Introduction ...............................................................................1
Features....................................................................................2
ULApprovalsandAgencyListings ............................................2
CompatibleULListedReceivers ...............................................2
Partitioning ................................................................................3
N-750DialUpInstallationWithOn-BoardCommunicator..........4
N-750DialUpInstallation ..........................................................6
N-750DirectConnectInstallation ..............................................8
N-750 Compatible Reader and Card Formats.........................10
DeviceWorksheet ...................................................................11
Worksheetfor Auxiliary Devices..............................................12
Glossary of Terms and Definitions...........................................13

Version1.0 October1997
N-750Configuration Guide

N-750 Configuration Guide
1
Version 1.0 October1997
Introduction
This guide is designed to help understand the N-750 panel and the
process of assembling a complete system.
The N-750 is a control/communicator for use in commercial
security and fire applications, with a built-in communicator for
reporting to most central stations. The N-750 includes a
sophisticated access control system, through which you can
monitor and control user access to specified areas of a building.
The benefit of the N-750 is that three separate systems are no
longer needed, everything is included in one panel.
The N-750 is ideal for colleges and universities, hospitals, shop-
ping malls, warehouses, office towers, business campuses, senior
housing, storage facilities, banks, airports, or wherever there is risk
involved.

2
Version 1.0 October1997
N-750 Configuration Guide
BURGLAR
Base number of zones 16
Maximum number of zones (expanded) 400
Total partitions* 64
Zone Characteristics/Options 19
Number of users 1800
Event Buffer 1000
User Profiles 100
* Each N-750 has 8 areas that can be divided into 8
sections for a total of 64 partitions. (See page 3 for more
information on partitions.)
ACCESSCONTROL
Number of doors 24
Number of touchpads 24 Supervised
Number of readers 24
Number of users 1800
ELECTRICAL
Accessory Power Supply (Source) 2.5 A
Optional Power Supply (Source) 2.5 A
Bell Power 1 A
Siren Driver Yes
Electronic Overcurrent Protection Yes
GENERAL
Programming Touchpad/Software
Software Programmable Yes
Memory EEPROM
Answering Machine Bypass Yes
Optional Printer Interface Up to 8
DIGITALCOMMUNICATOR
Supported Formats 2
SIA Format Yes
Contact ID Yes
UL294 Access Control Yes
UL Grade A Yes
UL 365 Police Connect Yes
UL 609 Local Burglary Yes
UL 611 C.S. Burglary Yes
UL 636 Holdup Alarm Units Yes
UL 681 Bank Burg Systems Yes
UL 864 Comm. Fire C.S. (DACT) Yes
NFPA 72 (Chapter 4) Yes
UL 985 Household Burglary Yes
UL 1023 Household Burglary Yes
UL 1076 Proprietary Burglary Yes
UL 1610 C.S. Burglary Yes
UL 1635 Digital Burglary Sys. Yes
UL 1641 Instal. Res. Burglary Yes
ULC Res./Comm. Burglary Yes
FCC Part 15 Yes
FCC Part 68 Yes
DOC CS-03 Yes
CSFM Res./Comm/ Fire Yes
CE Approved Yes
Features
UL Approvals and Agency Listings
Compatible UL Listed Receivers
MANUFACTURER RECEIVERMODEL FORMATS
Silent Knight Model 9000 SIA-1 (20 events per call)
Ademco Model 685 Contact ID
Sur-Guard SG-MLR2-DG SIA-1, Contact ID
Osborne Hoffman Quickalert SIA-1, Contact ID
This system is rated for central fire station fire reporting only. It is not rated for life safety.

N-750 Configuration Guide
3
Version 1.0 October1997
Partitioning
N-750
Area 1
Area 2
Area 3
Partition #3
single area Partition #6
single area
Area 1 Area 2
Area 3 Area 4
Partition #4
single area
Area 1
Area 2
Area 3
Area 4
Area 5
Area 6
Area 7
Area 8
Partition #1
single area
Partition #8
single area
Dotted lines show partition borders
A SINGLE N-750 CAN CONTROL UP TO 8 PARTITIONS
Each partition operates as an independent system that can be further subdivided into
eight areas. Partitions report as separate accounts to the central station (areas do not).
SAMPLE APPLICATION: FOUR-STORE STRIP MALL
Area 3
Partition 1
Drugstore Partition 2
Bookstore Partition 3
Take-out Partition 4
Discount
Area 1
Storage
Area 1
Pharmacy
Area 4
Customer Area
Area 3
Cashier
Area 2
Customer Area
Area 3
Cashier
Area 5 Storage
N-750 Panel
Area 1
Safe
Area 2
Kitchen
Area 3
Customer Area
Area 1
Storage
Area 4
Checkout
Area 2
Customer Area
N-750 Panel
Area 2
Post
Office

