certified switch/sensor of an appropriate safety classification or 2 independent tried and
tested switches in accordance with EN 13849-2, Table D.3,
and with wiring protection of the customer application according to EN 13849-2, Table D.4.
Tab. 22: Function mode 8 – 1oo2T (robust)
Function mode 9 – 1 of N (one of N)
Circuit diagram /contacts Comment
0
1
2
3
E3
T2/24 V
T4/24 V
0 V
0 V
E2
T3/FE
E5
E4
T5/FE
Evaluation of one of max. 8 signals with monitoring of signal
change over time. The input image is switched 100 ms after
actuation.
This function mode serves to evaluate a mode selector switch
or a rotary indexing table.
–Use only consecutive channel pairs for channel bundling.
–Activate this function mode for all channel pairs in use.
Variants: 1 of 2, 1 of 4, 1 of 6 or 1 of 8.
The circuit diagram shows the variant “1 of 4” as an example.
The directly consecutive channel pairs E2/E3 and E4/E5 are
used, which must both be set to function mode 9. The power
supply can be optionally switched from T2 or 24 V to one of
the inputs E2, E3, E4, E5.
Required for this example: channel pairs E0/E1 and E6/E7 are
not configured to function mode 9
è Tab. 24 Function mode 9 for multiple channel pairs for up to
2 circuits.
Functional safety
–PL c, Cat. 1/SIL 2
with tried and tested switches/sensors in accordance with EN 13849-2, Table D.3
–to PL e, Cat. 3/SIL 3
with certified switches/sensors of an appropriate safety classification.
Tab. 23: Function mode 9 – 1 of N
Multiple channel pairs in function mode 9
NOTICE
Ensuring operational reliability.
When evaluating more than two signals in a circuit:
• Use directly consecutive channel pairs.
When configuring two independent “1 of N” circuits on one input module:
• Ensure that the channel pairs used for the different circuits are not directly
consecutive to one another.
The following table shows all permitted configurations for setting function mode 9
for several channel pairs.
Channel pair E0 E1 E2 E3 E4 E5 E6 E7
“1 of 4” circuits Mode 9 Mode 9
Mode 9 Mode 9
Mode 9 Mode 9
"1 of 4" and "1 of 2"
circuits
Mode 9 Mode 9 Mode 9
Mode 9 Mode 9 Mode 9
“1 of 6” circuits Mode 9 Mode 9 Mode 9
Mode 9 Mode 9 Mode 9
“1 of 8” circuits Mode 9 Mode 9 Mode 9 Mode 9
Two independent
“1 of 2” circuits
Mode 9 Mode 9
Mode 9 Mode 9
Mode 9 Mode 9
Tab. 24: Function mode 9 for multiple channel pairs for up to 2 circuits
•Set the remaining channel pairs as desired – but not to function mode 9 –.
Function mode 10 – coded identifier
8x DIL switch DIL Valu
e
Input Comment
8 Parity E7 Evaluation of a coded identifier by DIL
switch in manifold block CPX-AB-ID-P.
To use the coded identifier:
–Switch all channel pairs to function
mode 10.
Set coded identifier:
1. Set the desired identifier with
switches 1 to 7.
Then use values from 1 to 126.
2. If you have an odd number of
switches (1 to 7) set to ON: also set parity
bit (switch 8) to ON.
Input image
A 0 is always output in the input image
instead of the parity bit so the set identifier
in the safety control can always be used
directly.
7 64 E5
6 32 E3
5 16 E1
4 8 E6
3 4 E4
2 2 E2
1 1 E0
Functional safety
–PL e, Cat. 3/SIL 3
with certified switch of an appropriate safety classification or independent tried and tested
switches in accordance with EN 13849-2, Table D.3
