North Slope Chillers NSC0250-FROST User manual

Model: NSC0250-FROST Owners Manual 1 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Cautions/Warnings
1. Power (ALWAYS check the Chiller Parameter tag and verify operational voltage before plugging in chiller)
a. Only connect North Slope Chillers to a properly grounded circuit
b. Never connect your North Slope Chiller to voltage that is outside the acceptable voltage range.
Connecting your chiller to any voltage outside of these ranges will damage the compressor.
i. 110V model will operate on voltages between 100 ~ 130V
ii. 230V model will operate on voltages between 200 ~ 250V
c. Only use power sources that are 60Hz, running the chiller at 50Hz will void the warranty and will
damage the compressor
2. Never run the pump dry, only turn on chiller after the fluid reservoir has been filled. Running the chiller without
fluid will permanently damage the pump and void the warranty
3. This chiller is air cooled and must have good ventilation. For proper function there must be a minimum of 1 foot
clearance on both sides and 2 foot clearance at the back of the chiller

Model: NSC0250-FROST Owners Manual 2 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Specification sheet
NSC0250-FROST
Voltage
Single Phase, 60hz, 110VAC
Current
4.5 –6.5 Amps
Compressor Power
.93HP (.68kW)
Refrigeration Capacity
3000 BTU/hr (878 kW) @90F ambient and 45F fluid
Refrigerant
R-410a
Refrigerant Charge
.77 lbs
Precision
±0.5°F (0.3°C)
Metering Device
Capillary
Protection
Overcurrent protection for compressor, flow alarm
and over temperature alarm
Pump Power
0.04HP (0.03kW)
Tank Capacity
2 Gallons (8 Liters)
Inlet and Outlet
¾” Nylon barbed fitting
Maximum Lift
40 feet (12 meters)
Maximum flow
3.5 GPM (13 L/min)
Dry Weight
64lbs (29kg)
Dimensions
21.8” x 11.125” x 21.5” (L x W x H)
Chiller Performance

Model: NSC0250-FROST Owners Manual 3 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Chiller overview
FRONT
BACK

Model: NSC0250-FROST Owners Manual 4 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Installation
1. Open package to check for damage and to verify that all components are there
2. Fill the reservoir
3. Connect inlet and outlet hoses
4. Plug in Power and turn on power switch
5. Verify water level in tank
6. Adjust temperature controller

Model: NSC0250-FROST Owners Manual 5 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Temperature control settings
Temperature Control Panel
LED Indicator Lights
D1
ON: System is running in intelligent control mode
OFF: System is running in temperature control mode
FLASHING: Controller is in parameter setting mode or displaying room temperature
D2
ON: Indicates that the compressor is running and the chiller is actively chilling fluid
OFF: Compressor is off (maintaining temperature)
FLASHING: Chiller is in energy-saving state
Alarm codes
Error Code
Problem
E1
High ambient (room) temperature
E2
High water temperature
E3
Low water temperature
E4
Ambient (room) temperature sensor failure
E5
Water temperature sensor failure
When alarm occurs the alarm code and fluid temperature will alternate on the display
The alarm sound can be suppressed by pressing any button, but the code will remain until the alarm condition is fixed.
Check ambient temperature
1. Press button to display ambient temperature
2. D1 indicator light will flash while ambient temperature is being displayed. The display will return to normal after
6 seconds.
Adjust temperature (Constant Temperature Mode)
Constant temperature mode is the default control mode. When this mode is selected
1. Press to display the current target temperature setting
2. Press or to adjust the target temperature setting
3. Press to save and exit parameters and return to temperature display. If no buttons are pressed for 20
seconds the controller will automatically return to the temperature display without saving changes.
Adjust temperature (Intelligent Temperature Mode)
1. Press to display the current target temperature setting
2. Press or to adjust the target temperature setting
3. Press to save and exit parameters and return to temperature display. If no buttons are pressed for 20
seconds the controller will automatically return to the temperature display without saving changes.