4
Version 1.0 October1997
N-750 Configuration Guide
N-750 DIAL UPN-750 DIAL UP
N-750 DIAL UPN-750 DIAL UP
N-750 DIAL UP
INSTINST
INSTINST
INSTALLAALLA
ALLAALLA
ALLATIONTION
TIONTION
TION
With On-BoardWith On-Board
With On-BoardWith On-Board
With On-Board
CommunicatorCommunicator
CommunicatorCommunicator
Communicator
Computer and Software
PC-AC-750
Stand alone PC for N-750 software includes:
CPU, keyboard, mouse, SVGA monitor, parallel printer,
and printer cable.
AND/OR
N-750-SK
Upload/download programming software for the N-750.
Only one copy is required per dealer. The N-750-SK can
support an unlimited number of accounts.
N-750
1 N-750 Security/Access Control Panel
1 N-750-COMM-CBL RJ31X Cable for Digital
Communicator
1 BAT-N-750 12 V, 7 A Battery Backup
1 M-9600 Hi-SpeedCommunications
ExternalModem
1 CBL-2 M-9600 Serial Interface Cable
ACAS Software/Printer Connection
1-8 N-750-PI CommunicationsInterface
1 CBL-N-750-PI Direct Connect Cable–10'
1 N-750-ACAS End-userProgramming Software
1-8 P-1000 Parallel Event/Report Printer
1-8 CBL-1 Parallel Printer Cable
Touchpads/ADMs
1-24*N-750-PAIT Programming & Access Touchpad
1-23*N-750-ADM Access Door Module
*Not to exceed a combined total of 24 PAITs & ADMs
See page 10 for supported reader and card types
Zone Expanders
1-3 N-750 SSE Smart Sensor Serial Zone
Expander
1-40 N-750-SS-10 Smart Sensor 10 Pack
with Resistor
1-40 N-750-EOL-UL-SS 10 pack EOL UL Resistor 1.43 k
for Smart Sensor Expander
1-6 N-750-ZONE Hardwire Zone Expander
1-40 N-750-EOL-UL 10 pack EOL UL Resistor 4.7 k
for hardwire Zone Expander
Not to exceed a combined total of 384 zones
Consult product guide for additional devices
Optional Accessories
N-750-APS 12 VDC Auxiliary Power Supply for
N-750
N-750-APS-24 24 VDC Auxiliary Power Supply for
N-750
N-750-BELL Bell Supervision for N-750
N-750-
BELL-SUP
Bell Suppressor for N-750-BELL
N-750-DPLM Dual Phone Line Module for UL
Communications
N-750-ENC Accessory Enclosure for the N-750
N-750-GSM Ground Start Module for N-750
N-750-KOHP Knock Out Hole Plug for N-750
(UL 6 Pack)
N-750-TC UL Tamper Proof Box for X-750
Transformer
(See pages 13-15 for complete descriptions)
The N-750-PAIT
N-750-PAIT
N-750-ADM
N-750-ADM
N-750-PAIT
You must have at least one
N-750-PAIT per system.
is a
programmable touchpad that
can be used to arm/disarm the
system, or perform a number
of programming functions.
Up to 24 s per
N-750
1 SPDT Relay
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
s, not to exceed
a total combination of 24
s and
s.
N-750-PAIT
Reader
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
26, 32 and 34 bit
Wiegand Reader
N-750-SSE
Programmable
Touchpad
CBL-1
P-1000
CBL-2
M-9600
PC-AC-750 PC running
N-750-SK Upload/Download
Software for the N-750
N-750-PAIT
The N-750-SSE N-750-SSE
N-750-SS
N-750-SSE SSE
N-750-SS
N-750-SS
N-750-EOL-US-SS
N-750-ZONE
is a Serial Zone Expander
for the N-750. The supports 2
serial lines with a total of 64 points per line
and 128 points per unit. The serial lines may
be run up to 5000' with an Smart
Sensor dropped no more than 200' from the
device to which it is connected.
128 Zones per , 3 N-750 s
per N-750 for a total of 384 zones
Used in conjunction with the
Smart Sensor
Serial Line can go up to 5000' total
distance
Supervised through , for UL
applications use the
10 pack
Can be used in conjunction with
, not to exceed a combina-
tion of 384 hardwired and serial zones
N-750-SS
1.43k EOL Resistor
N-750-EOL-UL-SS
Fire Sprinkler
Glass Break Sensor
A
B
(See p. 10 for available readers)
N-750-SSE
S-4 Suppressor