and with protection of the application against simple manipulation.
The manifold block CPX-AB-ID-P meets these requirements for functional safety without any supple-
mentary measures.
Tab. 25: Function mode 10 – coded identifier
6 Service, repair, disposal
The input module does not include parts requiring service or wearing parts.
NOTICE
Repairs are not allowed. Repairs will result in a lapse in conformity of the input
module. A professional replacement of the electronics module is permissible.
NOTICE
Incorrect behaviour is possible.
• Always replace the input module if there is an internal fault.
• Return the unmodified defective input module to Festo for analysis with a
description of the error and the application.
The material used in the packaging has been specifically chosen for its recycla-
bility.
For final disposal of the input module, please contact a certified waste disposal
business for electronic (WEE) scrap.
7 Technical data
General technical data of the CPX terminal è CPX-SYS-… system description
Approval information
CE
Type-examination The functional safety engineering of the product has
been certified by an independent testing body, see
EC-type examination certificate è www.festo.com/sp
Certificate issuing authority TÜV Rheinland, Certification Body of Machinery, NB
0035
Approval information
Certificate no. 01/205/5444.01/21
UKCA
Type-examination The functional safety engineering of the product has
been certified by an independent body, see UK-type
examination certificate è www.festo.com/sp
Certificate issuing authority TÜV Rheinland UK Ltd, UK Approved Body No. 2571
Certificate no. 01/205U/5444.00/22
Tab. 26: Approval information
Safety characteristics Function mode
1 2 3 4 5 6 7 8 9 10
TWCDT
Worst Case Delay Time
(Max. internal reaction time
to input signal)
[ms] 15 15 60 120 15 60 120 580 15 15
DCAVG
Average Diagnostic Coverage
(average diagnostic cov-
erage)
[%] 801) 99
SFF
Safe Failure Fraction
(safe failure fraction)
[%] 842) 99
Minimum period of request > Internal reaction time
PROFIsafe Watchdog time [ms] F_WD_TIME
Max. reaction time to input
change
[ms] F_WD_TIME + TWCDT
TDAT
Device Acknowledge Time
(Internal PROFIsafe pro-
cessing time)
[ms] < 20
MTTFd
Mean Time To dangerous
Failure
(Mean time to dangerous
failure)
[years
]
> 2500
PFHD
Probability of dangerous
Failure per Hour
(probability of dangerous
failure per hour)
[1/h] 1.0 x 10–9
HFT
Hardware Fault Tolerance
(Hardware fault tolerance)
1
Classification in accordance
with EN 61508-2:2010-05
Type B
ß
Beta factor for failures
resulting from common cause
CCF (Common Cause Failure)
[%] 2
Max. useful life [years
]
20
Safety protocol Profile for Safety Technology on PROFIBUS DP and PRO-
FINET IO; Version 2.4, March 2007
Safety classification CPX-F8DE-P
in accordance with
EN ISO 13849-1
PL d,
Cat. 23)
to PL e, Cat. 4
in accordance with EN 61508 SIL 2)bis SIL 3
in accordance with EN 62061 SIL CL 2)to SIL CL 3
1) Characteristic value if the application is tested within 24 hours: DCAVG = 94%
2) Characteristic value if the application is tested within 24 hours: SFF = 95%
3) Characteristic value if the application is tested within 24 h: to PL e Cat. 3, SIL 3, SIL CL 3
Tab. 27: Safety characteristics
Recommended sensors Function mode
1 2 3 4 5 6 7 8 9 10
Sensors with mechanical switch contacts – – ²®–® ® ® ® ®