Model: NSC0250-FROST Owners Manual 6 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
Advanced settings adjustment
1. Press and hold button then press and hold for 5 seconds until “0”is displayed
2. Press button to switch from 0 to 8 (default password)
3. Press to press enter after setting the correct password. F0 will be displayed.
4. Press or to select the parameter to be changed
5. Press when a parameter is selected to see the current value and make changes
6. Press or to change the parameter to the desired value
7. Press to save and exit parameters. If no button is pressed for 20 seconds the screen will return to the default
screen and exit without saving parameter changes.
Parameter List
Parameter
Description
Range
Factory
Default
Notes
Constant Temperature Mode
Intelligent Mode
F0
Temperature Setting
F8 –F9
45°F
Constant Temperature
F1
Temperature Difference
setting
-27 - +9
-3.6°F
Intelligent Mode (ambient tracking)
F2
Cooling differential
0.2 –5.4
0.5
F3
Control Method
0 –1
0
Constant Temperature (0) or
Intelligent Mode (1)
F4
High water temperature
alarm
2°F - 36°F
18°F
F5
Low water temperature
alarm
2°F - 36°F
27°F
F6
High ambient (room)
temperature alarm
104°F - 122°F
113°F
F7
Password
0 –99
8
F8
Max target temp limit
F0 - 104°F
86°F
F9
Min target temp limit
33.8°F - F0
40°F
WARNING: Do not run chiller
lower than 40°F. This will damage
the chiller and void your warranty.
Flow Alarm
Condition
Normal Flow Indicator
Flow Alarm Indicator
Buzzer
Circulating Pump works properly
Blockage in cooling water circulation line
Low water level
Circulation pump failure

Model: NSC0250-FROST Owners Manual 7 |P a g e
www.northslopechillers.com | (866) 826-2993 | 3130 S 1030 W, Suite 1 | Salt Lake City, UT 84119
STANDARD PRODUCT WARRANTY
1. LIMITED WARRANTY POLICY
Manufacturer warrants Ready to Ship products sold as “new” to be free from defects in material and workmanship
under normal and proper use and servicing for a period of the shorter of one (1) year from the date of purchase by a
retail customer. MANUFACTURER MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND, EXPRESSED OR
IMPLIED, IN FACT OR IN LAW, INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE OR USE OTHER THAN THE LIMITED WARRANTY SET FORTH ABOVE.
2. EXPRESS DISCLAIMER
Manufacturer MAKES NO WARRANTIES OR REPRESENTATIONS AS TO THE Products, EXCEPT AS SET FORTH ABOVE. ALL
IMPLIED WARRANTIES AND CONDITIONS, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF
MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT, ARE HEREBY DISCLAIMED.
3. WARRANTY EXCLUSIONS
Exclusions from warranty consideration include, but are not limited to: normal wear and tear; abuse, misuse, or non-
standard application; act of nature; lack of proper maintenance; unauthorized repair; unauthorized product
modification. The user of the Manufacturer’s Products is expected to follow all operating instructions and make periodic
checks and inspections to ensure the physical condition and performance of the Product(s). Neither Manufacturer, nor
its representatives, assumes any responsibility for results of the use of the Products beyond the operation and
performance of the Products themselves. Only the Manufacturer is authorized to make any warranty or representation
and the customer may not rely on any other warranty or representation. All implied warranties are hereby disclaimed.
4. RETURNS
a. When any of Manufacturer’s Products have been authorized to return for any inspection, or replacement, it must be
returned as specified in the Return Merchandise Authorization Form.
b. A Manufacturer-issued Returned Material Authorization (RMA) number authorizing a product return must be
acquired prior to sending any return. In addition, documentation of model, product serial number, dealer invoice
number, dated proof of resale, and description of failure shall accompany all returns.
c. All returns must come freight prepaid and in its original container, or in a manner conducive to proper shipping and
handling procedures. Product(s) replaced, or shipped in accordance with manufacturers’ warranty policy for doing so
will be returned freight prepaid.
d. Manufacturer reserves the right to postpone, delay, or refuse warranty claim consideration for either unauthorized
returns or returns made by dealers or distributors whose open and active accounts are past due or delinquent. The
dealer or distributor agrees that no warranties or other guarantees on any products shall be made in excess of those
made by Manufacturer. This agreement excludes Manufacturer or its representatives from all liability not covered in this
Warranty.
5. REFUSAL OF WARRANTY CLAIM
Manufacturer reserves the right to postpone, delay, or refuse warranty claim consideration for either unauthorized
returns or returns made by a Distributor whose open and active accounts are past due or delinquent with respect this
Agreement.
Table of contents
Popular Chiller manuals by other brands

Elkay
Elkay HRC2-1C installation instructions

Morgan
Morgan MCS-339 user manual

Trane
Trane AquaStream 2 CGWN Series Installation operation & maintenance

CLIVET
CLIVET WSAN-YES 18.2 Manual for installation, use and maintenance

Daikin
Daikin EWLD120MBYNN Operation manual

Envicool
Envicool EMW90HDNC1A user manual

Carrier
Carrier 30PA 90 Installation, operation and maintenance instructions

Trane
Trane CGWF Installation operation & maintenance

Zanussi
Zanussi 110723 Specifications

MTA
MTA OCT 018 manual

Daikin
Daikin WSC Installation, operation and maintenance manual

Mitsubishi Electric
Mitsubishi Electric CLIMAVENETA NECS-ME Series Technical bulletin