N-750 Configuration Guide
5
Version 1.0 October1997
Brown
Gray
Green
Red
Premises TIP
Premises Ring
Telco Tip
Telco Ring
N-750-ACAS & N-750-PI
The N-750-ZONE Expander
N-750-ZONE
N-750-UL-EOL
N-750-SSE
creates additional hardwired
zones for the N-750.
6 s per N-750
384 total hardwired zones
Connects to either SBUS
All zones are supervised with
the addition of the
10 pack UL
approved end of line resistor
Used in conjunction with
, not to exceed a
total combination of 384
hardwired and serial zones
N-750-ZONE
Door Access Module
The N-750-ADM
N-750-ADM
N-750-PAIT
N-750-ADM
N-750-PAIT
is a card
reader expansion device which
supports 26, 32 and 34 bit
Wiegand format cards.
Up to 23 s per N-
750
2 SPDT Relays
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
, not to exceed a
total combination of 24
s and
Reader
26, 32 and 34 bit
Wiegand Reader
(See p.10 for available readers)
N-750-ADM
N-750-ZONE
Adds 64 Hardwired Zones
N-750
NR2221-BR 1000'
2 Conductor 22 AWG Cable for N-750-SSE
or
NCP2221-BR 1000'
2 Conductor 22 AWG Plenum Cable for N-750-SSE
N-750-ADM
NC204-PR 1000'
RS-485 4 Conductor 20 AWG Non-Shielded Cable
or
NCP204-PR 1000'
RS-485 4 Conductor 20 AWG Plenum Non-Shielded Cable
N-750-COMM-CBL
The N-750-PI
N-750-PI
N-750-ACAS
CBL-N-750-PI
M-9600 CBL-2
N-750-ACAS
N-750-ACAS
N-750-PI
RS-232
is a Parallel/Serial interface which can be
used to connect the N-750 to a printer for report
generation and live transaction reporting. The
can be used for communications to the
software via direct connection with the
or via an modem & .
is optional Windows-based software
that allows the end user to program the system via a
PC-AC-750 Computer System.
allows for name entering in the
software, custom reports, time window entry, area
scheduling, card entry and live event reporting.
Up to 8 s per N-750 system.
Serial and Parallel Interface
9 Pin Connection
Can be used with partitions for separate reporting
per partition.
PRINTER
P-1000
PC-AC-750 PC for
direct connection
to ACAS Software
N-750-PI
CBL-1
Connect
to RJ31X Digital
Communicator
Max. 300 baud
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
S-4 Suppressor

6
Version 1.0 October1997
N-750 Configuration Guide
N-750 DIAL UPN-750 DIAL UP
N-750 DIAL UPN-750 DIAL UP
N-750 DIAL UP
INSTINST
INSTINST
INSTALLAALLA
ALLAALLA
ALLATIONTION
TIONTION
TION
Computer and Software
PC-AC-750
Stand alone PC for N-750 software includes:
CPU, keyboard, mouse, SVGA monitor, parallel printer,
and printer cable.
AND/OR
N-750-SK
Upload/download programming software for the N-750.
Only one copy is required per dealer. The N-750-SK can
support an unlimited number of accounts.
N-750
1 N-750 Security/Access Control Panel
1 BAT-N-750 12 V, 7 A battery backup
2 M-9600 Hi-SpeedCommunications
ExternalModem
2 CBL-2 M-9600 Serial Interface Cable
ACAS Software/Printer Connection
1-8 N-750-PI CommunicationsInterface
1 CBL-N-750-PI Direct Connect Cable–10'
1 N-750-ACAS End-userProgramming Software
1-8 P-1000 Parallel Event/Report Printer
1-8 CBL-1 Parallel Printer Cable
Touchpads/ADMs
1-24*N-750-PAIT Programming & Access Touchpad
1-23*N-750-ADM Access Door Module
*Not to exceed a combined total of 24 PAITs & ADMs
See page 10 for supported reader and card types
Zone Expanders
1-3 N-750 SSE Smart Sensor Serial Zone
Expander
1-40 N-750-SS-10 Smart Sensor 10 Pack
with Resistor
1-40 N-750-EOL-UL-SS 10 pack EOL UL Resistor 1.43 k
for Smart Sensor Expander
1-6 N-750-ZONE Hardwire Zone Expander
1-40 N-750-EOL-UL 10 pack EOL UL Resistor 4.7 k
for hardwire Zone Expander
Not to exceed a combined total of 384 zones
Consult product guide for additional devices
Optional Accessories
N-750-APS 12 VDC Auxiliary Power Supply for
N-750
N-750-APS-24 24 VDC Auxiliary Power Supply for
N-750
N-750-BELL Bell Supervision for N-750
N-750-
BELL-SUP
Bell Suppressor for N-750-BELL
N-750-COMM-CBL RJ31X Cable for Digital
Communicator
N-750-DPLM Dual Phone Line Module for UL
Communications
N-750-ENC Accessory Enclosure for the N-750
N-750-GSM Ground Start Module for N-750
N-750-KOHP Knock Out Hole Plug for N-750
(UL 6 Pack)
N-750-TC UL Tamper Proof Box for X-750
Transformer
(See pages 13-15 for complete descriptions)
CBL-1
P-1000
CBL-2
PC-AC-750 PC running
N-750-SK Upload/Download
Software for the N-750
Maximum
baud rate
19,200 bps.
The N-750-PAIT
N-750-PAIT
N-750-ADM
N-750-ADM
N-750-PAIT
You must have at least one
N-750-PAIT per system.
is a
programmable touchpad that
can be used to arm/disarm the
system, or perform a number
of programming functions.
Up to 24 s per
N-750
1 SPDT Relay
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
s, not to exceed
a total combination of 24
s and
s.
N-750-PAIT
Reader
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
26, 32 and 34 bit
Wiegand Reader
N-750-SSE
Programmable
Touchpad
N-750-PAIT
The N-750-SSE N-750-SSE
N-750-SS
N-750-SSE SSE
N-750-SS
N-750-SS
N-750-EOL-US-SS
N-750-ZONE
is a Serial Zone Expander
for the N-750. The supports 2
serial lines with a total of 64 points per line
and 128 points per unit. The serial lines may
be run up to 5000' with an Smart
Sensor dropped no more than 200' from the
device to which it is connected.
128 Zones per , 3 N-750 s
per N-750 for a total of 384 zones
Used in conjunction with the
Smart Sensor
Serial Line can go up to 5000' total
distance
Supervised through , for UL
applications use the
10 pack
Can be used in conjunction with
, not to exceed a combina-
tion of 384 hardwired and serial zones
N-750-SS
1.43k EOL Resistor
N-750-EOL-UL-SS
Fire Sprinkler
Glass Break Sensor
(See p. 10 for available readers)
N-750-SSE
S-4 Suppressor

