YORK INTERNATIONAL
14
STANDARD COMPRESSOR POWER SUPPLIES
(Each Compressor System Power Supply Individually Protected with Field Supplied Branch Circuit Protection)
NOTES for Electrical Data:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system
#1 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22.
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2.
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), (3) or (4)
preceeding the wire range indicates the number of termination points or lugs which are available per phase. The (1-2), (1-3) or (1-4)
preceeding the wire range indicates that a single multi-termination lug is available per phase that can accept from two (1-2) to four (1-4) wires
of the wire range specified (1) #1-600MCM OR (2) #1-250MCM indicates that a single lug is supplied and it will accept a single wire up to
600MCM or 2 wires up to 250MCM. Actual wired size and number of wires per phase must be determined based on ampacity and job
requirements using N.E.C. wire sizing information. The above recommendations are based onthe National Electrical Code and using copper
connectors only. FIeld wiring must also comply with local codes.
8. A ground lug is provided from each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6-350MCM.
9. The supplied disconnect is a Disconnecting Means as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
LEGEND
ACR-LINE ACROSS THE LINE
CB CIRCUIT BREAKER
DE FU DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKER
FACT MOUNT FUSE FACTORY MOUNTED FUSES
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON-FUSED
RLA RUNNING LOAD AMPS VOLTAGE CODE
S.P. WIRE SINGLE POINT WIRING 17 = 200-3-60
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON FUSED DISCONNECT SWITCH) 28 = 230-3-60
WYE-DELTA WYE-DELTA START 40 = 380-3-60
XLRA ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS 46 = 460-3-60
YLRA WYE-DELTA INRUSH LOCKED ROTOR AMPS 58 = 575-3-60
ELECTRICAL DATA
SYSTEM #1 & #3 (EACH) FIELD SUPPLIED WIRING
MODEL VOLTS MCA1MIN NF D.E. FU C.B. WIRE RANGE7(LUGS) COMPRESSOR FANS
DISC SW2MIN.3MAX.4MIN.5MAX.6WYE-DELTA ACR-LINE RLA Y LRA X LRA FLA (EA)
380 334 400 400 500 400 500 (2) #6 - 250 NA 250 401 N/A 5.2
YCAS310 460 268 400 350 450 350 400 (2) #6 - 250 1/0 - 500 198 331 1051 5.0
575 218 400 300 350 300 350 (2) #6 - 250 #6 - 250 158 145 463 4.9
380 415 400 500 700 500 700 (2) 1/0 - 500 NA 315 483 NA 5.2
YCAS340 460 333 400 400 500 400 500 (2) #6 - 250 1/0 - 500 250 398 1261 5.0
575 269 400 350 450 350 400 (2) #6 - 250 1/0 - 500 199 311 987 4.9
380 415 400 500 700 500 700 (2) 1/0 - 500 NA 315 483 NA 5.2
YCAS360 460 333 400 400 500 400 500 (2) #6 - 250 1/0 - 500 250 398 1261 5.0
575 269 400 350 450 350 400 (2) #6 - 250 1/0 - 500 199 311 987 4.9
380 439 600 600 700 600 700 (2) 1/0 - 500 NA 334 483 NA 5.2
YCAS380 460 352 400 450 600 450 500 (2) #6 - 250 1/0 - 500 265 398 1261 5.0
575 284 400 350 450 350 450 (2) #6 - 250 1/0 - 500 311 311 987 4.9
CONTROL POWER SUPPLY
UNIT CONTROL MIN MAX DUAL NON-FUSED
VOLTAGE POWER CIRCUIT ELEMENT DISC. SW.
SUPPLY AMPACITY FUSE SIZE SIZE
STD.
MODELS W/O 115-1-60 20A 20A 30A
TRANSFORMERS