Sensors with self-monitored electronic out-
puts
² ² ––®–––® ®
Electronic three-wire sensors with a ready-
state delay of < 23 ms
or
Electronic two-wire sensors with a ready-
state delay of < 2 ms
– – ²––²–²– –
Additionally:
–with reverse polarity protection at the
positive supply connection
or
–without free-wheeling diode at the
sensor output
– – – ®– – – – – –
® Recommended function mode
² Can be used with low safety requirement
Tab. 28: Recommended sensors
Electrical characteristic values
Nominal operating voltage DC [V DC] 24
Residual ripple (tip to tip) in operating voltage
range UEL/SEN
[VSS] 2
Permitted voltage tolerance
–In metal interlinking blocks (CPX-M-GE-...) [%] –15 … +20
Voltage drop bypass time for the internal elec-
tronics
[ms] 10
Intrinsic current consumption at nominal operating
voltage
[mA] typ. 35
Undervoltage monitoring UEL/SEN [V] U < 19.5 for t > 250 ms
Overvoltage monitoring UEL/SEN [V] U < 29.5 for t > 250 ms
Potential reference of the input channels UEL/SEN
Electrical isolation between the channels no
Input characteristics in accordance with
IEC 61131-2 for digital inputs
Type 2
Max. accepted test pulse duration at the input [ms] 0.7
Max. load current per clock line T0, T2, T4, T6 [A] 0.7
Max. resultant current at T1, T3, T5, T7 [A] 0.2
Max. output current at 24 V terminals [A] 2
Max. residual current per input module [A] 3
Cable lengths to sensor
Cable type LiFY11Y-OB, unshielded, 3 x 0.14 mm2[m] < 200
Cable type LiF9Y11Y, unshielded, 4 x 0.10 mm2[m] < 200
Cable type LiYCY, shielded, 4 x 0.14 mm2[m] < 200
Tab. 29: Electrical characteristic values
Module characteristic
values
Function mode
012345678910
Module code 28d (1Ch)
Sub-module code 1d (01h)
No. of inputs 8
Switching logic at inputs PNP (positive switching)
Compatible with fast start-up
(FSU)
Yes
Time for switch-on phase
until input module ready
(start up)
[s] < 2
Max. tolerance time until
diagnostic message of
channel fault
[s] – – – 0.5 10 0.5 0.5 10 2 2 2
Tab. 30: Module characteristic values
Ambient characteristics
Ambient operating temperature [°C] –5 … +50
Ambient temperature during storage and
transportation
[°C] –20 … +70
Relative humidity
(non-condensing)
[%] 5 … 90
Contamination level in accordance with
DIN EN 60664-1:2007
£ 2
Degree of protection in accordance with
IEC 60529
Dependent on the connection block1)
UL certification c UL us - Recognised (OL)
1) è Description CPX-F8DE-P-..., "Technical data of the manifold blocks"
Tab. 31: Ambient characteristics
No
.
Error messages Function mode
012345678910
02 Channel error short circuit 24 V – – – üü–üüü– –
02 Module error short circuit 0 V
clock output T1357
üüüüüüüüüüü
03 Channel error wire break – – – – ü––ü– – –
05 Module error undervoltage üüüüüüüüüüü
29 Channel error configuration
e.g. invalid function mode
–––––––––––
55 Channel error process value – – – – – üü–ü ü ü
61 Module error overvoltage üüüüüüüüüüü
65 Module error F_DEST_ADD dif-
ferent
üüüüüüüüüüü
66 Module error communication üüüüüüüüüüü
67 Module error communication
timeout
üüüüüüüüüüü
68 Channel error cross circuit – – – üü–üüü– –
69 Module fault, parameters üüüüüüüüüüü
75 Module error excessive temper-
ature
üüüüüüüüüüü
80 Channel error channel function üüüüüüüüüüü
145 Module error in self test üüüüüüüüüüü
Tab. 32: Error messages