N-750 Configuration Guide
7
Version 1.0 October1997
The N-750-ZONE Expander
N-750-ZONE
N-750-UL-EOL
N-750-SSE
creates additional hardwired
zones for the N-750.
6 s per N-750
384 total hardwired zones
Connects to either SBUS
All zones are supervised with
the addition of the
10 pack UL
approved end of line resistor
Used in conjunction with
, not to exceed a
total combination of 384
hardwired and serial zones
N-750-ZONE
Door Access Module
The N-750-ADM
N-750-ADM
N-750-PAIT
N-750-ADM N-750-
PAIT
is a card
reader expansion device which
supports 26, 32 and 34 bit
Wiegand format cards.
Up to 23 s per N-
750
2 SPDT Relays
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
, not to exceed a
total combination of 24
s and
s.
Reader
26, 32 and 34 bit
Wiegand Reader
(See p.10 for available readers)
N-750-ADM
N-750-ZONE
Adds 64 Hardwired Zones
N-750
N-750-PI
NR2221-BR 1000'
2 Conductor 22 AWG Cable for N-750-SSE
or
NCP2221-BR 1000'
2 Conductor 22 AWG Plenum Cable for N-750-SSE
N-750-ADM
NC204-PR 1000'
RS-485 4 Conductor 20 AWG Non-Shielded Cable
or
NCP204-PR 1000'
RS-485 4 Conductor 20 AWG Plenum Non-Shielded Cable
N-750-ACAS & N-750-PI
The N-750-PI
N-750-PI
N-750-ACAS
CBL-N-750-PI M-9600 CBL-2
N-750-ACAS
N-750-ACAS
N-750-PI
RS-232
is a Parallel/Serial interface which can
be used to connect the N-750 to a printer for report
generation and live transaction reporting. The
can be used for communications to the
software via direct connection with the
or via an modem & .
is optional Windows-based software
that allows the end user to program the system via
a PC-AC-750 Computer System.
allows for name entering in the
software, custom reports, time window entry, area
scheduling, card entry and live event reporting.
Up to 8 s per N-750 system.
Serial and Parallel Interface
9 Pin Connection
Can be used with partitions for separate reporting
per partition.
PRINTER
P-1000
PC-AC-750 PC for
direct connection
to ACAS Software
N-750-PI
CBL-1
M-9600
CBL-2
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
S-4 Suppressor

8
Version 1.0 October1997
N-750 Configuration Guide
N-750 Direct ConnectN-750 Direct Connect
N-750 Direct ConnectN-750 Direct Connect
N-750 Direct Connect
CBL-1
P-1000 CBL-N-750-PI
10 ft. cable
PC-AC-750 PC running
N-750-SK Upload/Download
Software for the N-750
Maximum baud
rate 19,200 bps.
The N-750-PAIT
N-750-PAIT
N-750-ADM
N-750-ADM
N-750-PAIT
You must have at least one
N-750-PAIT per system.
is a
programmable touchpad that
can be used to arm/disarm the
system, or perform a number
of programming functions.
Up to 24 s per
N-750
1 SPDT Relay
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
s, not to exceed
a total combination of 24
s and
s
N-750-PAIT
Reader
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
26, 32 and 34 bit
Wiegand Reader
N-750-SSE
Programmable
Touchpad
N-750-PAIT
The N-750-SSE
N-750-SSE
N-750-SS
N-750-SSE SSE
N-750-SS
N-750-SS
N-750-EOL-US-SS
N-750-ZONE
is a Serial Zone Expander for
the N-750. The supports 2 serial
lines with a total of 64 points per line and 128
points per unit. The serial lines may be run up
to 5000' with an Smart Sensor
dropped no more than 200' from the device to
which it is connected.
128 Zones per , 3 N-750 s
per N-750 for a total of 384 zones
Used in conjunction with the
Smart Sensor
Serial Line can go up to 5000' total distance
Supervised through , for UL
applications use the
10 pack
Can be used in conjunction with
, not to exceed a combination
of 384 hardwired and serial zones
N-750-SS
1.43k EOL Resistor
N-750-EOL-UL-SS
Fire Sprinkler
Glass Break Sensor
(See p. 10 for available readers)
N-750-SSE
S-4 Suppressor
Computer and Software
PC-AC-750
Stand alone PC for N-750 software includes:
CPU, keyboard, mouse, SVGA monitor, parallel printer,
and printer cable.
AND/OR
N-750-SK
Upload/download programming software for the N-750.
Only one copy is required per dealer. The N-750-SK can
support an unlimited number of accounts.
N-750
1 N-750 Security/Access Control Panel
1 BAT-N-750 12 V, 7 A Battery Backup
ACAS Software/Printer Connection
1-8 N-750-PI CommunicationsInterface
1 CBL-N-750-PI Direct Connect Cable–10'
1 N-750-ACAS End-userProgramming Software
1-8 P-1000 Parallel Event/Report Printer
1-8 CBL-1 Parallel Printer Cable
Touchpads/ADMs
1-24*N-750-PAIT Programming & Access Touchpad
1-23*N-750-ADM Access Door Module
*Not to exceed a combined total of 24 PAITs & ADMs
See page 10 for supported reader and card types
Zone Expanders
1-3 N-750 SSE Smart Sensor Serial Zone
Expander
1-40 N-750-SS-10 Smart Sensor 10 Pack
with Resistor
1-40 N-750-EOL-UL-SS 10 pack EOL UL Resistor 1.43 k
for Smart Sensor Expander
1-6 N-750-ZONE Hardwire Zone Expander
1-40 N-750-EOL-UL 10 pack EOL UL Resistor 4.7 k
for hardwire Zone Expander
Not to exceed a combined total of 384 zones
Consult product guide for additional devices
Optional Accessories
N-750-APS 12 VDC Auxiliary Power Supply for
N-750
N-750-APS-24 24 VDC Auxiliary Power Supply for
N-750
N-750-BELL Bell Supervision for N-750
N-750-
BELL-SUP
Bell Suppressor for N-750-BELL
N-750-COMM-CBL RJ31X Cable for Digital Communicator
N-750-DPLM Dual Phone Line Module for UL
Communications
N-750-ENC Accessory Enclosure for the N-750
N-750-GSM Ground Start Module for N-750
N-750-KOHP Knock Out Hole Plug for N-750
(UL 6 Pack)
N-750-TC UL Tamper Proof Box for X-750
Transformer
CBL-2 M-9600 Serial Interface Cable
M-9600 Hi-SpeedCommunications
ExternalModem
(See pages 13-15 for complete descriptions)

N-750 Configuration Guide
9
Version 1.0 October1997
The N-750-ZONE Expander
N-750-ZONE
N-750-UL-EOL
N-750-SSE
creates additional hardwired
zones for the N-750.
6 s per N-750
384 total hardwired zones
Connects to either SBUS
All zones are supervised with
the addition of the
10 pack UL
approved end of line resistor
Used in conjunction with
, not to exceed a
total combination of 384
hardwired and serial zones
N-750-ZONE
Door Access Module
The N-750-ADM
N-750-ADM
N-750-PAIT
N-750-ADM
N-750-PAIT
is a card
reader expansion device which
supports 26, 32 and 34 bit
Wiegand format cards
Up to 23 s per
N-750
2 SPDT Relays
2 Dry Contacts
+5VDC or +12VDC Output
Used in conjunction with
, not to exceed a
total combination of 24
s and
s.
Reader
26, 32 and 34 bit
Wiegand Reader
(See p.10 for available readers)
N-750-ADM
N-750-ZONE
Adds 64 Hardwired Zones
N-750
N-750-PI
NR2221-BR 1000'
2 Conductor 22 AWG Cable for N-750-SSE
or
NCP2221-BR 1000'
2 Conductor 22 AWG Plenum Cable for N-750-SSE
N-750-ADM
NC204-PR 1000'
RS-485 4 Conductor 20 AWG Non-Shielded Cable
or
NCP204-PR 1000'
RS-485 4 Conductor 20 AWG
N-750-ACAS & N-750-PI
The N-750-PI
N-750-PI
N-750-ACAS
CBL-N-750-PI M-9600 CBL-2
N-750-ACAS
N-750-ACAS
N-750-PI
RS-232
is a Parallel/Serial interface which can
be used to connect the N-750 to a printer for report
generation and live transaction reporting. The
can be used for communications to the
software via direct connection with the
or via an modem & .
is optional Windows-based software
that allows the end user to program the system via
a PC-AC-750 Computer System.
allows for name entering in the
software, custom reports, time window entry, area
scheduling, card entry and live event reporting.
Up to 8 s per N-750 system.
Serial and Parallel Interface
9 Pin Connection
Can be used with partitions for separate reporting
per partition.
PRINTER
P-1000
PC-AC-750 PC for
direct connection
to ACAS Software
N-750-PI
CBL-1
Exit Switch
Monitor Contact
/Door Zone
Door Strike
/Maglock
PWR
S-4 Suppressor