Other manuals for CPX-F8DE-P

4

Other Festo I/O System manuals

Festo 03-FB-8 Series User manual

Festo

Festo 03-FB-8 Series User manual

Festo CPX-AP-I-4AI-U-I-RTD-M12 Parts list manual

Festo

Festo CPX-AP-I-4AI-U-I-RTD-M12 Parts list manual

Festo CPX-FB33 Reference guide

Festo

Festo CPX-FB33 Reference guide

Festo CPX-AP-I-4DI-M8-3P User manual

Festo

Festo CPX-AP-I-4DI-M8-3P User manual

Festo CPX Series Operating and installation instructions

Festo

Festo CPX Series Operating and installation instructions

Festo CPX-AP-I-8DI-M8-3P User manual

Festo

Festo CPX-AP-I-8DI-M8-3P User manual

Festo CPX-E AI-U-I Series User manual

Festo

Festo CPX-E AI-U-I Series User manual

Festo CPX-AP-I-4DI4DO-M8-3P Parts list manual

Festo

Festo CPX-AP-I-4DI4DO-M8-3P Parts list manual

Festo CPX Series User manual

Festo

Festo CPX Series User manual

Festo CP-E16...M Series User manual

Festo

Festo CP-E16...M Series User manual

Festo CPX-E AI-U-I Series Parts list manual

Festo

Festo CPX-E AI-U-I Series Parts list manual

Festo CPX-...DE Series User manual

Festo

Festo CPX-...DE Series User manual

Festo SPC200-DIO User manual

Festo

Festo SPC200-DIO User manual

Festo CPX-E-4IOL User manual

Festo

Festo CPX-E-4IOL User manual

Festo SPC200-2AI-U Parts list manual

Festo

Festo SPC200-2AI-U Parts list manual

Festo CPX Series User manual

Festo

Festo CPX Series User manual

Festo CP-FB13-E Parts list manual

Festo

Festo CP-FB13-E Parts list manual

Festo CPX-E DO Series User manual

Festo

Festo CPX-E DO Series User manual

Festo CP-FB11-E Parts list manual

Festo

Festo CP-FB11-E Parts list manual

Festo CPX-E- DI Series User manual

Festo

Festo CPX-E- DI Series User manual

Festo CPX-2ZE2DA User manual

Festo

Festo CPX-2ZE2DA User manual

Festo CPX-F8DE-P Parts list manual

Festo

Festo CPX-F8DE-P Parts list manual

Festo VIGE-03-FB Series Operating and installation instructions

Festo

Festo VIGE-03-FB Series Operating and installation instructions

Festo CPX-4AE-4AA-H User manual

Festo

Festo CPX-4AE-4AA-H User manual

Popular I/O System manuals by other brands

SIGMA TEK SR 012 Technical manual

SIGMA TEK

SIGMA TEK SR 012 Technical manual

Murrelektronik xtreme DB DP-34005-12 user guide

Murrelektronik

Murrelektronik xtreme DB DP-34005-12 user guide

Black Box IC901C manual

Black Box

Black Box IC901C manual

Data Video DAC-90 quick start guide

Data Video

Data Video DAC-90 quick start guide

Delta DVP06XA-H2 instruction sheet

Delta

Delta DVP06XA-H2 instruction sheet

Contec DIO-1616L-PE user guide

Contec

Contec DIO-1616L-PE user guide

Murrelektronik MVP12 Series manual

Murrelektronik

Murrelektronik MVP12 Series manual

MOTU 24i user guide

MOTU

MOTU 24i user guide

Beck INDUSTRY 100.DIO8.UMTS Startup guide

Beck

Beck INDUSTRY 100.DIO8.UMTS Startup guide

PXM PX227-L0 user manual

PXM

PXM PX227-L0 user manual

Allen-Bradley ControlLogix 1756-IF6CIS installation instructions

Allen-Bradley

Allen-Bradley ControlLogix 1756-IF6CIS installation instructions

BERGHOF B-EasyConnect user manual

BERGHOF

BERGHOF B-EasyConnect user manual

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

JS Automation Corp DIO-3232 user manual

JS Automation Corp

JS Automation Corp DIO-3232 user manual

Moeller EU5C-SWD-PF1-1 Hardware and engineering

Moeller

Moeller EU5C-SWD-PF1-1 Hardware and engineering

IDT DAC1627D Quick start guides

IDT

IDT DAC1627D Quick start guides

NI FD-11605 CALIBRATION PROCEDURE

NI

NI FD-11605 CALIBRATION PROCEDURE

Siemens SIMATIC S7 EIP-200S System manual

Siemens

Siemens SIMATIC S7 EIP-200S System manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.