10
Version 1.0 October1997
N-750 Configuration Guide
N-750 Compatible Reader and Card Formats
The N-750 supports 26, 32 and 34 bit format Wiegand outputs. The following are com-
patible Northern Card Readers. Please consult the factory if a certain type is not men-
tioned.
Reader Card Bit Structure
CR-1 All Wiegand Cards except SC-2-A and NC-110000 26
NR-1-WR* NC-2, NPC-2 26, 32
BR-7** BC-2, BC-2-M (Code 39, 3 of 9, and 2 of 5) 26
PR-MINI-PROX PVC-H-1, PVC-H-2, PX-4-H, PX-DUO-H, 34
PX-DUOPROX, PX-PROXCARDII, PX-26-H, 26
PR-P-PRO PVC-H-1, PVC-H-2, PX-4-H, PX-DUO-H, 34
PX-DUOPROX, PX-PROXCARDII, PX-26-H, 26
PR-MAX-PRO PVC-H-1, PVC-H-2, PX-4-H, PX-DUO-H, 34
PX-DUOPROX, PX-PROXCARDII, PX-26-H, 26
PR-ASR-500 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-503 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-505 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-603 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-605 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-610 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-110 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-112 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-120 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-122 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
PR-ASR-136 PX-121-I, PVC-I-3, PVC-I-4, PX-115-I 26
KP-11 32
KP-11/26 26
KP-13 32
KP-13-26 26
* Does not support ABA
** 5 Digit Wiegand Barcode Only

N-750 Configuration Guide
11
Version 1.0 October1997
Device Worksheet
Current Draw Worksheet for N-750 Modules
DeviceDevice
DeviceDevice
Device NumberNumber
NumberNumber
Number CurrentCurrent
CurrentCurrent
Current TT
TT
Total Standbyotal Standby
otal Standbyotal Standby
otal Standby TT
TT
Total Alarmotal Alarm
otal Alarmotal Alarm
otal Alarm
of Devicesof Devices
of Devicesof Devices
of Devices per Deviceper Device
per Deviceper Device
per Device CurrentCurrent
CurrentCurrent
Current CurrentCurrent
CurrentCurrent
Current
Model N-750 Control\Communicator 1 Standby: 100 mA 100 mA
(1 max. ) Alarm: 120 mA 120 mA
N-750-ADM Door Module _______ Standby: 25 mA _______ mA
(23 max.*) Alarm: 40 mA _______ mA
N-750-PAIT Touchpad _______ Standby: 48 mA _______ mA
(24 max.*) Alarm: 90 mA _______ mA
N-750-SLTP Touchpad _______ Standby: 10 mA _______ mA
(used with the N-750-ADM) (24 max.) Alarm: 10 mA _______ mA
N-750-PI Printer Interface _______ Standby: 40 mA _______ mA
(8 max.) Alarm: 40 mA _______ mA
N-750-SSE Smart Sensor Expander _______ Standby: 80 mA _______ mA
(3 max.) Alarm: 80 mA _______ mA
N-750-ZONE 64 Point Zone Expander _______ Standby: 80 mA _______ mA
(6 max.) Alarm: 80 mA _______ mA
N-750-DPLM Dual Phone Line Monitor 1 Standby: 0 mA _______ mA
(1 max.) Alarm: 18 mA _______ mA
N-750-BELL Module 1 Standby: 5 mA _______ mA
(1 max.) Alarm: 60 mA _______ mA
Card Readers _______ Standby: mA _______ mA
(24 max.) Alarm: mA _______ mA
N-750-GSM Ground Start Relay 1 Standby: 0 mA _______ mA
(1 max.) Alarm: 18 mA _______ mA
A. Subtotal of current ratings for Northern Computers devices _______ mA _______ mA
Standby Alarm
*NOTE: The combined total of N-750-ADMs and N-750-PAITs is not to exceed 24 devices.
NOTE: The N-750-BELL shares its power with the auxiliary output. The auxiliary output is rated at 1A total current for all devices.

12
Version 1.0 October1997
N-750 Configuration Guide
Worksheet for Auxiliary Devices
Use this worksheet to record current draw for N-750-compatible devices which are not manufactured
by Northern Computers. These could include signalling devices, smoke detectors, etc.
DeviceDevice
DeviceDevice
Device NumberNumber
NumberNumber
Number CurrentCurrent
CurrentCurrent
Current TT
TT
Total Standbyotal Standby
otal Standbyotal Standby
otal Standby TT
TT
Total Alarmotal Alarm
otal Alarmotal Alarm
otal Alarm
of Devicesof Devices
of Devicesof Devices
of Devices per Deviceper Device
per Deviceper Device
per Device CurrentCurrent
CurrentCurrent
Current CurrentCurrent
CurrentCurrent
Current
SMOKE DETECTORS Refer to device manual for current ratings.
Standby: _______ mA _______mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
SIGNALING DEVICES Refer to device manual for alarm current ratings. Standby current is always 0 mA.
Alarm: _______ mA _______ mA
Alarm: _______ mA _______ mA
Alarm: _______ mA _______ mA
OTHER DEVICES Refer to device manual for current ratings.
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
Standby: _______ mA _______ mA
Alarm: _______ mA _______ mA
B. Subtotal of current ratings
for auxiliary devices listed above _______ mA _______ mA
Standby Alarm
A. Subtotal of current ratings for Northern Computers devices _______ mA _______ mA
Standby Alarm
C. Total current ratings of all devices in system devices _______ mA _______ mA
(Row A + Row B) Standby Alarm

N-750 Configuration Guide
13
Version 1.0 October1997
Glossary of Terms and Definitions
N-750: The N-750 is a control/communicator for
use in residential and commercial security appli-
cations, commercial and residential fire applica-
tions. The N-750 includes a sophisticated access
control system, through which you can monitor
and control user access to specific areas of a
building. Power: 18 VAC, 60 Hz, 50 VA, Temp: 32
to 120 F (0 to 49 C), Dimensions: 15"W x 20"H x
3"D, Weight 17lbs.
N-750-ACAS: The Access Control Administration
Software (N-750-ACAS) enables you to manage
the access control functions of the security
system. Used in conjunction with the N-750
security system, you can use ACAS to manage a
database of users and system events. Establishing
a communication function enables system opera-
tors to upload and store events from the control
panel, form both on and off site locations. This
information can then be used in generating
reports, which can be displayed and printed based
on event selection and sort criteria. N-750-ACAS
also enables management of user and site infor-
mation, such as access codes and security levels,
user profiles, and time schedules.
N-750-ADM: The N-750-ADM is a card reader
interface for the N-750. The N-750-ADM can be
used in conjunction with the N-750-PAIT for a
total combination of 24 devices. The N-750-ADM
has 2 SPDT relays for door lock and door held
open and 2 contact inputs for door egress and
status. The touchpad can also be used to program
the system in addition to arming and disarming
alarms.
N-750-APS: The N-750-APS is a notification and
auxiliary power expander that provides up to 2.5
amps of and 12 volt power for powering notifica-
tion appliances and auxiliary devices. The
N-750-APS uses the N-750 snap track located in
the N-750 cabinet or the N-750-ENC accessory
enclosure.
N-750-APS-24: The N-750-APS-24 is a notification
and auxiliary power expander that provides up to
6 amps of regulated, 24 volt power for powering
notification appliances and auxiliary devices. The
N-750-APS-24 provides its own AC power connec-
tion, battery charging circuit, and battery connec-
tions. Used with security and fire panels, the N-
750-APS-24 enables you to connect and distribute
power to many more devices than your panel may
normally allow.
N-750-BELL: The N-750-BELL module provides an
output for a bell sounding device to annunciate
alarms from the N-750 system.
N-750-BELL-SUP: TheN-750-BELL-SUPprovides
supervision of the N-750-BELL and is required for
UL applications.
N-750-COMM-CBL: The N-750-COMM-CBL is a 3'
RJ31X cord for connecting a phone line to the
built in digital communicator on the N-750. The
cable can also be used when the N-750-DPLM
dual phone line adapter is installed in the N-750.
N-750-DPLM: The N-750-DPLM provides a second
phone line connection. The N-750-DPLM includes
a line monitor and ring detector for a second line.
The N-750-DPLM is required for UL installations.
The N-750-DPLM connects and mounts directly to
the standoffs provided on the panel. Power: 11 to
14 VDC at 20 mA (active only), Temp: 32 to 120
F (0 to 49 C), Dimensions: 2.175"W x 2.375"H x
1.75"D (including mounts).
N-750-ENC: Standard N-750 size enclosure with an
2 snap tracks. Snap tracks are used to mount
accessories such as the N-750-APS and N-750-
SSE. Each enclosure can hold 4 accessories, as
well as 2 BAT-N-750s. Dimensions: 15"W x 20"H x
3"D.
N-750-EOL-UL-10: The N-750-EOL-UL-10 is a 10
pack of End-of-Line UL approved 4.7 k resistors.
The N-750-EOL-UL-10 is used for all hardwire
input zones on the N-750. (The N-750-EOL-UL-10
is not used with the N-750-SS, use the N-750-
EOL-UL-SS).
N-750-EOL-UL-SS: TheN-750-EOL-UL-SS End-of-
Line resistors are a 10 pack of 1.43K ohm resistors
for use with the N-750-SS. The N-750-EOL-UL-SS
is required for UL applications.

14
Version 1.0 October1997
N-750 Configuration Guide
N-750-GSM: The N-750-GSM is for a ground start
telephone system, and consists of a ground start
chip. Please note that a ground start module
cannot be used in UL applications.
N-750-INPT-CNCT: The N-750-INPT-CNCT is a
connector that plugs into the N-750-PAIT. This
allows for the input zones and output relay of the
N-750-PAIT to be connected. One unit comes
standard with each N-750-PAIT.
N-750-KOHP: The N-750-KOHP provide tamper
proof hole plugs for the N-750 enclosure. The N-
750-KOHP comes in a pack of 6 UL approved
knock out hole plugs.
N-750-PAIT: The N-750-PAIT is a commercial
touchpad that can be used as a door access
station. The N-750-ADM can be used in conjunc-
tion with the N-750-ADM for a total combination
of 24 devices. The N-750 system must have at
least one N-750-PAIT. The N-750-PAIT has 1
SPDT relay for door lock and 2 contact inputs for
door egress and status. The touchpad can also be
used to program the system in addition to arming
and disarming alarms and checking the status of
areas.
N-750-PI: The N-750-PI Serial/Parallel Module
provides one 9 pin RS-232 serial port and one
parallel printer port. Eight N-750-PIs can be used
per N-750. The N-750 can be used for either
connection to a PC directly using the CBL-N-750
or in conjunction with an M-9600 and CBL-2 for
remote communications.
N-750-RDR-CNCT: The N-750-RDR-CNCT is a 5
wire Wiegand connector that plugs into the N-
750-PAIT. This allows a Wiegand format reader to
be plugged directly into the N-750-PAIT. One unit
comes standard with each N-750-PAIT.
N-750-SK: The N-750-SK upload/download soft-
ware is for programming the N-750 system by the
installing dealer or central station. The software
programs partitions, zones, time windows, user
levels, system devices, and central station report-
ing accounts. Only one copy is required per
dealer. Each copy can support an unlimited
number of panels.
N-750-SLTP: The N-750-SLTP is an indoor/outdoor
touchpad with weather resistant housing. The N-
750-SLTP can be used to arm/disarm an N-750
system as well as used for door access as entry
only or in conjunction with a card reader for high
security with a combination card and pin number.
The touchpad has “READY” and “Armed” lights,
but there is no display screen. The N-750-SLTP
must be interfaced with the N-750-ADM. Current
Draw: 10 mA, Temp: 32 to 120 F (0 to 49 C),
Dimensions: 1.5"W x 6.37"H x .5"D.
N-750-SS: The N-750-SS SmartSensor is used in
conjunction with the N-750-SSE. The N-750-SS
connects to serial loops on the N-750-SS control-
ler module. N-750-SS SmartSensor point ID
modules allow connection to and point identifica-
tion of, most security devices. SmartSensor point
ID modules are addressed on-site using an N-750-
PAIT.
N-750-SSE: The N-750-SSE Serial Zone Expander is
a UL listed zone expansion system. The N-750-
SSE is used in conjunction with the N-750-SS
Smart Sensor. Each N-750 system can support a
total of 3 N-750-SSE expanders for a total of 384
points, with 128 points per N-750-SSE. Each point
on the N-750-SSE is addressed with an N-750-SS.
The N-750-SS does not have a built-in end-of-line
resistor, and the N-750-EOL-UL-SS resistor should
be used for all UL Smart Sensor applications.
N-750-TC: The N-750-TC transformer cover is a UL
rated outlet cover for a standard duplex outlet.
The N-750-TC is required for NFPA 71 and NFPA
72A fire alarm installations to protect class 2
transformer and power wiring to N-750 control.
Knockouts provided for 3/4" conduit. Dimensions:
3.625" W x 6.125"H x 2.5"D.
N-750-ZONE: The N-750-ZONE is a hardwire
expander that allows 64 zones to be added to the
N-750 system. A total of six N-750-ZONE mod-
ules can be added to the system (if no other zone
expansion device is being used).

N-750 Configuration Guide
15
Version 1.0 October1997
NOTES:

Headquarters:
5007 S. Howell Ave.
Milwaukee, WI 53207 USA
Northern Computers, Inc.
Leaders in Access Control Technology
Worldwide Locations
Canada United Kingdom Germany France Italy Russia Egypt Brazil Mexico Ecuador Argentina Hong Kong Australia Japan
Phone: (414) 769-5980
Fax: (414) 769-5989
http://www.nciaccess.com
Table of contents